Principle loop resistance
Measurement loop resistance
None of the devices (front-door station, indoor station
or extended function) should be further than 8 Ohm
away from the power supply and control unit!
Procedure for measuring:
Switch off the 230 V / 50 Hz of the power supply
and control unit.
Install a/b short-circuit at the power supply and
control unit.
Other devices are not disturbing the measure-
ment and can stay connected.
Measure the resistance at a/b at the strand of the
last indoor or front-door station. Remove the
short-circuit.
To measure the loop resistance at P/M proceed
in the same way as for a/b.
Rule for 8 Ohm:
Distance from TCS:BUS
®
power supply to the most
distant front-door or indoor station:
at
0.6 mm
wire diameter
max. 65 m
,
at 0.8 mm
wire diameter
max. 115 m
Optional accessory
Short text
Article number
name field foil
on request
colored foil red, green, blue, orange
on request
cleaning cloth for stainless steel
on request
ZAB ground anchor K3 post
ZAB3001-0002