W7622D
Triac Output Board
GENERAL
The W7622D Triac Output Board (“Triac Board”) is a Type F,
four-output accessory board that increases DeltaNet
MicroCel™ Controller (“M-CEL”) output from four to eight
using triacs as spst switches. Each M-CEL can use only one
output board. If an M-CEL has an output board, the Triac
Board can replace it.
Outputs can be used for standard on/off control. In sets of
two, they can be used to modulate Series 60 (floating) control
with on-time resolution as low as 10 ms.
Specifications:
Outputs
Four isolated triac (spst)
Maximum voltage
30V ac
Maximum current
0.5A steady, 4.0A surge
Minimum current
50 mA
Latching current
20 mA
Holding current
5 mA
Isolation
Each triac is isolated and can
be powered from separate or
common 24V ac or dc sources.
M-CEL models
R7515A3030, R7515B3004,
and R7516B3011 (Triac
Boards can only be mounted in
M-CELs that have a large
enclosure [7.9 in. long X 6.6 in.
wide X 4.95 in. deep, 201 X
167.6 X 125.8 mm])
INSTALLATION
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations.
�
Remove power from M-CEL. Remove metal cover.
CAUTION
If power is connected via screw terminals, you
MUST remove power
at its source rather than
removing each wire individually. Removing
individual wires can cause damage.
INSTALLATION INSTRUCTIONS
�
If an existing output board is in place, remove
the board:
a. Remove the two self-tapping screws and metal
standoffs that secure the board to the bracket.
b. Using a pair of needle nose pliers, compress
the tab of the white plastic standoff (located near
the center of the board) and, at the same time,
carefully rotate the board away from the screw
terminal bracket to free the 10-pin connector
located on the back of the board near its
bottom edge.
�
Starting with the Triac Board at an angle, align the
bottom part of the 10-pin connector to the 10 holes in
the bottom of the Triac Board. Rotate the Triac Board
toward the main bracket and allow the plastic standoff
to secure and center the board.
�
Using the two long self-tapping screws, as well as the
two metal standoffs, secure the Triac Board to the
terminal strip bracket.
�
Attach the new wiring label over the existing label on
the bracket.
�
Wire to the outputs with 18 AWG (0.8012 sq mm) wire.
See job drawings for specific wiring. See Wiring
Diagram (this sheet) for terminal locations.
�
After ensuring that there are no metal or wire scraps in
the M-CEL case, reconnect power and resecure cover.
Copyright © 1991 Honeywell Inc. • All Rights Reserved
95-7454