background image

W7622D 

Triac Output Board 

GENERAL 

The W7622D Triac Output Board (“Triac Board”) is a Type F, 
four-output accessory board that increases DeltaNet 
MicroCel™ Controller (“M-CEL”) output from four to eight 
using triacs as spst switches. Each M-CEL can use only one 
output board. If an M-CEL has an output board, the Triac 
Board can replace it. 

Outputs can be used for standard on/off control. In sets of 
two, they can be used to modulate Series 60 (floating) control 
with on-time resolution as low as 10 ms. 

Specifications: 

Outputs 

Four isolated triac (spst) 

Maximum voltage 

30V ac 

Maximum current 

0.5A steady, 4.0A surge 

Minimum current 

50 mA 

Latching current 

20 mA 

Holding current 

5 mA 

Isolation 

Each triac is isolated and can 
be powered from separate or 
common 24V ac or dc sources. 

M-CEL models 

R7515A3030, R7515B3004, 
and R7516B3011 (Triac 
Boards can only be mounted in 
M-CELs that have a large 
enclosure [7.9 in. long X 6.6 in. 
wide X 4.95 in. deep, 201 X 
167.6 X 125.8 mm]) 

INSTALLATION 

NOTE:   All wiring must conform to applicable local codes, 

ordinances, and regulations. 

  

Remove power from M-CEL. Remove metal cover. 

CAUTION 

If power is connected via screw terminals, you 
MUST remove power 

at its source rather than 

removing each wire individually. Removing 
individual wires can cause damage. 

INSTALLATION INSTRUCTIONS 

  

If an existing output board is in place, remove 
the board: 

a.   Remove the two self-tapping screws and metal 

standoffs that secure the board to the bracket. 

b.   Using a pair of needle nose pliers, compress 

the tab of the white plastic standoff (located near 
the center of the board) and, at the same time, 
carefully rotate the board away from the screw 
terminal bracket to free the 10-pin connector 
located on the back of the board near its 
bottom edge. 

  

Starting with the Triac Board at an angle, align the 
bottom part of the 10-pin connector to the 10 holes in 
the bottom of the Triac Board. Rotate the Triac Board 
toward the main bracket and allow the plastic standoff 
to secure and center the board. 

  

Using the two long self-tapping screws, as well as the 
two metal standoffs, secure the Triac Board to the 
terminal strip bracket. 

  

Attach the new wiring label over the existing label on 
the bracket. 

  

Wire to the outputs with 18 AWG (0.8012 sq mm) wire. 
See job drawings for specific wiring. See Wiring 
Diagram (this sheet) for terminal locations. 

  

After ensuring that there are no metal or wire scraps in 
the M-CEL case, reconnect power and resecure cover. 

Copyright © 1991 Honeywell Inc.  •  All Rights Reserved 

95-7454 

Reviews: