TCS Basys Controls SUPERSTAT SZW123 Product Manual Download Page 7

R

2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

7

Operation                              

 

unoCCuPieD SetBACK 

The SZW123 operates in either an occupied or unoc-

cupied mode. During the occupied mode, the occupied 

heating and cooling setpoints will be maintained, and the 

fan will operate according to its occupied setting. During 

the unoccupied mode, the unoccupied heating and cool-

ing setpoints will be maintained, and the fan will oper-

ate according to its unoccupied setting. The occupied 

LED will be lit when the unit is operating in the occupied 

mode. 
The occupied schedule may be set utilizing the internal 

Schedule Announcement Screen.  

Announces the next screen.  

 

 

 
occupied times Screen.  

Set hours 

and minutes of start and end times 

for up to two occupied periods.

occupied times Screen.  

Set hours 

and minutes of start and end times 

for up to two occupied periods.

 
Schedule Announcement Screen.  

Announces the next screen.  

 

  

Copy Schedule Screen.  

Indicate 

whether or not to use the same 

schedule that was used for the previ-

ous day.  If the same schedule is 

used, the following 2 screens are not 

displayed.

occupied times Screen.  

Set hours 

or minutes of start and end times for 

up to two occupied periods. 

occupied times Screen.  

Set hours 

and minutes of start and end times 

for up to two occupied periods.

 

A:08:00 TO 12:00

B:00:00 TO 00:00F

SET OCCUPIED

TIMES MONDAY: 

clock

setup

3.

4.

override

COPY MON FOR

TUE? 

 

 

 

NO

clock

setup

SET OCCUPIED

TIMES TUESDAY:

clock

setup

A:08:00 TO 12:00

B:00:00 TO 00:00

clock

setup

6.

7.

8.

override

C:00:00 TO 00:00

D:00:00 TO 00:00

clock

setup

5.

override

clock

setup

The following screens are repeated for 

Wednesday, Thursday Friday Saturday, Sunday.

C:00:00 TO 00:00

D:00:00 TO 00:00

9.

override

clock

setup

MON

12:00  AM                72F

main monitoring Screen.  

time clock or DI3 may be used with an external time 

clock, where- as when DI3 is closed, the unit is in the 

occupied mode. The Smart Recovery function is disabled 

when DI3 is used for external time clock. (This function 

uses a virtual DI, see Note on page 6 for details.) 

oVerriDe

A timed override is available using the button on the 

face of the thermostat or through momentary contacts 

wired into the OVR terminal. The amount of time the unit 

will be overridden is set from 0 to 255 minutes in the 

programming screen. This override behaves differently 

depending on the mode the thermostat is operating in 

(occupied or unoccupied) and the options that have been 

enabled within the software.
In standard mode, the override only activates in unoccu-

pied mode and takes the thermostat into occupied mode. 

If "Override for Occupied Period" is enabled using the 

software, the override also activates in occupied mode 

and takes the thermostat into unoccupied mode. In either 

case, you are able to view the time remaining in the 

override period both within the software and by using the 

service button to scroll through the status screens. If the 

occupant desires to return the thermostat to unoccupied 

or occupied operation (depending on how the override 

was used) before the override time remaining elapses, 

they may press the override button again.
Additionally, an "Override Hold" feature is built into the 

thermostats. When in unoccupied mode, pressing the 

override once and then pressing/holding it for 5 sec-

onds puts the thermostat into a "hold” mode (the over-

ride LED on the thermostat will flash quickly to confirm 

the mode change). In this mode, the override setpoints 

are used until the next occupied period is reached or 

until the thermostat is manually taken out of the "hold" 

mode by pressing the override button again. This feature 

also works when the "Override for Occupied Period" is 

enabled BUT starting from the occupied mode and hold-

ing the thermostat in the unoccupied state.
A continuous override is available through the DI3 con-

tact or the software. If DI3 is set to external override, the 

unit will be in the occupied mode whenever the DI3 con-

tact is closed. When using this option, the timed override 

may still be activated.

SetBACK AnD oVerriDe APPliCAtionS 

In most applications, it is desired to maintain a regular 

schedule, and allow timed override with the button on the 

face.
To allow a regular schedule, and also automatically over-

ride with the use of an occupancy or light sensor, set DI3 

to external override and set it up so that the contact is 

closed when you want the override.  (This function uses 

a virtual DI, see Note on page 6 for details.)
For applications where a room might not be used on a 

regular schedule, such as conference rooms, set DI3 to 

external time clock and close the contact when you want 

the room occupied, such as with a switch or wind-up 

Summary of Contents for SUPERSTAT SZW123

Page 1: ...it or Celsius temperature display Convertible to heat pump mode in programming Uses ZigBee protocol IEEE 802 15 4 compliant Self healing plug play mesh network 100mW output at 2 4 GHz 150 to 500 feet...

Page 2: ...the installation environment is free of electrical noise Sensor wire should be kept at least five feet away from line voltage wiring The SZW123 accepts three Consult the TS Series Temperature Sensor S...

Page 3: ...outdoor air sensor only Using remote room sensor with both discharge and outdoor air sensors Keypad Access The dipswitches in the thermostat cover shown above must be set in order to lock the user out...

Page 4: ...K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and CELSIUS for tem perature indication Controller Type Screen Choose Conventional or Heat Pump mode Unit will reset the screen will mome...

Page 5: ...for dipswitch settings which must also be set Discharge Air Low Limit Screen Enter a discharge air low limit value This screen will not appear if the discharge air sensor function is disabled Discharg...

Page 6: ...ot be changed Main Monitoring Screen HEAT PUMP MODE CONVERSION TABLE Cool 1 Becomes Compressor Heat 1 Becomes Reversing Value Everything else not mentioned here remains same as if it is in conventiona...

Page 7: ...overridden is set from 0 to 255 minutes in the programming screen This override behaves differently depending on the mode the thermostat is operating in occupied or unoccupied and the options that ha...

Page 8: ...to pro tect equipment on fan failure To utilize this function input a pressure or current switch which tells when the fan is running If the thermostat closes its fan contact and the DI1 is not closed...

Page 9: ...the next stage is allowed to turn on as well as when one stage turns off until the next stage is allowed to turn off DELAY ON POWER UP The SZW123 has an adjustable delay on power up When several ther...

Page 10: ...prob lems poor connections opens or shorts If the tem perature is at a minimum or maximum reading check that the sensor dipswitch positions are correct as shown in the Setup section of this document A...

Page 11: ...nge the occupied heating and cooling setpoints 5 F by factory default This setpoint change will remain until the end of the current occupied period at which time the program reverts to the setpoints d...

Page 12: ...controllers are communicating 5 If any controller s is are not communicating it may require a QW1011 wireless repeater nearby to connect to the ZigBee network 2800 LAURA LANE MIDDLETON WI 53562 800 28...

Page 13: ...multi device supports up to 32 hard wired controllers devices SW Superstat Series ZigBee wireless thermostat SZ10xxW series SW133 ZigBee wireless thermostat SW244 ZigBee wireless unit board Input SZ...

Reviews: