8. Design and Installation of Connecting Pipes
8.1. Pipe length and drop height shall comply with the scope required below.
Mode
18K
24K
Max pipe length
30m
35m
Max drop height l
15m
20m
Max bending No.
5
5
The refrigerant shall be
increased while the
22g/m
65g/m
mounted pipe is more
than the standard piping
Mode
36K
48K
60k
Max pipe length
50m
50m
50m
Max drop height l
30m
30m
30m
Max bending No.
5
5
5
The refrigerant shall be
increased while the
50g/m
50g/m
50g/m
mounted pipe is more
than the standard piping
Note: A return oil elbow must be equipped for each drop of 10m in the vertical height of
refrigerant pipe!
Connection Mode
Gas Side
Liquid Side
Outdoor Unit
Flare nut
Flare nut
Indoor Unit
Flare nut
Flare nut
8.2. Material and Size of the Pipes
Outdoor pipe dimension and installation modes (in sequence of cooling capacity)
Pipe material
Copper Pipe For Air Conditioner
Model
18‐‐22K
23‐‐28K
30‐‐48K
49‐‐60k
Size(mm)
Liquid side
Φ6.35(1/8inch)
Φ9.52(3/8inch)
Φ9.52(3/8inch)
Φ9.52(3/8inch)
Gas side
Φ12.7(1/2inch)
Φ15.88(5/8inch)
Φ19.05(3/4inch)
Φ19.05(3/4inch)
67
/
113
Summary of Contents for TCA-18HRA/DVO
Page 1: ...Technical Manual for DC Inverter Air Conditioner 1 113...
Page 13: ...DC Inverter Air 1 4 Electrical Wiring Diagram 13 113...
Page 14: ...DC Inverter Air 1 5 Air Velocity and Temperature Distributions Airflow velocity 14 113...
Page 22: ...DC Inverter Air 22 113...
Page 28: ...DC Inverter Air 2 3 Service Space 2 4 Wiring Diagrams 28 113...
Page 41: ...DC Inverter Air 3 2 Wirin g Diagra ms 41 113...
Page 42: ...DC Inverter Air A irflow velo city Discharge angle 60 FLOOR 42 113...
Page 43: ...DC Inverter Air Airflow velocity Temperature 43 113...
Page 64: ...DC Inverter Air 7 2 Electrical Wiring Diagram 2 1 TCA 36HRA DV 64 113...
Page 65: ...DC Inverter Air 2 2 TCA 48H RA DV3 TCA 60HRA DV3 65 113...
Page 66: ...DC Inverter Air 2 2TCA 18HRA DVO TC A 24HRA DVO 66 113...
Page 82: ...DC Inverter Air 82 113...