TXP Inst. & Maint. Manual: IM-825
41
WARNING!
Incorrect parameterization
of the inverter
If inadmissible parameters
are set at frequency or
speed, this leads to motor
overload and/or destruction
of the fan. There is a risk of
personal injury.
Use only the infor-
mation on the perfor-
mance plate
Connect the tempera-
ture sensors at the in-
verter inputs
Please keep the infor-
mation in the manufac-
turer's documentation
from the frequency in-
verter
Important information about
acceleration and deceleration
In order to avoid high component
loads and malfunctions in inverter
operation, the following times ap-
ply for the respective device en-
gine power class (see name-
plate) in the event of a ramp/run
as well as a change in speed for
the respective device engine
power class (see nameplate):
Device
engine
power
Accelera-
tion Time
[s]
Deceler-
ation
Time [s]
0.34 HP <
power
<=4.0 HP
10
20
4.0 HP <
engine
20
40
Device
engine
power
Accelera-
tion Time
[s]
Deceler-
ation
Time [s]
power <=
10 HP
10 HP <
engine
power <=
14.8 HP
30
60
14.8 HP <
engine
power <=
40.2 HP
30
60
Table 8: Acceleration and Deceleration
Times
Within the acceleration and deceleration
times, a steady rise and fall must be
guaranteed.
During operation, no speed changes
may occur that exceed the speed
change during the acceleration and de-
celeration.