background image

IM-5500

Installation, Operation & Maintenance Manual

10

      

*Suggested lubrication interval under continuous operation in adverse loading or with 

elevated temperatures. For operation less than 24 hours per day or under ideal conditions, 

lubrication frequency may be reduced. Relubricate while running, if safety permits, until 

some purging occurs at seals. Adjust lubrication frequency depending on condition of 

purged grease. Hours of operation, temperature and surrounding conditions will affect the 

relubrication frequency required.
1.  Lubricate with a high quality NLGI No. 2 lithium-base grease having rust inhibitors and 

antioxidant additives, and a minimum oil viscosity of 500 SUS at 100°F (38°C). Some 

greases having these properties are:

   

Shell - Gadus S2 V100 2 

Mobil - Ronex MP 

 

Mobil - Mobilith SHC100 

Mobil - Mobilith SHC220

2.  Lubricate bearings prior to extended shutdown or storage and rotate shaft monthly to aid 

corrosion protection.

Fans with Ball Bearings

Relubrication Schedule (Weeks)*

Ball Bearing Pillow Blocks

Shaft DIA

Speed (RPM)

500

1000 1500 2000 2500 3000 3500 4000 4500

3

4

" (19 mm)

6

6

5

3

3

2

2

2

1

1.  This equipment must not be operated without proper guarding 

of all moving parts. While performing maintenance be sure 

remote power switches are locked off. See installation manual 

for recommended safety practices.

2.  Before starting: Check all set screws for tightness and rotate 

impeller by hand to make sure it has not moved in transit.

WARNING

Safety & Bearing Lubrication Instructions

Twin City Fan

Fan Bearing Maintenance 

(refer to safety section)

Proper lubrication of the fan drive bearings helps assure maximum bearing life. All fans are equipped with decals indicating the 

recommended relubrication intervals for normal operating conditions.

The standard pillow block bearings on belt driven ventilators are factory lubricated and are provided with external grease fittings. 

Annual lubrication is recommended, or more frequently if needed (see 

Greasing Intervals

 table). It is recommended to add fresh grease 

at start-up, but do not over-grease. Use only 1 or 2 shots of a recommended lubricant with a hand gun in most cases. Maximum hand 

gun rating 40 P.S.I. Rotate bearings during lubrication where good safety practice permits. The most frequent causes of bearing failure 

are not greasing often enough, using an excessive quantity of grease or using incompatible greases. Excessive vibration, especially if 

the bearing is not rotating, will also cause bearings to fail. Bearings must also be protected from water and moisture to avoid internal

corrosion.

During the first few months of operation it is recommended that the bearing set screws be checked periodically to ensure that they are 

tight. The rotating impeller requires particular attention since materials in the air being handled can build up on the blades to cause 

destructive vibration or weaken the structure of the impeller by corroding and/or eroding the blade metal. Regular inspection and 

corrective action at intervals determined by the severity of each application are essential to good service life and safety.

Suggested Fan Bearing Greasing Intervals

INTERVAL 

(MONTHS)

TYPE OF SERVICE

12 to 18

Infrequent operation or light duty in clean atmosphere

 6 to 12

8 to 16 hrs./day in clean, relatively dry atmosphere

 3 to 6

12 to 24 hrs./day, heavy-duty or if moisture is present

 1 to 3

Heavy-duty in dirty, dusty locations; high ambient 

temperatures; moisture-laden atmosphere; vibration

Greases of different soap bases (lithium, sodium, etc.) may 

not be compatible when mixed. Prevent such intermixing 

by completely purging the bearing of old greases.

CAUTION

EC Motor Information

See IM-4055 for EC motor details.

Summary of Contents for IM-5500

Page 1: ...in nature Additional product and engineering information is available at www tcf com REVIEW AMCA BULLETIN 410 PRIOR TO INSTALLATION Table of Contents Exploded View 2 Fan Overview Impeller Rotation an...

Page 2: ...ing Bird Screen Impeller Shroud Curb Cap Vent Tube Drain Support Brackets Horizontal Support Post Vertical Support Post Upblast Exhaust Fan Models VCU VCUB Downblast Exhaust Fan Model VC Motor Cover M...

Page 3: ...offer a broad range of end use applications and should be carefully integrated to provide best use Upblast direct drive fans are available with nominal impeller sizes from 8 5 to 19 7 and belt driven...

Page 4: ...processes that are hot the fan housing could be hot Sharp edges wear protective gloves when handling installing or servicing a fan Fans can operate at high decibel sound levels Wear proper ear protect...

Page 5: ...VCU fans All Sizes Fans may be lifted using hooks around the four 4 horizontal support posts with a minimum of four lifting straps with spreader bars to ensure that no contact is made with the motor...

Page 6: ...ith the bearing manufacturer s instructions The drives and belts should be removed if the fan is to be stored for a prolonged period The drives should be labeled for service and stored in a dry place...

Page 7: ...r details 3 Perform fan pre check See Check Test Start Procedure section for a full checklist 4 Perform installation of any externally mounted accessories that were shipped loose with the fan 5 Remove...

Page 8: ...e made by sliding the idler pulley along the groove to either tighten or loosen the belt See image to the right c Verify the RPM of the impeller Adjustment can be made via the variable speed sheave at...

Page 9: ...res are required it may be necessary to increase wire size to prevent excessive voltage drop Wires should be sized for a maximum of 3 voltage drop 4 Disconnect switches are not fused The power leads m...

Page 10: ...g conditions The standard pillow block bearings on belt driven ventilators are factory lubricated and are provided with external grease fittings Annual lubrication is recommended or more frequently if...

Page 11: ...line voltage 115V only Never connect across line See Connection Diagrams Minimum Speed Setpoint All controls are factory set to 65V 3V output as standard with an input voltage of 120V If different mi...

Page 12: ...essary to adjust belt tension do not over tension as bearing damage will occur Recommended belt tension should permit 1 64 deflection per inch of span of the belt at the center of the belt span To fin...

Page 13: ...ths is suggested 3 All motors supplied with Twin City Fan Blower ventilators carry a one year limited warranty from date of shipment For repairs within the warranty period the motor must be taken to t...

Page 14: ...les on the curb hinge to the holes on the curb cap This should be on the opposite side of the drain A B Step 2 Insert provided screws to affix the hinge to the curb cap Step 3 Place and install fan on...

Page 15: ...ex 4 Security Hasp Hinged Step 1 Drill 4 0 19 holes on center curb cap from either corner Step 2 Attach the hasp to the curb cap by using the included 10 hardware Step 3 Drill 4 0 19 holes on center o...

Page 16: ...of curb base Step 2 Attach chain to outside of curb base with bolt head on inside of curb base Step 3 Use one flat washer under bolt head and one on top of chain Step 4 Use remaining fasteners to atta...

Page 17: ...ping screws that are fastened to the support post Step 2 Drill holes and install firestat Holes must be near a support post Note The hole drilled in the motor housing must be close to in line with the...

Page 18: ...ce the insect screen between the fan inlet and the roof or roof curb Fasten with screws or nails if desired Twin City Fan Performance Baffle Installation Step 1 Place the performance baffle between th...

Page 19: ...g sheet metal screws Roof curbs come with damper trays Grease Box Installation Step 1 Fasten the grease box to the curb cap under the drain using supplied hardware Parts Included Grease Box Cover Grea...

Page 20: ...erate noise 4 Poor fan inlet conditions 5 Acoustics or sound measurement procedure incorrect Vibration Problems 1 Poor foundation or mounting structure resonances 2 Foreign material attached to rotati...

Page 21: ...n Check Inspect fan for damage Are the bolts tight Fan Impeller Impeller overlap checked Fasteners tight Impeller rotates freely Bearings Bearings aligned Bearings greased Note Rotate while greasing S...

Page 22: ...M 5500 Installation Operation Maintenance Manual 22 Date Completed Maintenance Performed By Comments Model Number __________________________ Serial Number __________________________ Fan Maintenance Lo...

Page 23: ...nstallation Operation Maintenance Manual IM 5500 23 Date Completed Maintenance Performed By Comments Model Number __________________________ Serial Number __________________________ Fan Maintenance Lo...