TB Controls TC02 Operation & Maintenance Manual Download Page 8

 

Operations & Maintenance Manual

 

January 2002

 

Doc: TC02 O&M

 

Page 8 of 20

 

Status: 

Final

 issue: 11 

 

©TB Controls 2011 

 

4. 

Master / Slave 

 

Where several controllers are operating in the same space, they must be synchronized via 
the Master / Slave interface.  
 

  Up to 8 slaves may be used (further options available) 
  The operating parameters are passed via the data bus (LON) 
  Up to 8 control plates may be used. 
  Single Belden 8723 cable connects slaves and control plates 

 
To set the unit to slave mode; 
 

  Switch Dipswitch 8 to ON 
  Master Unit will require Dipswitches 9 and 10 switched to ON and 8 to OFF   
  Dip  Switch  9  and  10  are  the  Terminating  resistors  for  the  LON  network  on  the 

Belden 8723 cable 

  The  Slave  Address  on  the  LON  is  set  using  Dip  switches  1,  2,  and  3  giving  8 

combinations addresses 0 to 7. The switches are set using Binary, (see notes on 
setting switches). Each slave unit in a group must have a different address. 

  The Slave will follow all settings of the Master 
  Each slave will report its faults to the Control Plate. 
  Any unit may be set to a Master to suit site conditions; this must be the only Master 

unit of the group. 

  Return air and Off coil temperature sensors are local to each unit 
  Outside  air  temperature  sensor  is  connected  to  the  Master  this  input  controls  all 

slave units. 

  BMS time switch control signal must be wired to the Master this input controls all 

slave units. 

 

4.1. 

Phased Start Sequence 

 
The  TC02 is designed for soft start,  this avoids  large numbers of  fan decks switching on 
simultaneously causing electrical overload or tripping of circuit breakers due to very large 
starting currents, each unit has a delay 

of „x‟ mS. on power up. 

The phased start is set  using the Dipswitches 1 to 7. The switches are set  using Binary, 
(see notes on setting switches) 
 

4.2. 

Controller Start sequence 

 
The  TC02  has  a  green  LED  on  board.  This  LED  will  flash  three  times  on  power  up  and 
afterwards will flash for 20mS every second. Three flashes, flash, flash, flash, indicates the 
unit has self tested and is OK. Regular flashing indicates unit is running OK 
 
 

Summary of Contents for TC02

Page 1: ...B U I L D I N G C O N F I D E N C E TC02 Curtain heater controller Previously known as the mini FCU Operations Maintenance manual TBControls 2011...

Page 2: ...ONTROL PLATE UNIT 6 3 1 TC02 Connections 7 4 MASTER SLAVE 8 4 1 Phased Start Sequence 8 4 2 Controller Start sequence 8 4 3 Error Messages 9 4 3 3 Master 9 4 3 4 Slave Messages 9 4 4 LCD Modes 9 4 4 5...

Page 3: ...user interface to be locked Requested by Diffusion TC02 firmware V3 23 8 16 July 08 Final MODBUS BMS interface details LON comms error for slave device added Return air sensor now NOT required on slav...

Page 4: ...s The curtain heater controller unit has the following features Powered from 12 24 volts AC or DC Four fan speed settings with silent fan speed switching Controlled by four snubberless triacs with hea...

Page 5: ...230 VAC lamps as in the Ambassador unit On board real time clock for timed operation and event log time stamping Log of the last 500 system events Fan speed monitoring input to detect fan motor failur...

Page 6: ...height is 5mm 3 mm fixing screws are recommended Push over type plastic stand offs may be used if it eases production The following points should be noted The controller should be freely accessible a...

Page 7: ...re A RS485 black wire B RS485 shield in RS485 shield out RS485 jumper on shield out 24VAC feed Actuator drive open 24VAC feed 24VAC common 0v Earth Actuator drive closed Fan speed common output Fan sp...

Page 8: ...ll settings of the Master Each slave will report its faults to the Control Plate Any unit may be set to a Master to suit site conditions this must be the only Master unit of the group Return air and O...

Page 9: ...s the heating will be turned off The display will read Off Coil Sensor Fault Where the Return Air Temperature sensor fails the heating will still be functional The display will read Return Air Sensor...

Page 10: ...xx C Range 10 to 70 C Default 18 C Winter Off Coil Setpoint is displayed as Winter OC xx C Range 10 to 70 C Default 40 C Summer Return Air Setpoint Trip is displayed as Summer Ret xx C Range 40 to 40...

Page 11: ...en for Summer mode and closed for Winter mode BMS 0 10v fan input if enabled ENA the fan speed is taken from a 0 10v signal on the fan speed analogue input see 3 1 The fan speeds are set as follows Fa...

Page 12: ...after 30 seconds of inactivity ie no buttons pressed 4 4 7 User Mode User display mode default display when powered up will be Fan Status it will read Fan Off or Fan Speed x on the top line and Mode...

Page 13: ...oil and Return Air sensors only fitted will result in the temperature of the air leaving the supply grill being controlled to the given set point for Summer or Winter modes however when the return air...

Page 14: ...1 Default Set points Setpoints 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Outside temperature C temperature C off coil setpoint retu...

Page 15: ...New Look Mode Set points DIP 5 on 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 temperature C Outside temperature C Setpoints off coil setpoint r...

Page 16: ...64 Sw8 128 Using various combinations of switches to on the requires address up to a decimal value of 255 may be set see next illustration Dipswitch Settings Switch ON position Switch Number 1 2 3 4 5...

Page 17: ...5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8...

Page 18: ...7 1 Fitting the sensor For best results locate the sensor on the north side of the structure high under an eave This prevents incorrect readings due to direct sunlight and damage from the elements Mo...

Page 19: ...Default 16 C R W 9 Winter Return Air Set point Trip range 10 to 40 C Default 25 C R W 10 Summer Outside Air Set point range 5 to 40 C Default 20 C R W 11 Winter Outside Air Set point range 5 to 40 C...

Page 20: ...his may either be the main BMS system holding the units off or the N O or N C may need to be altered The contacts can be altered by accessing the engineering mode Should units be master slaved it will...

Reviews: