33
3
CM
ISM
Earthing point for cables shields
and CM-earth connection
Actuator cable
Lapp Ölflex classic 110 CY
2 x 1.5 mm² (or equivalent)
2)
ISM auxiliary switch cable
1)
Lapp Ölflex classic 110 CY
2 x 1.5 mm² (or equivalent)
2)
Closing lock-out contact cable
1)
Lapp Ölflex classic 110 CY
2 x 1.5 mm² (or equivalent)
2)
Closing lock-out contact
(optional)
1
2
3
4
5
6
7
1)
For ISM auxiliary switch cable and closing lock-out cable the cross section
chosen can be 0.5 mm² minimum. This switch is not used with the CM_16.
2)
The degree of coverage of the cable shield shall not be less than 85%.
The cables are fixed with a special
screwdriver supplied with every
ISM and CM (Figure 54). Solid or
multi-wire cables with or without
sleeves with a cross section of
0.5 to 2.5 mm² can be connected
to the terminals. The bare ends of
the cables shall be 8 to 9 mm.
Figure 52
Figure 53
Ins tallation of Secondary Cables Between ISM and CM: All Models
In the high voltage compartment it is recommended to install secondary shielded cables between the ISM and CM
in an earthed metal hose or an enclosed metal duct.
ISM auxiliary switch
Actuator coil
1 2 3 4 5 6 7 8 91011121314
XT1
SC1 SC2
151617181920212223242526 2728
AS
1
AS
2
XT2
XT1
XT2
10 1112
X1
X2
10 1112
4
3
5
6
7
1
2
Unshielded parts of wires to earth point and to CM must be kept
as short as possible (max. 10 cm).
Earthing point as near as possible at CM.
Unshielded parts of wires to ISM must be kept as short as possible
(max. 10 cm).
3
Note CM_12 series control shown. CM_1501 and CM_16 series pinouts can be seen on pages 28 and 29 of Chapter 3.
CM_16 series does not utilize the auxiliary switch on the ISM.
Summary of Contents for ISM15_LD_1 Series
Page 2: ......
Page 6: ...6 1 Introduction 1...
Page 11: ...11 2 Receiving Handling and Storage...
Page 17: ...17 Ins tallation 3...
Page 34: ...34 4 Switching and Control Functions 4...
Page 38: ...38 5 Commiss ioning Operation Maintenance 5...
Page 41: ...41 6 Signalling 6...
Page 45: ...45 6 Product Line 6...
Page 47: ...47 7 Dimens ions and Weights 7...
Page 53: ...53 8 Circuit Diagrams 8...
Page 54: ...54 ISM_LD with CM_16_1 Control Module 8...
Page 55: ...55 8 ISM_LD with CM_1501_01 Control Module...
Page 56: ...56 9 Technical Data 9...
Page 62: ...62 9 9...
Page 63: ...63 10 Regulations and Ambient Conditions 10...
Page 65: ...65 11 Legal Information 11...
Page 69: ...69 11 Date...