  6. TERMINAL BOARD CONNECTIONS

Terminals

Function

Description

1 + 2

POWER SUPPLY

POWER input 230/115 V AC 50-60 Hz. 1= NEUTRAL 2= PHASE;

3 + 4

FLASHING LIGHT

FLASHING LIGHT output 230/115 V AC, max. 50 W. The signal is already modulated for direct use; fast flashing 

during closing, slow during opening. 3= 230/115 V AC, 4= 0 V AC;

5 - 6

LED 

FLASHING LIGHT

FLASHING LIGHT Output FLASHING 12 VDC. Intermittent output during the operation, the flashing frequency is 

doubled during closing;

7 + 10

OPEN/CLOSE

OPEN/CLOSE input (Normally Open contact);

8 + 10

STOP

STOP input (Normally Closed contact);

9 + 10

PHOTOCELLS

PHOTOCELLS OR SAFETY DEVICES input; active during closure (Normally Closed contact); the automation will 

stop during closing and totally reopen it, (10= Common). If there is more than one safety device, connect all the 

NC contacts 

IN SERIES

.

11 + 12

24V AC

PHOTOCELLS

24 V AC 10 W output to Photocells, Receivers etc.; connect a up to 3 pair of photocells. 11= 0 V AC, 12= 24 V AC;

13 + 14

AERIAL

433,92 MHz built-in RX aerial input; 13= EARTH, 14= SIGNAL;

M2

MICRO SWITCH

Quick coupling for MICRO SWITCH connection (Normally Closed contacts). ORANGE= Micro Switch  deceleration 

in the closing maneuver

 

(CLS)

, RED= Micro Switch Deceleration in the opening maneuver 

(OLS)

, GREY= Common 

(COM)

;

FS1 + FS2

CAPACITOR

CAPACITOR Terminals for motor start-up;

M3

MOTOR

Quick coupling for 230 V AC single-phase MOTOR connection. BLUE= common 

(M-COM)

;

BROWN= closing 

(M-CL)

; BLACK= opening 

(M-OP)

.

J4

APP

quick plug-in for device connection for APP operation (mod. T-WIFI / T- CONNECT)

SM

MEMORY CARD

 quick plug-in for MEMORY CARD connection for transmitters codes.

  7. TRIMMER ADJUSTMENTS

FR.

Motor torque adjustment. 

Turning the trimmer clockwise (+) the torque will be increased; Turning the trimmer counterclockwise (-) 

the torque will be decreased.

Note: The trimmer is set to provide sufficient thrust to work the automation within the limits established by current 

standards (EN 12453).

SENS.

It allows you to adjust the detection sensitivity of the mechanical limit switches. By turning the trimmer clockwise (+) the detec

-

tion of the limit stop will be more sensitive. On the contrary, by turning counterclockwise (-) the sensibility will decrease. With 

the trimmer in the minimum position, the motor will remain powered for the total time set by the dip switch n° 6 even though 

the mechanical limit switch has been already reached. It is therefore necessary to adjust it correctly to avoid motor overheating.

T.C.A.

Automatic closing time adjustment. 

Turning the trimmer clockwise (+) time will be increased; Turning the trimmer counterclockwise 

(-) the time will be decreased.

Note: The time values can be set between 1 and 120 seconds.

   8. LIMIT SWITCH ADJUSTMENT

The microswitches control the deceleration of the barrier both during closing and opening maneuvers. Adjust the limit switch cams at the point 

where you want the barrier to start the deceleration in both opening and closing maneuvers.

  9. DIP SWITCH

1

AUTOMATIC

CLOSING

On

automatic closing enabled.

Off

automatic closing disabled.

2

2 / 4 STROKE

On

(with Automatic closing enabled) Two-Stroke operation mode OPEN-CLOSE, OPEN-CLOSE, etc

.

Off

(with Automatic closing enabled) Four-Stroke operation mode OPEN-STOP-CLOSE-STOP, OPEN-STOP-CLOSE-

STOP, etc

.

3

NO REVERSE

On

the 

automation

 ignores the close command while it is opening (NO REVERSE)

;

Off

the 

automation

 behaves according to the position of dip-switch n° 2;

4

OPENING

DIRECTION

On

Left-hand leaf opening mode;

Off

Right-hand leaf opening mode;

5

NOT USED

Off

keep it in the OFF position

6

OPERATING RANGE

On

8 seconds for RBLO-LE

Off

4 seconds for RBLO-E

  10. SETUP STROKE PROCEDURE

It is not required to memorize the stroke because the control unit uses the working times. With the dip switch n° 6 set the desired working time 

based on the type of the barrier used (RBLO-LE/ RBLO-E).

The motor will be powered for the entire duration of the set time, regardless of whether the mechanical limit switches have been reached.

If the set time is higher than the actual time taken by the automation to open or to close you will have to adjust the Trimmer SENS so you can 

allow an early stop once the mechanical limit switch has been reached.

Summary of Contents for K101M

Page 1: ... 8 9 10 11 12 13 14 1 2 3 Neutral 230 V AC Power supply Phase M OP CLS OLS COM FS1 FS2 M COM M CL 4 RADIO OP CL RESET DL3 DL4 DL5 DL6 DL2 DL1 1 2 3 4 5 6 1 2 3 4 5 6 Flashing light 230 V AC max 50W Flashing light VLED DC Open Close Stop Antenna Dip switches ON M2 J4 SM M3 DL3 DL4 DL5 DL6 DL2 DL1 PHOTO CLOSE LIMIT SWITCH OPEN LIMIT SWITCH STOP OPEN CLOSE RADIO CONTROLS TCA SENS FR Photocells Common...

Page 2: ...ATO DA LEDs PROTEZIONE INGRESSO LINEA CON FUSIBILE CIRCUITO DI LAMPEGGIO INCORPORATO RADIO RICEVITORE 433 92 MHz INTEGRATO TEMPO DI LAVORO FISSO max 40 sec RILEVAMENTO AUTOMATICO DELLA FREQUENZA DI ALIMENTAZIONE 50 o 60 Hz RALLENTAMENTO REGOLABILE COMPATIBILITÁ CON L APP TAUOPEN E TAUAPP ATTENZIONE In caso di lunghi tratti di cavi 20 m per i comandi N A N C es APRE CHIUDE STOP PEDONALE ecc al fine...

Page 3: ... trimmer in senso orario la rileva zione del fermo di battuta fine corsa sarà più sensibile Viceversa ruotando in senso antiorario diminuirà la sensibilità Con il trimmer nella posizione minima il motore rimarrà alimentato per il tempo totale impostato dal dip switch 6 nonostante l accostamento al finecorsa meccanico avvenga precedentemente È pertanto necessario regolarlo correttamente per evitare...

Page 4: ...CH2 in questo caso il led DL8 si accende con colore rosso 8_ se si desidera uscire dalla modalità di apprendimento senza memorizzare un codice premere brevemente il tasto CH1 o il tasto CH2 Nel caso di raggiungimento del nr massimo di radiocomandi nr 30 il led DL8 lampeggia velocemente per circa 3 secondi senza però eseguire la memorizzazione PROGRAMMAZIONE REMOTA TRAMITE T 4RP e K SLIM RP S 2RP S...

Page 5: ...emuti i tasti CH1 e PROG fino a che i led DL7 e DL8 iniziano a lampeggiare velocemente entrambi in giallo A questo punto rilasciare i tasti e premerli nuovamente fino a che i led si spengono a conferma che l operazione è terminata se non vengono premuti e si resta in attesa la scheda ritorna in funzionamento normale dopo circa 12 secondi RESET DI FABBRICA tenere premuti i tasti CH2 e PROG fino a c...

Page 6: ... 6 5 8 9 10 11 12 13 14 1 2 3 Neutral 230 V AC Power supply Phase M OP CLS OLS COM FS1 FS2 M COM M CL 4 RADIO OP CL RESET DL3 DL4 DL5 DL6 DL2 DL1 1 2 3 4 5 6 1 2 3 4 5 6 Flashing light 230 V AC max 50W Flashing light VLED DC Open Close Stop Antenna Dip switches ON M2 J4 SM M3 DL3 DL4 DL5 DL6 DL2 DL1 PHOTO CLOSE LIMIT SWITCH OPEN LIMIT SWITCH STOP OPEN CLOSE RADIO CONTROLS TCA SENS FR Photocells Co...

Page 7: ...N CONTRACT TORT OR ANY OTHER LEGAL THEORY DURING THE COURSE OF THE WARRANTY OR AT ANY TIME THEREAFTER 2 CONTROL PANEL FOR 230 V ac BARRIER MICROPROCESSOR CONTROLLED LOGIC STATUS LEDS LINE FUSE BUILT IN FLASHING LIGHT CIRCUIT BUILT IN 433 92 MHz RADIO RECEIVER MAX OPERATING TIME 40 AUTOMATIC 50 60 HZ FREQUENCY DETECTION ADJUSTABLE SOFT STOP COMPATIBILITY WITH OUR APPS TAUOPEN AND TAUAPP ATTENTION I...

Page 8: ...mechanical limit switches By turning the trimmer clockwise the detec tion of the limit stop will be more sensitive On the contrary by turning counterclockwise the sensibility will decrease With the trimmer in the minimum position the motor will remain powered for the total time set by the dip switch n 6 even though the mechanical limit switch has been already reached It is therefore necessary to a...

Page 9: ...y for about 3 seconds but with out performing memorisation REMOTE PROGRAMMING BY MEANS OF T 4RP K SLIM RP S 2RP S 4RP V 4 X With the new version of software V 4 X it is possible to carry out the remote self learning of the new version of transmitters T 4RP K SLIM RP S 2RP S 4RP V 4 X that is without pressing the receiver s programming buttons It will be sufficient to have an already programmed tra...

Page 10: ...ance with European Directive 2006 42 EC App II B Manufacturer TAU S r l Address Via E Fermi 43 36066 Sandrigo Vi ITALY Declares under its sole responsibility that the product Electronic control unit designed for automatic movement of Road barriers for use in a General environment complete with Radioreceiver Model K101M Type K101M Serial number see silver label Commercial name Control panel for aut...

Page 11: ...11 ...

Page 12: ...Via Enrico Fermi 43 36066 Sandrigo VI Italy Tel 39 0444 750190 Fax 39 0444 750376 info tauitalia com www tauitalia com ...

Reviews: