Warnings 

Strict Prohibitions 

Checkpoints 

Do not install the detector in the following locations! 

Water Leakage Detector 

AD-AS-1AM

 

 

Instruction Manual 

 

We thank you for using our Model AD-AS-1AMWater Leakage Detector. 
Be sure to read the following instructions before installing, adjusting and using the detector. 
 

 
 
 

  Use  the  detector  in  a  working  environment  with  a  temperature  range  between  -10˚C,  and  50˚C  and  a 

humidity range between 35%RH and 85%RH. 

 Avoid using the detector near sources of vibration, harmful gas, or strong electromagnetic induction. 

 For connection to the power supply, avoid using receptacles (sockets); use fixed wiring connection. 

 Use our products for sensors and break detection terminals (excepting AD-LS sensors and ZT-L2 

products). 

 Be sure to affix the insulating sheet to the terminal block, fix the outer cover and check detector operation. 

 Smoke or abnormal sound occurrence with the power indication LED turned off indicates detector failure. 

Switch off the main power breaker, stop using the detector and contact us. 

 
 
 
 

 Check at least once every six months to confirm that detector is operating normally. At the same time, 

check to see that screws on different parts of the detector are tightened properly. 

 Be careful of water-repellant substances, such as oil, adhering to sensor surface and interior; this may 

interfere with correct detector operation. 

 If a sensor is stained with dirty water, replace it with a new one. 

 
 
 
 
This detector is delivered to customers after strict quality control and inspection. Should it fail under normal 
usage, we will repair it free of charge or replace it during the warranty period (within one year of delivery). 
* Detector failure due to natural disaster, fire, unauthorized repair, dropping or damage after purchase is not 

covered by the warranty. 
Ask place of purchase for the guarantee document. 
When asking for the guarantee document, provide detector serial number (indicated on label on right-side 
face of the right-side terminal block). 

 
 
 
 
 
 
 
 
 
 
 
 

Handling Method 

 Typical Configuration of Water Leakage Detection System   

* Using vinyl tape or similar material, insulate the connections of water leakage sensor break detection 

terminals and instrumentation wires (it is recommended that they be housed in a box.), and fix them at a 
location above the floor to keep them from getting wet. 

 
 
 
 
 
 
 
 
 
 
 

 Operating the Detector and Checking Detector Operations 

 
 
 
 
 
 
 
 
 
 
 
 

 Checking power-on 

Power-on causes the power indicator LED (yellow) to light. 

 Checking water leakage detection function 

 Checking water leakage detection test function:   

 Pressing buzzer stop and reset buttons simultaneously for three seconds or more causes output of 

simulated  water  leakage  alarms  (water  leakage  indicator  LED  flashing  output,  buzzer  sounding 
output,and water leakage alarm contact output). 

 Checking water leakage detection function with water:   

By  allowing  tap  water  to  drip  on  the  sensor,  you  can  check  how  well  the  sensor  detects  water 

leakage. Wipe off water with dry  cloth after check to restore sensor to operational state for water 
leakage detection. 

 Checking of the break detection function 

 Checking break detection test function:   

You  can  check  break  detection  function  without  removing  break  detection  terminal  or  sensor. 

Pressing buzzer stop and reset buttons simultaneously for three seconds or more causes output of 
simulated water leakage alarm; pressing both of them for three seconds after this causes output of 
simulated break alarms (break indicator LED (green) flashing output; buzzer sounding output; break 
alarm contact output). 

Note: Break alarm is also output when the break detection function is “not activated.” 

 Checking actual break detection function:   

Remove outer cover

insulating sheet and the terminals connected to sensor (I) on the terminal block 

to check actual break detection function. 
After checking, reattach terminals, insulating sheet and outer cover. 

 Buzzer stop button 

If this button is pushed while buzzer is sounding, buzzer stops sounding until next alarm. 

 Reset button 

 If reset button is pushed while the alarm is being held with alarm hold setting activated, alarm output is 

reset. 

 If reset button is pushed with alarm hold setting not activated or under normal conditions, lamp test can 

be performed. 
All  LEDs  are  lit  and  buzzer  is  sounds  (with  monotonous  tone).  Under  this  condition,  control  output 
contacts do not operate. 

<<<Important safety instructions>>> 

Erroneous operation of this water leakage detector not complying with the warning labels or the following 
warnings may lead to fatal accident, serious injury, electric shock, fire, or detector failure. 
 
 
 
 
 

 Never modify or disassemble the detector. 

 Observe ratings of power supply voltage and contact capacity. 

 Allow only persons responsible for handling this product to perform installation work on it or to adjust 

or inspect it with the outer cover opened. 

 After the detector is installed, do not leave it with the cover open, except for inspection and 

maintenance purposes. 

 Do not touch any internal component with wet hands. 

 When performing maintenance on the product, avoid using organic solvent. Use dry wiping rags or a 

small amount of diluted neutral detergent. 
Note: Be careful not to allow detergent solution to remain on the sensor. 

 
 
 

 Check detector supply voltage and rated voltage before installing. 

 When installing and electrically connecting the detector, follow the instructions in the instruction 

manual. 

 When inspecting and maintaining the detector, follow the instructions in the instruction manual. 

 When using control output contacts, check the contact rated load in the instruction manual. 

 
 
 

 Locations easily accessible to the general public 

 Locations close to sources of vibration, organic gas or strong electromagnetic induction. 

 Locations with much waste and dust 

 Locations where there is possibility of water leakage and temperature and humidity are high 

 Detector Specification 

Rated voltage

 

AC 100 V to 240 V (common to 50 Hz/60 Hz); voltage fluctuation: within ±10%

 

Sensor interelectrode 
voltage

 

Break detection terminal not provided: AC 2.8 V or less 
Break detection terminal provided: AC 1.5 V or less

 

Interelectrode 
short-circuit current

 

AC 0.13 mA or less

 

Power consumption

 

3 VA or less

 

Working ambient 
temperature and 
humidity

 

-10˚C to 50˚C (no icing); 35%RH to 85%RH (no condensation)

 

Outside dimensions, 
weight and color

 

W120 

´

 H124 

´

 D55 mm; 300 g ± 20 g; ivory white

 

Number of sensor 
circuits

 

One

 

Water leakage 
detection and recovery 
levels

 

Factory default setting: Break detection function “activated” 

Detection level: 5.0 kΩ

*1

/recovery level: 6.7 kΩ ± 20% 

*1: Combined resistance  of 6.7 kΩ for an isolated sensor and 20 kΩ for  a  break  detection 

terminal (ZT-2) 
* Sensor with break detection terminal or break detection terminal (ZT-1) must be 

connected.

 

Alarm output

 

Buzzer; water leakage indicator LED (red) flashing; break indicator LED (green) flashing; 
water leakage alarm contacts (no voltage, 1c); break alarm contacts (no voltage, 1c)

 

 

Resistive load

 

Inductive load

 

Rated load

 

AC 250 V, 6.0 A 

DC 24 V 6.0 A 

AC 250 V 3.0 A 

DC 24 V 3.0 A 

Relay contacts: FTR-LYCA005 according to catalog of Fujitsu Component Limited

 

 
 

 Detector Setting Method 

 
 
 
 
 
 
 
 
 
 
 
 

 Dip switch (DIP-SW) setting 

To select dip switch (DIP-SW) positions, use a thin flat-blade screwdriver to move tiny sliders. 

Setting item 

Description 

Factory default setting 

Break detection 
setting 

Break detection setting 
activated/not activated 

Break detection setting 
activated 

DIP-SW-4 

ON 

Alarm hold setting 

Alarm hold setting 
activated/not activated 

Alarm hold setting not 
activated 

DIP-SW-3 

 

OFF 

Fail-safe setting 

Fail-safe output 
activated/not activated 

Fail-safe output not 
activated 

DIP-SW-2 

 

OFF 

Buzzer sound 
setting 

Buzzer sound setting 
activated/not activated 

Buzzer sound setting 
activated 

DIP-SW-1 

ON 

* “Alarm hold” denotes function of holding alarm until reset button is pressed. 
*  “Fail-safe  setting”  denotes  setting  to  reverse  contact  logic  so  that  system  can  judge  detector  power 

supply OFF state to be an abnormality. This setting reverses action of N.O. (Normally Open) contacts 
and N.C. (Normally Close) contacts. Under this setting, power-on causes contacts to operate. 

 Knob adjustment 

Use a thin flat-blade screwdriver to adjust VR-1 and VR-2. 

Setting item

 

Adjustment range

 

Factory default setting

 

Buzzer volume 
adjustment

 

Buzzer volume between 
“low” and “high”

 

Buzzer volume “high”

 

VR-1 

Clockwise to 

maximum

 

Detection level 
adjustment 

2k-5k-14 k

W

 

±

20% 

5.0 k

W

 

±

20% 

VR-2 

Middle 

position 

*  Factory  default  setting  is  value  at  which  water  leakage  sensor

*1

  can  properly  detect  the  presence  of 

common city water. 

*1: Line sensors (AD-S, AD-RS, AD-HS, and FR-AD): within 100 m; point sensor (AD-PA) 
Our  suggestions:  When  detecting  a  low  conductivity  liquid  or  using  a  low-sensitivity  water  leakage 
sensor (such as AD-FH), raise detection level; conversely, when detecting a high conductivity liquid or 
installing detector in a high-temperature, high-humidity environment, lower detection level. 

Water leakage 

detection/recovery level ±20% 

With break detection setting 

“activated”: (Factory default 

setting)   

With break detection setting 

“not activated” 

Adjuster position 

Detection level  Recovery level  Detection level  Recovery level 

Adjuster at the minimum 

setting 

2.0 k

W

 

2.8 k

W

 

2.2 k

W

 

3.3 k

W

 

 

3.0 k

W

 

4.2 k

W

 

3.5 k

W

 

5.3 k

W

 

4.0 k

W

 

5.5 k

W

 

5.0 k

W

 

7.5 k

W

 

Adjuster at middle setting 

(Factory default setting) 

5.0 k

W

 

6.7

 

k

W

 

6.7 k

W

 

10.1 k

W

 

 

6.0 k

W

 

7.8 k

W

 

8.6 k

W

 

12.9 k

W

 

7.0 k

W

 

9.0 k

W

 

10.8 k

W

 

16.2 k

W

 

8.0 k

W

 

10.0 k

W

 

13.3 k

W

 

20.0 k

W

 

9.0 k

W

 

11.0 k

W

 

16.4 k

W

 

24.6 k

W

 

Adjuster at maximum setting 

14.0 k

W

 

15.6 k

W

 

46.7 k

W

 

70.0 k

W

 

 

 

Cautions in installing and handling the detector 

Maintenance and inspection 

Guarantee 

 

 

 

O

N

1

2

3

4

AD-AS-1AM-1

VR–1: 

Buzzer volume 

adjusting knob

VR–2: 

Detection level 

adjusting knob

DIP-SW: 

Function-setting 

switches

* After peeling off insulating sheet and changing 

settings, be sure to reattach sheet. 

Insulating sheet

 

DIP-SW 

VR 

AC power supply

Instrumentation line for

control output contacts

Instrumentation line for sensors:

0.3 SQ or more, within 100 m

Water leakage sensor: within 100 m

Break detection

terminal

AD-AS-1AM

P O W E R

WATER LEAKAGE

CUT-OFF SENCOR

BUZZER STOP

R E S E T

WATER-LEAKAGE

DETECTOR

Connected to the

central monitor

panel and others

Tatsuta Electric Wire &cable Co., Ltd.

AD-AS-1AM

P O W E R

WATER LEAKAGE

CUT-OFF SENCOR

BUZZER STOP

R E S E T

WATER-LEAKAGE

DETECTOR

Break indicator

LED (green)

Buzzer stop button

Reset button

Power indicator

LED (yellow)

Water leakage

indicator LED (red)

Tatsuta Electric Wire & Cable Co., Ltd.

CN1

Break detection
Alarm hold
Fail-safe
Buzzer

VR1

VR2

Power

Water 

leakage

Break

Sensitivity 
adjustment

ON OFF

Reset 

Buzzer stop

H

M

L

Buzzer  
volume

Detection 
sensitivity

Loud

High

100V

200V

Ground

Sensor (I)

 Sensor (O)

AC power input

NC

COM

NO

NC

COM

NO

Electric shock!

* Do not remove this 

protective sheet.

* Do not insert foreign 

bodies into the 

opening.

* Do not touch with wet 

hands.

Caution

L ong- pushing the buzzer stop 

a nd reset buttons together 

(for 2 sec.) allows you to 

check how the detector circui t 

a nd relay opera te.

Water leakage

Break

If you have any questions about handling the detector, contact:

 

 