background image

 

TTS-KS-W-5002-5 

 
 
 
 
 
 
 
 
 
 
 
 
 

Multi-circuit Water Leakage Detector

 

AD-AS-10DRM 

Operation Manual 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 

 

Tatsuta Electric Wire & Cable Co., Ltd. 

Electronics Division   

System Department 

Summary of Contents for AD-AS-10DRM

Page 1: ...TTS KS W 5002 5 Multi circuit Water Leakage Detector AD AS 10DRM Operation Manual Tatsuta Electric Wire Cable Co Ltd Electronics Division System Department ...

Page 2: ...sure to water or high temperature and humidity Warranty Before shipping this product is subjected to strict quality control and inspection In the event of spontaneous failure resulting from defective manufacturing we will repair or replace it according to the following provisions Warranty Provisions 1 Warranty period one year after the delivery date of the product Should the product fail during th...

Page 3: ...Activated 5 Adjustment of Water Leakage Detection Precision 8 5 1 Adjustment Method 6 Buzzer Setting 8 6 1 Buzzer Volume Setting 6 2 Buzzer Stop Setting 7 Maintenance and Periodic Inspection 9 8 Specifications 10 8 1 Ratings 8 2 Performances 8 3 Control Output Contact Specifications Attached Drawing 1 Outside Dimensions of Water Leakage Detector AD AS 10DRM Attached Drawing 2 Parts Layout of Water...

Page 4: ...may lead to malfunction and failure 3 Avoid using the socket lead as the power source as far as possible and use fixed wire to connect power source 4 After installation be sure to conduct tests in conformance with the operation check items described in Chapter 3 2 External Connection To form CPU unit AD AS CPU and 5 circuit expansion unit AD AS UNIT set the terminal block as shown in Drawing 1 Dra...

Page 5: ...wing 3 Due to main output contact of water leakage and abnormalities contact c connect when external control is required Drawing 4 Main Control Output Contact Water leakage contacts COM NO Closed when single circuit water leakage is detected COM NC Open when single circuit water leakage is detected Abnormality COM NO Closed when single circuit water leakage or break is detected COM NC Open when si...

Page 6: ...Setting SW2 on the CPU unit the function of alarm hold and fail safe can be effective If the fail safe function is effective the contact will be operated reversely For details refer to Attached Drawing 6 and the Operation Chart of Chapter 4 3 Operation Check 3 1 Power On Refer to Attached Drawing 3 When the power source switch is at it is ON when at o it is OFF Set the CPU unit power source switch...

Page 7: ...r and then connect the sensor and the DIP switch again When water leakage sensor circuit is not connected set the DIP switch at ON When water leakage sensor circuit is connected set the DIP switch at 1 3 3 Check for Water Leakage Detection Function Refer to Attached Drawing 3 Attached Drawing 4 and Drawing 3 1 Check that the DIP switch for the circuit required to be checked has been set at I 2 Dro...

Page 8: ...age detection function Water leakage indicator LED Break detection function Break indicator LED Buzzer Alarm Stop Switch Buzzer stop indicator LED Buzzer sounding Total control output contact Total control output contact water leakage COM NO Abnormal COM NO Water leakage COM NO Break COM NO Individual control output contact Individual control output contact OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ...

Page 9: ...t switch Water leakage detection function Water Leakage Indicator LED Break detection function Break Indicator LED Buzzer alarm stop switch Buzzer Stop Indicator LED Buzzer sounding Main control output contact Main control output contact water leakage COM NO Abnormal COM NO water leakage COM NO break COM NO Individual control output contact Individual control output contact OFF OFF OFF OFF OFF OFF...

Page 10: ...ed from the factory When the detection precision is required to be changed contact with our company for confirmation 6 Buzzer Setting 6 1 Buzzer Volume Setting Perform volume adjustment through the volume adjustment VR of the indicator unit When rotating clockwise the volume is increased and when rotating counterclockwise the volume is decreased When dispatched from the factory the volume has been...

Page 11: ...ntacts are functioning so if the control output contacts are used adopt the measures such as underlay wiring in order not to affect other devices Be careful to prevent oil based substances such as wax from adhering to the sensor this mayrepel water and interfere with correct detector operation If the sensor is tainted with water absorbing substances electrically conductive dirty water etc replace ...

Page 12: ...Break indication red 10 lighting up Indication during buzzer stop red 1 lighting up Alarm buzzer Maximum sound pressure 70dB 30 cm Catalogue value by manufacturer adjustable Control output contact Contact configuratio n Main contact refer to Specification 8 3 Water leakage 1c Abnormalities water leakage or break 1c Individual contact Water leakage 1c 10 contacts Break 1c 10 contacts Withstand volt...

Page 13: ...hed Drawing 1 Approved by Checked by Prepared by Scale Unit Prepared on mm 2011 08 Tatsuta Electric Wire Cable Co Ltd Name Drawing No TTS KS W3150 2 Outer dimension drawing AD AS 10DRM of water leakage detector ...

Page 14: ...D AS 10DRM TTS KS W3151 2 Attached Drawing 2 Power indicator LED Break indicator LED Water Leakage Indicator LED CPU unit Buzzer Buzzer alarm stop switch Buzzer Stop Indicator LED Indicator Unit Buzzer Volume Adjustment VR Earth Wire Connection Terminal Indicator LED switch alarm cancel switch 5 Circuit Expansion Unit of water leakage detector ...

Page 15: ...Wire Cable Co Ltd Parts layout drawing of CPU unit TTS KS W3152 3 Power supply terminal block DIP switch for operation setiong SW2 SW3 Indication of Indicator unit connector DIP switch setting for Setting OFF when connecting the sensor Setting ON when not connecting the sensor Detection precision adjustment Terminal block for sensor No 1 5 A6 B6 Connection sensor 1 A5 B5 Connection sensor 2 A4 B4 ...

Page 16: ...nsor Setting ON when not connecting the sens Precision detection adjustment VR No 6 10 Terminal block for sensor No 6 10 A6 B6 Connection sensor 6 A5 B5 Connection sensor 7 A4 B4 Connection sensor 8 A3 B3 Connection sensor 9 A2 B2 Connection sensor 10 A1 B1 No connection TTS KS W3153 2 Approved by Checked by Prepared by Scale Unit Prepared on Tatsuta Electric Wire Cable Co Ltd Name Drawing No mm 2...

Page 17: ...witch 1 Indicate that the circuit selection switch has selected the circuit information SW2 No 1 of DIP is set ON indicate detection sensitivity OFF indicate sensor resistance E g Sensor resistance for No 1 circuit is indicated as 20 0kΩ 2 Check the operation of individual control output contacts concerning indicator Under this condition when pressing the test switch break indicator LED water leak...

Page 18: ...Not activated ON Activated OFF Not activated ON Activated Individual relay alarm hold Indicator LED alarm hold Fail safe performance main relay relay operation when the sensor is normal Failure safe performance individual relay relay operation when the sensor is normal Abnormal contact operation switchover OFF Abnormal contact operation when water leakage and break occur ON Abnormal contact operat...