4. Inspect the splashguards, scarves, grip covers, and confirm that there are not damages and intense dirt. 

Carry out replacement if abnormality is discovered. 

 

Trouble Shooting 

 

Problem

 

Solution

 

Nozzle keeps tripping off immediately. 

1.  The  sensor or the air passage on the nozzle spout may be 

blocked by an alien substance or fuel. Remove the alien 
substance or fuel and fill again. 

 

2.  The safety cut out attitude valve may operate with some 

near horizontal fill pipes. Turn the nozzle spout downward 
and fill again. 

 

3.  Some filler necks are difficult to refuel. 

Slow down fuel delivery.  Put on low latch position. 

 

Nozzle fails to open. 

1.  Pump pressure is not added to the nozzle. Check the pump 

and solenoid valve.

 

 

2.  The passage in the nozzle is clogged up.  

Replace or clean the nozzle. 

 

3.  Confirm whether nozzle lever was damaged. 

In the case of damage, change the lever. 

 

Nozzle does not close automatically

 

Stop use promptly. 
Call your service contractor for repair or replace the nozzle.

 

 

Nozzle leaks. 

Stop use promptly. 
Call your service contractor for repair or replace the nozzle. 

 

 

 

Guarantee 

TATSUNO guarantees against defective materials and manufacturing during warranty period.     
Warranty period: One year from date of supply.  

If the delivery date cannot be established, the date code on the nozzle prevails. 
Warranty does not cover below. 

(1) Damage to the nozzle & swivel in an accident etc. 

(2) Damage by natural disasters, such as a typhoon and an earthquake. 

(3) Wear items such as spouts, vapour recovery boots, scarves or grip covers. 

 

Replacement period 

Nozzles are expendables. Even if there is no abnormality, we recommend replacement after use of  
the nozzle & swivel for three years or the quantity of refuelling 2,500,000L. 

 

 
 

Summary of Contents for FN-1024

Page 1: ...1 5 TATSUNO ULTRAAutomatic Nozzle for Fuel Dispenser Nozzle Model FN 1024 FN 1029 Installation and Maintenance Manual II 1 G EN 13012 CML 17ATEX9003U TATSUNO ULTRA automatic nozzle for standard speed FN 1024 TATSUNO ULTRA automatic nozzle for high speed FN 1029 ...

Page 2: ...ow test 1 Leak confirmation Start pump and check for leaks between the nozzle swivel and hose connections 2 Flow rate test Measure the flow rate of the nozzle first latch position Ensure the maximum flow rate is below the maximum flow rate of the dispenser 3 Automatic shut off test Start flow into approved metal test container place nozzle in first latch position Immerse the sensor on nozzle spout...

Page 3: ...in the nozzle is clogged up Replace or clean the nozzle 3 Confirm whether nozzle lever was damaged In the case of damage change the lever Nozzle does not close automatically Stop use promptly Call your service contractor for repair or replace the nozzle Nozzle leaks Stop use promptly Call your service contractor for repair or replace the nozzle Guarantee TATSUNO guarantees against defective materi...

Page 4: ... Yokohama shi Kanagawa Japan FAX 81 45 893 4680 No part of this manual may be copied or reproduced in any form or by any means without prior written consent of TATSUNO CORPORATION The information in this manual is subject to change without notice and should not be construed as a commitment by TATSUNO CORPORATION TATSUNO CORPORATION has taken great effort to verify the accuracy of this manual but a...

Page 5: ...UP050 EN Nozzle FN 1024 FN 1029_Instructions_rev3 docx Page 5 5 ...

Reviews: