PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-102T
PAGE 6
Issue: 1.1 Authorised: GH Date: 06/11/02
4.3 WHAT THE INDICATORS MEAN
The table below summarises the various indicators available on the Fire Alarm Panel and what they mean in their
various states.
INDICATOR
STATUS OF LIGHT WHAT THIS MEANS
Power
STEADY GREEN
The panel is supplied with power
GEN FLT
ONLY
STEADY YELLOW
Problem with keyswitch
GEN FLT &
SUPPLY FLT
STEADY YELLOW
FLASHING YELLOW
There is a problem with either the mains supply or
the battery backup
GEN FLT &
EARTH FLT
STEADY YELLOW
FLASHING YELLOW
There is a wiring problem. One of the cables is
touching the earth screen.
GEN FLT &
ZONAL FLT
STEADY YELLOW
FLASHING YELLOW
There is an open circuit fault in the wiring of the
zone indicated.
GEN FLT &
ZONAL FLT
GEN S/C
STEADY YELLOW
FLASHING YELLOW
FLASHING YELLOW
There is a short circuit fault in the wiring of the
zone indicated.
GEN FLT &
SND FLT
STEADY YELLOW
FLASHING YELLOW
There is an open circuit fault in the wiring of one
or both of the sounder circuits
GEN FLT &
SND FLT
GEN S/C
STEADY YELLOW
FLASHING YELLOW
FLASHING YELLOW
There is a short circuit fault in the wiring of one or
both of the sounder circuits
GEN FLT &
SYSTEM FLT
STEADY YELLOW
STEADY YELLOW
A processor fault has occurred. To reset, turn
keyswitch on then back off. If problem persists,
consult your dealer.
GEN FIRE
ONLY
STEADY RED
A manual evacuation has occurred.
The sounders will be active.
GEN FIRE &
ZONE FIRE
STEADY RED
STEADY RED
A fire has occurred in the zone indicated.
The sounders will be active.
GEN FIRE &
ZONE FIRE &
GEN DISABLE
& DEL
STEADY RED
STEADY RED
STEADY YELLOW
STEADY YELLOW
A fire has occurred in the zone indicated.
The sounders have a delay set, and will become
active after the programmed delay. To override
the display, press delay override.
GEN DISABLE
FLASHING YELLOW
(FAST – 4 HZ)
The panel is ready for selecting disable or test
mode
GEN DISABLE
FLASHING YELLOW
(SLOW – 0.5 HZ)
The panel is in SELECT DISABLEMENT MODE
GEN DISABLE
ZONE DISABLE
FLASHING YELLOW
(SLOW – 0.5 HZ)
The user is scrolling through zones to select
which one to disable/or user has just enabled the
zone.
GEN DISABLE
ZONE DISABLE
STEADY YELLOW
STEADY YELLOW
The indicated zone is disabled.
GEN DISABLE
DEL
STEADY YELLOW
STEADY YELLOW
The Sounders are delayed by the amount set on
the rotary switch.
GEN TEST
ZONE DISABLE
STEADY YELLOW
STEADY YELLOW
The indicated zone is in Test Mode.
4.4 TESTING THE INDICATOR LIGHTS
To test the Panel’s indicator lights are working correctly, turn key switch to “Controls Enable” position then press
the LED test button. The panel’s internal buzzer will also sound when pressing the button to show it is working
correctly.