5

4.0 FLOW CHARACTERISTICS AND CHARTS

The Vortex 1.5” and 2.5” have has a 1 3/8” waterway integrated into the outlet. If a smaller smooth-bore is attached to the outlet, 

follow the appropriate flow chart for the smaller orifice size instead.

NOTICE

SPECIAL CONFIGURATIONS If nozzles are made according to the special marking or performance 

requirements of the fire department then the operating characteristics may differ from the published data 

in this manual. Repair parts specific to each serial number may differ from those shown in the service 

procedure. The required parts for each serial number are available online by entering tft.com/H123456 

with the numbers corresponding to the serial number engraved on the product.

20

Flow (lpm)

Pr

es

su

re

 (p

si

)

0

500

250

Pr

es

su

re

 (b

ar

)

1

50

100

150

200

Flow (GPM)

10

0

0

Figure 4.0 

1-3/8” Waterway Flow Chart

3.3 NOZZLE COUPLINGS

NH (National Hose Threads per NFPA #1963) threads are standard on all nozzles.  Other threads such as NPSH (National Pipe 

Straight Hose threads per ANSI/ASME #B1.20.7) can be specified at time of order.

CAUTION

Nozzle must be properly connected. Mismatched or damaged threads may cause nozzle to leak 

or uncouple under pressure and could cause injury.

CAUTION

Dissimilar metals coupled together can cause galvanic corrosion that can result in the inability 

to  unscrew  the  threads  or  complete  loss  of  thread  engagement  over  time.    Per  NFPA  1962 

(2008 edition), if dissimilar metals are left coupled together an anti-corrosive lubricant should 

be applied to the threads.  Also, the coupling should be disconnected and inspected at least 

quarterly.

3.4 USE WITH SALTWATER

Use with saltwater is permissible provided nozzle is thoroughly cleaned with fresh water after each use. The service life of the nozzle 

may be shortened due to the effects of corrosion and is not covered under warranty.

Summary of Contents for VORTEX

Page 1: ...and understand the following 1 Firefighting and Emergency Response are inherently dangerous activities requiring proper training in their hazards and the use of extreme caution at all times 2 It is your responsibility to read and understand any user s instructions including purpose and limitations provided with any piece of equipment you may be called upon to use 3 It is your responsibility to kno...

Page 2: ... FLOW CHARACTERISTICS AND CHARTS 5 0 NOZZLE CONTROLS 5 1 FLOW CONTROL 5 1 1 LEVER TYPE FLOW CONTROL 5 1 2 TIP ONLY 5 2 PATTERN CONTROL 6 0 USE WITH FOAM 7 0 USE OF NOZZLES 8 0 APPROVALS 9 0 COLOR CODED VALVE HANDLE AND PISTOL GRIP 10 0 EXPLODED VIEWS AND PARTS LISTS 11 0 WARRANTY 12 0 MAINTENANCE 12 1 FIELD LUBRICATION 12 2 SERVICE TESTING 12 2 1 HYDROSTATIC TESTING 12 2 2 FLOW TESTING 12 2 3 RECO...

Page 3: ...eam and can result in injury death or loss of property See flow graphs or call 800 348 2686 for assistance WARNING The nozzle may be damaged if frozen while containing significant amounts of water Such damage may be difficult to detect visually and can lead to possible injury or death Any time the nozzle is subject to possible damage due to freezing it must be tested by qualified personnel before ...

Page 4: ...ilable by request Two Vortex 2 5 models are available SVFV NJ Vortex with integrated detent ball valve SVFG NJ Vortex with integrated detent ball valve and pistol grip INLET THREADS OUTLET THREADS FOR CONNECTING TO SMOOTH BORE NOZZLE not included TWIST STREAM SHAPER TO SELECT STRAIGHT STREAM OR VORTEX DISPERSED PATTERN COUPLING PISTOL GRIP ON OFF FLOW CONTROL VORTEX TIP ONLY VORTEX WITH INTERGRATE...

Page 5: ...50 200 Flow GPM 10 0 0 Figure 4 0 1 3 8 Waterway Flow Chart 3 3 NOZZLE COUPLINGS NH National Hose Threads per NFPA 1963 threads are standard on all nozzles Other threads such as NPSH National Pipe Straight Hose threads per ANSI ASME B1 20 7 can be specified at time of order CAUTION Nozzle must be properly connected Mismatched or damaged threads may cause nozzle to leak or uncouple under pressure a...

Page 6: ...slowly to eliminate unnecessary strain on the hose and couplings and reduce pressure surges TFT recommends the use of a pistol grip for easier handling For additional stress reduction a hose rope or strap may also be used This permits more effective use and ease of advancement while minimizing strain and fatigue 5 1 FLOW CONTROL Open valve slowly to avoid sudden changes in nozzle reaction Close va...

Page 7: ...ckwise moves the shaper to the straight stream position shown in figure 5 2 3 Twisting the shaper counterclockwise will result in an increasingly wider pattern until reaching the full Vortex pattern shown in figure 5 2 4 Allows up to 5 8 debris to pass TWIST CLOCKWISE FOR STRAIGHT STREAM TWIST COUNTER CLOCKWISE FOR FULL VOTREX Allows up to 5 8 debris to pass Figure 5 2 3 Straight Stream pattern se...

Page 8: ...e fireground tactics and operations 8 0 APPROVALS Vortex 1 5 and 2 5 NH threaded nozzles meet the requirements of NFPA 1962 2013 and NFPA 1964 2008 WARNING There are a wide variety of foam concentrates Each user is responsible for verifying that any foam concentrate chosen to be used with this unit has been tested to assure that the foam obtained is suitable for the purpose intended WARNING Use of...

Page 9: ...ION SHIM 2 P170 18 TRUNNION RIGHT 1 P120R 19 BACKUP RING 330 PTFE SINGLE TURN 1 VOB 330T 20 BASE 1 5 NHF X 1 5 NHM 1 SVF100NF 21 STREAM PATTERN LABEL 1 SVF131 22 VORTEX PATTERN LABEL 1 SVF132 23 ROLLER 6 SVF114 24 VANE 6 SVF110 25 O RING 015 6 VO 015 ITEM DESCRIPTION QTY PART 26 CAM SCREW 3 HD780 27 CAM FOLLOWER 3 SVF121 28 DOWEL PIN 6 VP156X1 00 29 BACKUP RING 332 PTFE SINGLE TURN 1 VOB 332T 30 S...

Page 10: ...e discharge of its obligations under this limited warranty If TFT makes this election claimant shall return the equipment to TFT free and clear of any liens and encumbrances This is a limited warranty The original purchaser of the equipment any person to whom it is transferred and any person who is an intended or unintended beneficiary of the equipment shall not be entitled to recover from TFT any...

Page 11: ...45 kPa increments held for 30 seconds at each pressure up to the maximum pressure for which the nozzle is being tested and then held for one minute without leakage 5 There shall be no sign of leakage through the valve or shut off 12 2 2 FLOW TESTING Flow testing must be conducted in the following manner 1 The nozzle shall be mounted so that the flow rate and pressure through the nozzle and the pre...

Page 12: ...A National Fire Protection Agency WARNING Any nozzle failing any part of the checklist is unsafe for use and must have the problem corrected before use or being placed back into service Operating a nozzle that has failed the checklist is a misuse of this equipment 12 3 REPAIR Factory service is available with repair time seldom exceeding one day in our facility Factory serviced nozzles are repaire...