background image

©Copyright Task Force Tips, Inc. 1998 - 2009 

LIM-035 June 15, 2009 Rev07

5

2.4.1  FOAMJET LX WITH MASTERSTREAM NOZZLE

To increase the expansion ratio and drain time, Task Force Tips “Foamjet LX” (model FJ-LX-M) may be used with the Masterstream 
nozzle. This low expansion foam tube attaches and detaches quickly from the nozzle. Note: As expansion ratio is increased, the 
reach of the stream will be decreased due to the greater amount of bubbles in the stream and their inability to penetrate the air. 
Generally, the reach with foam is approximately 10 % less than with water only. Actual results will vary based on brand of foam, 
hardness of water, temperature, etc.

! W
A

RNI

NG

FIG 2.4.1A - FJ-LX-M Shown on Masterstream Nozzle

FIG 2.4.1B - FJ-LX-MD Shown on ZN Nozzle

3.0  FLOW CHARACTERISTICS OF ZN & ZM NOZZLES

The ZN & ZM Nozzles are manufactured to a predetermined fi xed orifi ce. The orifi ce size is not adjustable and is specifi ed at time 
of order. 250, 350, 500 or 750 GPM fl ow rates at 100 PSI are available on the ZN and 500, 750, 1000 or 1250 GPM @ 100 psi are 
available on the ZM nozzle. The fl ow rate is marked on the nozzle’s baffl e. Figure 3 gives relationship of fl ow and pressure for various 
orifi ce sizes.

3.1  FLOW CHARACTERISTICS OF MASTERSTREAM 1000 SELECTABLE NOZZLE

The Masterstream 1000 Selectable Nozzle allows the user to select one of several orifi ce sizes by turning a knob at the front of the 
nozzle. An indicator on the knob shows which fl ow has been selected. Figure 3 gives relationship of fl ow and pressure for various 
orifi ce sizes.

0

0

20

40

4

60

80

8

100

120

12

140

160

180

200

0

0

100

1000

200

2000

300

3000

400

4000

500

600

700

800

900 1000 1100 1200

FLOW (GPM)

FLOW (LPM)

2

5

0

 G

P

M

 @ 

1

0

0

 P

S

I

3

5

0

 G

P

M

 @ 

1

0

0

 P

S

I

500

 G

P

M

 @

 1

0

0

 P

S

I

75

G

P

M

 @

 1

00

 P

S

I

10

00

 G

PM

 @

 1

00

 P

SI

PRESSURE (PSI)

PRESSURE (BAR KP

A/100)

1250 GPM @

 100 PSI

FIG 3 - Nozzle Flow Characteristics

Summary of Contents for MASTERSTREAM 1000 FIXED Series

Page 1: ...el with the operation servicing and safety procedures associated with the ZN ZM and Masterstream firefighting nozzles This manual should be kept available to all operating and maintenance personnel ZN NOZZLE ZN NOZZLE 250 350 500 or 750 GPM 100 PSI 500 1000 1500 or 2000 LPM 7 BAR 700 KPA ZM NOZZLE ZM NOZZLE 500 750 1000 or 1250 GPM 100 PSI 2000 3000 4000 or 5000 LPM 7 BAR 700 KPA MASTERSTREAM 1000...

Page 2: ... result in death burns or other severe injury FEMSA Fire and Emergency Manufacturers and Service Association P O Box 147 Lynnfield MA 01940 www FEMSA org Table Of Contents 1 0 MEANING OF SAFETY SIGNAL WORDS 2 0 GENERAL INFORMATION 2 1 USE WITH SALT WATER 2 2 VARIOUS MODELS AND TERMS 2 3 PATTERN CONTROL 2 4 USE WITH FOAM 2 4 1 FOAMJET LX WITH MASTERSTREAM NOZZLE 3 0 FLOW CHARACTERISTICS OF INDUSTRI...

Page 3: ...to 135 F 40 C to 57 C for ZM nozzles WARNING Injury can occur from an inadequately supported nozzle The mounting must be capable of supporting the nozzle reaction force which can be in excess of 665 LBS 1250 GPM at 100 PSI WARNING Some volatile liquids can be ignited by static discharge Static build up can occur from Electrochemical separation of charge as water drains through low conductivity ref...

Page 4: ...also available with linear push pull remote electric or hydraulic actuation of the stream shaper 2 4 USE WITH FOAM The ZN ZM and Masterstream nozzles may be used with foam solutions Refer to fire service training for the proper use of foam WARNING For Class B fires lack of foam or interruption in the foam stream can cause a break in the foam blanket and greatly increase the risk of injury or death...

Page 5: ...determined fixed orifice The orifice size is not adjustable and is specified at time of order 250 350 500 or 750 GPM flow rates at 100 PSI are available on the ZN and 500 750 1000 or 1250 GPM 100 psi are available on the ZM nozzle The flow rate is marked on the nozzle s baffle Figure 3 gives relationship of flow and pressure for various orifice sizes 3 1 FLOW CHARACTERISTICS OF MASTERSTREAM 1000 S...

Page 6: ...Masterstream Fixed Nozzle WARNING An inadequate supply of nozzle pressure and or flow will cause an ineffective stream and can result in injury death or loss of property 3 3 DETERMINING FLOW WITH PRE PIPED MONITORS The simplest procedure to determine flow is with a flow meter If a flow meter is unavailable then the flow may be estimated using pressure loss data between the nozzle and an in line pr...

Page 7: ...stream nozzles at various pressures The graphs represent orifice sizes of 250 350 500 750 and 1000 GPM at 100 PSI For other orifice sizes and pressures the graphs may be interpolated Notes on trajectory graphs Graphs show approximate effective stream trajectory at 30 degrees elevation in no wind conditions Distance to last water drops approximately 10 farther Trajectories shown are for water The a...

Page 8: ...emove debris trapped in the nozzle 1 Shut off flow to the nozzle 2 Move the stream shaper to the wide fog position 3 For ZN Nozzle Unscrew baffle using a 1 1 8 inch 28mm socket For ZM Nozzle Unscrew the bolt using 7 8 socket and remove baffle For Masterstream Selectable Gallonage Nozzle Turn flow selector on front of nozzle to FLUSH position For Masterstream Fixed Gallonage Nozzle Remove nozzle to...

Page 9: ... PIN 1 Z660 3 BUMPER 1 Z700 9 NAME LABEL ZN NOZZLE 1 ZL150 4 SHAFT 1 Z505 10 GASKET 2 5 HOSE COUPLING 1 V3190 ZM NOZZLE 1 2 3 4 5 6 7 9 10 12 11 13 8 ZM PARTS LIST ITEM DESCRIPTION QTY PART ITEM DESCRIPTION QTY PART 1 GASKET 2 5 HOSE COUPLING 1 V3190 8 SPRING 1 ZFM580 2 NOZZLE BODY 2 5 NH 1 ZFM600NJ 9 BAFFLE K 125 1 ZFM560 3 CUP SEAL 4 25 X 4 75 X 1 4 1 XGE380 13 SUBBAFFLE K 75 K 100 1 ZFM5656 4 1...

Page 10: ...32 X 3 16 DRIVE SCREW 1 VT02 00DS187 5 NAME LABEL 1 M750 24 O RING 345 1 VO 345 6 SHAPER 1 M216 25 CAM PINS 2 M260 7 HALO RING 1 M230 26 SELECT GAL BAFFLE 1 C027 8 HALO CAP 4 M231 27 SELECT GAL CAM US 1 C028 9 5 16 18 X 1 1 2 SOCKET HEAD SCREW 4 VT31 18SH1 5 28 SELECTABLE FLOW SPRING 1 C031 10 MASTER BUMPER 1 M700 29 I O SCREW 1 C033 11 GASKET 2 5 HOSE COUPLING 1 V3190 30 3 8 24 X 3 8 DOG POINT 2 ...

Page 11: ...AM NUT 1 VT62 18NT 4 NAME LABEL 1 M755 19 WASHER 1 VW700X203 60 5 SHAPER 1 M216 20 10 24 X 1 2 BUTTON HEAD SCREW 1 VT10 24BH500 6 HALO RING 1 M230 21 3 6 BALL 48 V2120 7 HALO CAP 4 M231 22 WEAR STRIP 1 M510 8 5 16 18 X 1 1 2 SOCKET HEAD SCREW 4 VT31 18SH1 5 23 3 32 X 3 16 DRIVE SCREW 1 VT02 00DS187 9 MASTER BUMPER 1 M700 24 O RING 345 1 VO 345 10 GASKET 2 5 HOSE COUPLING 1 V3190 25 CAM PINS 2 M260...

Page 12: ...urchase price of the equipment less reasonable depreciation in complete discharge of its obligations under this limited warranty If TFT makes this election claimant shall return the equipment to TFT free and clear of any liens and encumbrances This is a limited warranty The original purchaser of the equipment any person to whom it is transferred and any person who is an intended or unintended bene...