background image

Read instruction manual before use. Operation of this device without understanding the
manual and receiving proper training is a misuse of this equipment. A person who has not
read and understood all operating and safety instructions is not qualified to operate the
Industrial and Masterstream nozzle.

This instruction manual is intended to familiarize firefighters and maintenance personnel
with the operation, servicing and safety procedures associated with the Industrial and
Masterstream firefighting nozzles.

This manual should be kept available to all operating and maintenance personnel.

MANUAL: Deluge Nozzles

With Fixed & Selectable Flow

350, 500 or 750 GPM @ 100 PSI

1300, 2000, or 3000 LPM @ 7 BAR (700 KPA)

INDUSTRIAL

250, 350, 500, 750, 1000 GPM @ 100 PSI

1000 GPM MAX @ 100 PSI

1000, 1500, 2000, 2500, 3000, 4000 LPM @ 7 BAR (700 KPA)

1200, 1800, 2400, 3000, 3600, 4800 LPM @ 10 BAR (1000 KPA)

500, 1000, 1500, 2000, 2500 LPM @ 7 BAR (700 KPA)

4000 LPM MAX @ 7 BAR (700 KPA)

MASTERSTREAM 1000

SELECTABLE

MASTERSTREAM 1000

FIXED

WARNING

N

ozzle

F

or
W

ater

and

F

oam

S

o

lutio

ns

Nozzle

Fo
r

W

a

ter

and

F

oam

Solutions

STRIAL

NOZZL

STRIAL

NOZZL

INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

INDUSTRIAL & MASTERSTREAM 1000

2800 E Evans Ave • Valparaiso , IN 46383-6940 USA

800-348-2686 • 219-462-6161 • Fax 219-464-7155

Made in USA • www.tft.com

TASK FORCE TIPS, Inc.

selectable

FIXED

FLOW

LIM-035 October 5, 2004 Rev02

©Copyright Task Force Tips, Inc. 1998-2004

Summary of Contents for INDUSTRIAL Series

Page 1: ... Deluge Nozzles With Fixed Selectable Flow 350 500 or 750 GPM 100 PSI 1300 2000 or 3000 LPM 7 BAR 700 KPA INDUSTRIAL 250 350 500 750 1000 GPM 100 PSI 1000 GPM MAX 100 PSI 1000 1500 2000 2500 3000 4000 LPM 7 BAR 700 KPA 1200 1800 2400 3000 3600 4800 LPM 10 BAR 1000 KPA 500 1000 1500 2000 2500 LPM 7 BAR 700 KPA 4000 LPM MAX 7 BAR 700 KPA MASTERSTREAM 1000 SELECTABLE MASTERSTREAM 1000 FIXED WARNING N...

Page 2: ...ean far reaching straight stream They are adjustable from straight stream to a dense fog pattern Their rugged construction is compatible with the use of fresh water as well as fire fighting foam solutions A summary of each nozzle s characteristics is shown in the tables below This equipment is intended for use by trained personnel for firefighting Their use for other purposes may involve hazards n...

Page 3: ...y be carried back to the nozzle will depend on the following factors Voltage of the line or equipment Distance from the nozzle to the line or equipment Size of the stream Whether the stream is solid or broken Purity of the water 2 WARNING 1 2 Electrostatic Hazards of Foam Blanketing Operations by Peter Howels Industrial Fire Safety July August 1993 The Fire Fighter and Electrical Equipment The Uni...

Page 4: ... to complete task see NFPA for minimum duration time requirements Foam logistics have been carefully planned Allow for such things as Storage of foam in a location not exposed to the hazard it protects Personnel equipment and technique to deliver foam at a rapid enough rate Removal of empty foam containers Keeping clear path to deliver foam as hoses other equipment and vehicles are deployed Improp...

Page 5: ...zzle s baffle Figure 3 gives relationship of flow and pressure for various orifice sizes The Masterstream 1000 Selectable Nozzle allows the user to select one of several orifice sizes by turning a knob at the front of the nozzle An indicator on the knob shows which flow has been selected Figure 3 gives relationship of flow and pressure for various orifice sizes 0 0 20 40 4 60 80 8 100 120 12 140 1...

Page 6: ...Q D P Flow water with a smooth bore nozzle and record the nozzle s size pitot pressure and in line pressure gauge reading The smooth bore nozzle s flow is calculated from the Freeman formula Where F 29 71 for English units GPM INCHES PSI F 667 for metric units LPM MM BAR Note 1 BAR 100 KPA is smooth bore nozzle flow in GPM or LPM is nozzle exit diameter in INCHES or MM is pitot pressure in PSI or ...

Page 7: ...1000 GPM at 100 PSI For other orifice sizes and pressures the graphs may be interpolated Notes on trajectory graphs Graphs show approximate effective stream trajectory at 30 degrees elevation in no wind conditions Distance to last water drops approximately 10 farther Trajectories shown are for water The addition of foam is expected to decrease the reach by approximately 10 Tail or head winds of 20...

Page 8: ...limited warranty the claimant must return the equipment to TFT at 2800 East Evans Avenue Valparaiso Indiana 46383 within a reasonable time after discovery of the defect TFT will examine the equipment If TFT determines that there is a defect attributable to it TFT will correct the problem within a reasonable time If the equipment is covered by this limited warranty TFT will assume the expenses of r...