©Copyright Task Force Tips, Inc. 2002-2015
LIX-630 July 2, 2015 Rev19
9
4.2 STACKED TIPS OR SMOOTHBORE NOZZLES
NOZZLE
DIAMETER
NOZZLE EXIT PRESSURE
50 PSI
80 PSI
100 PSI
150 PSI
175 PSI
FLOW
(GPM)
REACTION
(LBS)
FLOW
(GPM)
REACTION
(LBS)
FLOW
(GPM)
REACTION
(LBS)
FLOW
(GPM)
REACTION
(LBS)
FLOW
(GPM)
REACTION
(LBS)
1.0 INCH
210
80
266
126
297
157
364
236
390
275
1-1/4 INCH
328
120
415
196
464
245
—
—
—
—
1-1/2 INCH
473
177
—
—
—
—
—
—
—
—
NOZZLE
DIAMETER
NOZZLE EXIT PRESSURE
4 BAR
6 BAR
8 BAR
10 BAR
12 BAR
FLOW
(L/min)
REACTION
(KG)
FLOW
(L/min)
REACTION
(KG)
FLOW
(L/min)
REACTION
(KG)
FLOW
(L/min)
REACTION
(KG)
FLOW
(L/min)
REACTION
(KG)
25 MM
830
40
1000
60
1200
80
1300
100
1400
120
32 MM
1300
70
1700
100
1900
130
—
—
—
—
38 MM
1900
90
—
—
—
—
—
—
—
—
FLOW EXCEEDS RATING OF BLITZFIRE PORTABLE MONITOR
4.3 STREAM STRAIGHTENERS
Stream quality, especially with smooth bore nozzles, is generally improved with the use of a stream straightener. A stream straightener
is integrated into the exit of the monitor.
4.4 USE WITH FOAM
The Blitzfi re may be used with various foam nozzles and foam solutions. Refer to fi re service training for the proper use of foam.
WARNING
Use of compressed air foam (CAF) with portable nozzles can cause sudden surges in nozzle
reaction force resulting in injury or death from loss of footing, hose whipping, or an out of control
portable monitor. Be prepared for sudden changes in nozzle reaction caused by: Slug loading
(Loss of foam concentrate sends slugs of air and water into the nozzle) sudden release of built-up
pressure in the hose when opening a nozzle.
4.0 FLOW CHARACTERISTICS
The Blitzfi re Portable Monitor is designed for maximum fl ows of 500 GPM (2000 LPM) and a maximum pressure of 175 PSI (12
BAR). Do not exceed these limits.
4.1 AUTOMATIC, FIXED, AND SELECTABLE FLOW NOZZLES
A variety of water or foam nozzles may be used with the Blitzfi re Portable Monitor. Automatic nozzles maintain a constant pressure
by adjusting their opening to match the available fl ow. Consult the nozzle manufacturer for maximum fl ow and pressure ratings. In
all cases do not exceed 500 GPM (2000 LPM) and/or 175 PSI (12 BAR).