 Troubleshooting

Failure

Potential cause

LED "ON" does not light up

- Power supply A1+/A2

not connected

LED "ERR" flashes 
in relation 1:1

- Under- or overvoltage

(check power supply A1+/A2)

LED "ERR" flashes 
in relation 4:1

- external failure (see flashing code)

LED "ERR" 
continuously on

- system error

(if cannot be removed after restart
unit must be replaced)

Maintenance and Repairs

- The device contains no parts that require maintenance.

- In case of failure, do not open the device but send it to manufacturer

for repair.

Technical Data

Switching capacity

to AC 15
NO contacts:  

3 A / AC 230 V 

IEC/EN 60 947-5-1

to DC 13
NO contacts:  

2 A / DC 24 V 

IEC/EN 60 947-5-1

Electrical life

at 5 A, AC 230 V cos 

j

 = 1:  

> 1.5 x 10

5

 switching cycles

Permissible operating frequency 

 

1. safety function:  

max. 1800 switching cycles / h

2. safety function:  

max. 360 switching cycles / h

Short circuit strength

max. fuse rating:  

6 A gL 

IEC/EN 60 947-5-1

Mechanical life: 

 

10 x 10

6

 switching cycles

Semiconductor monitoring output
(not safety): 

 

1 per safety function
max. 50 mA DC 24 V, plus switching

General Data

Nominal operating mode: 

 

continuous operation

Temperature range

Operation:  

- 15 ... + 55 

°

C

Storage:  

- 25 ... + 85 

°

C

Altitude:

 

< 2.000 m

Clearance and creepage distance

rated impuls voltage /
pollution degree:  

4 kV / 2  

IEC 60 664-1

EMC

Electrostatic discharge (ESD):   8 kV (air) 

IEC/EN 61 000-4-2

HF irradiation:  

10 V / m 

IEC/EN 61 000-4-3

Fast transients:  

2 kV 

IEC/EN 61 000-4-4

Surge voltage
between
wires for power supply:  

1 kV 

IEC/EN 61 000-4-5

between wire and ground:  

2 kV 

IEC/EN 61 000-4-5

HF-wire guided:  

10 V 

EN 61 000-4-6

Interference suppression: 

 

Limit value class B 

EN 55 011

Degree of protection

Housing:  

IP 40 

IEC/EN 60 529

Terminals:  

IP 20 

IEC/EN 60 529

Housing: 

 

thermoplastic with VO behaviour
according to UL subj. 94

Vibration resistance:

 

Amplitude 0,35 mm
Frequency 10 ... 55 Hz, IEC/EN 60 068-2-6

Klimate resistance: 

 

15 / 055 / 04 

IEC/EN 60 068-1

Terminal designation: 

 

EN 50 005

Wire connection:

 

DIN 46 228-1/-2/-3/-4

Wire fixing:

 

captive slotted screw

Mounting: 

 

DIN rail 

IEC/EN 60 715

Weight:

 

approx. 275 g

 UL-Data

The safety functions were not evaluated by UL. Listing is accom-

plished according to requirements of Standard UL 508, “general use 

applications”

Switching capacity:

Ambient temperature 55°C

 

Pilot duty B300, Q300

5A 250Vac Resistive or G.P.

5A 24Vdc Resistive

Ambient temperature 40°C:

 

Pilot duty B300, Q300

8A 250Vac Resistive or G.P.

8A 24Vdc G.P.

Wire connection:: 

60°C / 75°C copper conductors only

Terminal: 

AWG 28 - 12 Sol/Str Torque 0.5 Nm

Summary of Contents for PRSU/M2SI

Page 1: ... is used for the safety related release and interruption of a safety circuit It can be used to protect people and machinery in applications with emergency stop pushbuttons safety gates self test type 4 photocells in accordance with IEC EN 61 496 1 two hand switches for metalworking presses and other working machines with dangerous closing movements Type III C according to EN 574 and for safety rel...

Page 2: ...his device presents no known residual risks Non observance may lead to personal injuries and damages to property The PRSU M2SI is used to enable and interrupt a safety circuit in a safe way It can be used to protect people and machines in applications with e stop buttons safety gates light curtains with selftesting Type 4 acc to IEC EN 61 496 1 2 hand controls for presses as well as other producti...

Page 3: ... A new reset is only possible when the reset signal had been switched off temporarily If an external failure occurs because both input channels of a safety function did not switch on or off within the simultanious time a reset is only possible if both channels are switched to off state after removing failure cause If an external failure occurs in only one safety function only this function will be...

Page 4: ...acts 5 Start up at UN 65 ms Release delay at UN and disconnecting the supply 40 ms Release delay at UN and disconnecting S12 S22 or S32 S42 60 ms Two hand control 3 Start up at UN 110 ms Release delay at UN and disconnecting the supply 40 ms Release delay at UN and disconnecting S12 S22 or S32 S42 60 ms simultaneity demand max 0 5 s Safety mat 4 Safety Edge Tapeswitch Start up at UN 85 ms Release ...

Page 5: ... 15 55 C Storage 25 85 C Altitude 2 000 m Clearance and creepage distance rated impuls voltage pollution degree 4 kV 2 IEC 60 664 1 EMC Electrostatic discharge ESD 8 kV air IEC EN 61 000 4 2 HF irradiation 10 V m IEC EN 61 000 4 3 Fast transients 2 kV IEC EN 61 000 4 4 Surge voltage between wires for power supply 1 kV IEC EN 61 000 4 5 between wire and ground 2 kV IEC EN 61 000 4 5 HF wire guided ...

Page 6: ...7 Auto Start Safety function 2 see page 7 Manual Start Operating mode 5 MANUAL with common button Safety function 1 see page 7 Manual start with common button Safety function 2 see page 7 Manual start with common button Application examples with safety function PRSU M2SI PRSU M2SI ...

Page 7: ...754 S22 S11 S12 S12 S1 M11124 S21 S22 S11 S12 M10753 Not Aus S21 Fct Safety mat Safety edge Tape switch 4 with cross fault detection SIL 3 PL e Cat 4 Fct Exclusive or contacts 5 with cross fault detection SIL 3 PL e Cat 4 Fct E Stop 6 without cross fault detection SIL 3 PL e Cat 4 1 S21 S22 S11 S12 Schiebeschutztür geschlossen M10752 OSSD1 OSSD2 S22 S21 S11 S12 Sender Empfänger DC 24V 0V M10751 Fc...

Page 8: ... A 0 6 x 3 5 0 5 Nm 5 LB IN M10248 A A 7 mm 1 x 0 2 2 5 mm2 1 x AWG 24 to 12 2 x 0 2 1 0 mm2 2 x AWG 24 to 18 M10249 A A 7 mm 1 x 0 25 2 5 mm2 1 x AWG 24 to 12 2 x 0 25 1 0 mm2 2 x AWG 24 to 18 M10250 A A 7 mm 1 x 0 2 2 5 mm2 1 x AWG 24 to 12 2 x 0 2 1 5 mm2 2 x AWG 24 to 16 Dimensions dimensions in mm A B PRSU M2SI 110 1 22 5 M4345_a M4345_a 35 115 3 0 0 7 122 6 0 0 7 B A 106 9 Mounting disassemb...

Page 9: ... variants are available on request The safety relevant data of the complete system has to be determined by the manufacturer of the system Approvals and Markings Demand to our device based on the evaluated neccessary safety level of the application Intervall for cyclic test of the safety function EN ISO 13849 1 PL e with Cat 3 or Cat 4 once per month PL d with Cat 3 once per year IEC EN 62061 IEC E...

Reviews: