                                                                                                       TX7140 Intelligent Manual Call Point 

 

 

        Installation &Operation Manual  

                                                                                                                               4050100269-Rev1.1-1215                                                                       

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

      

 

 

 

 

 

 

 

 

 

 

           

   

 

 

 

4 General Maintenance   

 

1.

 

Inform the suitable personnel before conducting the maintenance. 

2.

 

Disable the manual call point on the control panel to prevent false alarm. 

3.

 

Do  not  attempt  to  adjust  or  modify  the  manual  call  point,  it  may  affect  the  ability  of  the 
device to respond to a fire condition and will void the manufacturer’s warranty.  

4.

 

Use a damp cloth to clean the call point.  

5.

 

Notify again proper personnel after conducting the maintenance and make sure to enable 
the manual call point and confirm if up and running.  

6.

 

Perform the maintenance on semi-annually or quarterly depending on the site conditions.  

 

4.1 Resetting Manual Call Point     

1.

 

Ensure the fire is cleared before resetting the call point. 

2.

 

Open the protected flap and insert the supplied reset key into the key hole. (Figure 9). 

3.

 

Rotate the key clockwise position up to 90-degree angle (Figure 10).then forcedly push the 
key inside until the glass plate completely return to its normal position. (Figure 11) 

 
 
 

 
 

 
 
 
 
 
 
 
 
 
 

 
 
 
 

1. Read 
2. Write                  T 
3. R/W Config  

4. Set 

 

 

Address:  123 
ID: 123456789012 

 

Read Description  

Address

: Unique number 

assigned 

ID

: Device serial number 

 

 

 

 

 

 

 

Figure 9 

 

Figure 10 

 

Figure 11 

 

Figure 7  

 

Figure 8  

 

Summary of Contents for TX7140

Page 1: ...TX7140 Intelligent Manual Call Point Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved...

Page 2: ...nstalling the manual call point to ensure proper and safe operation of the system European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted...

Page 3: ...ction 4 1 1 Overview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Manual Call Point Configuration 6 3 1 Pr...

Page 4: ...to the control panel The TX7140 manual call point is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compa...

Page 5: ...and EN54 2 2 Installation and Wiring 1 Mount the call point standard base on standard one gang electrical back box Follow the arrow mark for the correct position Do not over tighten the screws otherwi...

Page 6: ...witch on the unit 2 Switch on the programmer then press button Write or number 2 to enter Write Address mode Figure 4 3 Input the desire device address value from 1 to 254 and then press Write to save...

Page 7: ...roper personnel after conducting the maintenance and make sure to enable the manual call point and confirm if up and running 6 Perform the maintenance on semi annually or quarterly depending on the si...

Page 8: ...Manual Call Point The manual call point cannot last forever In order to keep the call point working in good condition please maintain the equipment continuously according to recommendations from manuf...

Reviews: