background image

VELOCITY VS. 

PRESSURE DROP

Pr

essur

e Dr

op 

(inches w

.g.)

Face Velocity 

(fpm)

AMCA Figure 5.3

100 

500  1,000 

5,000 10,000

1.0

0.5

0.1

.03

.01

LEGEND:

12" x 12"

(305 mm x 305 mm)

36" x 36"

(915 mm x 915 mm)

12" x 48"

(305 mm x 1220 mm)

24" x 24"

(610 mm x 610 mm)

48" x 12"

(1220 mm x 305 mm)

INSTALLATION:

10. Smoke dampers may be mounted vertically 

(standing up/horizontal airflow)

 with blades 

running horizontally, or mounted horizontally

 (lying down/vertical airflow)

.

11. Dampers are available in four install types: Installed In Duct, Flanged to Duct, Extended Rear 

Flange, and Square to Round Transition. 

(See Install Types pages for details.)

12. Multi-section smoke dampers may require field assembly of sections.
13. Installation of dampers must be in accordance with TAMCO’s current UL/ULC Approved 

Smoke Damper Installation Guidelines, provided with each smoke damper shipment. 

(Printed installation guidelines are provided with each damper shipment, however all 

technical information available on TAMCO’s web site at www.tamcodampers.com supersedes 

information contained within printed versions.)

ACTUATORS:

14. UL 555S/ULC-S112.1 requires that all actuators for smoke dampers be factory mounted. 

Approved actuators are Belimo and Honeywell.

15. Voltage:   24 vac, 120 vac, 230 vac, single phase.
16. Mounting: Internal or external actuator mounting. 

(All smoke dampers with internally 

 

mounted actuators, will be mounted on a jackshaft. If actuator side of damper is to be 

 

connected to duct work, smoke damper assembly will have to be installed in a sleeve.)

17. Options:   Auxiliary switches.
18. Actuator quantity and location requirements are shown in, and must be in accordance with, 

TAMCO UL/ULC Approved Smoke Damper Configurations.

38

SUBMITTAL DATA  |  

Series 1000 SM

UL/ULC Approved Smoke Damper

2

TAMCO® Series 1000 SM meets the require-

ments for smoke dampers established by:

UL 555S/ULC-S112.1 File R16679

National Fire Protection Association: 

NFPA Standards 80, 90A, 92, 101, 105

California State Fire Marshall Listing#: 

3230-2116:0100

MINIMUM OPENING SIZE:

11”w x 6”h

(280 mm x 153 mm)

MAXIMUM SINGLE-SECTION OPENING SIZE: 

36"w x 48"h

(915 mm x 1220 mm)

MAXIMUM MULTI-SECTION OPENING SIZES:

144”w x 96”h 

(3658 mm x 2438 mm)

288”w x 48”h

(7316 mm x 1220 mm)

PERFORMANCE DATA  |  

Series 1000 SM

UL/ULC Approved Smoke Damper

FIG. 5.3 

Test damper is fully ducted with a 5 diameter duct run 

upstream, and a 6 diameter duct run downstream.

Pressure drop values are based on Flanged to Duct install type. 

Pressure drop will be greater for In Duct install type dampers.

TAMCO JUNE, 2016

www.tamcodampers.com

© T.A. Morrison & Co. Inc., 2016

T.A. Morrison & Co. Inc. certifies that 
the TAMCO Series 1000 SM UL/ULC 
Approved Smoke Damper shown 
herein is licensed to bear the AMCA 
Seal. The ratings shown are based on 
tests and procedures performed in 
accordance with AMCA Publication 511 
and comply with the requirements of 
the AMCA Certified Ratings Program. 
The AMCA Certified Ratings Seal 
applies to air performance ratings.

Summary of Contents for 1000 SM Series

Page 1: ... Smoke dampers are custom made to required size without blanking off free area 9 Smoke dampers are available with parallel blade action CONSTRUCTION OPTIONS For each option listed replace the lines above with their corresponding lines below MR MOISTURE RESISTANCE OPTION 1 Extruded aluminum 6063 T5 smoke damper frame is not less than 0 080 2 03 mm in thickness Damper frame is 4 101 6 mm deep x 1 25...

Page 2: ...unted on a jackshaft If actuator side of damper is to be connected to duct work smoke damper assembly will have to be installed in a sleeve 17 Options Auxiliary switches 18 Actuator quantity and location requirements are shown in and must be in accordance with TAMCO UL ULC Approved Smoke Damper Configurations 38 SUBMITTAL DATA Series 1000 SM UL ULC Approved Smoke Damper 2 TAMCO Series 1000 SM meet...

Page 3: ... mm greater than opening width and height dimensions MINIMUM SECTION SIZE 11 w x 6 h 280 mm x 153 mm MAXIMUM SECTION SIZE 12 ft 1 1 m 36 w x 48 h 915 mm x 1220 mm Extended Rear Flange install type dampers are not designed so that the front of the damper may be inserted into an opening as the side frame members extend to the full height of the rear flange EXTERNAL ACTUATOR Both front and rear flang...

Page 4: ...ch 111023 Shelf 24 PB Jumper 1 5 625 Jumper Blade Size 56 9896 GREY PARALLEL E 23F LEFT MILL BOTH 1 5 69000 DRIVE S10080080 BATCH 111023 Shelf 24 Item 7 Section 4 Item 7 S10080080 180 000 X 120 000 Series 1000 SM PARALLEL PO 123456 FLANGED TO Project ANYTOWN CITY HALL Tag OAS 1EA Batch 111023 Shelf 21 PB Jumper 1 5 625 Jumper Blade Size 56 9896 GREY PARALLEL E 23F LEFT MILL BOTH 1 5 69000 DRIVE S1...

Reviews: