Open the OY1410 using a screwdriver. Replace the right cable gland with the supplied blind 
plug. The enclosure has two openings that can be used for wall mounting. 
 
The cable from IWM-PL3 and IWM-PL4 has four wires. Cut the white wire since it will not 
be used and might cause short circuits if it is left unconnected inside the OY1410. Feed the 
cable though the left cable gland. 
 
Connect the IWM-PL3 or IWM-PL4 
according to the table below as illustrated 
by the picture to the right. 

White cable 

Cut 

Yellow cable 

Ch2 0-10V 

Green cable 

Ch1 0-10V 

Brown cable 

GND 

 
Make sure that both jumpers are set to 0-10V as illustrated by the picture below. 
  

 
After that you install the (replaceable) batteries, 
which activates the unit, you close the box and 
start measuring your data! 
 
 

 

Summary of Contents for OY1410

Page 1: ...epool visualization layer and information for advanced users The OY1400 Industrial communication and control unit is designed with focus on ease of use and reliable operation in LoRaWAN networks The p...

Page 2: ...Dev EUI also can be found on the outside of the unit 2 App Key These codes are unique for each sensor The Dev EUI can be seen as a simple identification code the App Key is a securely generated authe...

Page 3: ...Set depending on watermeter see table below Pulse ratio X Set to same a K index OUT3 Absolute count Pulse length 80 The K index and Pulse ratio X defines the number of liters per pulse It is important...

Page 4: ...circuits if it is left unconnected inside the OY1410 Feed the cable though the left cable gland Connect the IWM PL3 or IWM PL4 according to the table below as illustrated by the picture to the right W...

Page 5: ...r If you require more advanced information on the OY1410 Pulse meter please check the next sections 3 Open the unit connect the sensor and verify the jumper settings 4 Install batteries activating the...

Page 6: ...he fraud detection indicator in the LoRa uplink message will be set in coming reports until the fraud detection indicator has been explicitly cleared using a LoRa downlink request The OY1410 also dete...

Page 7: ...Field Bytes Value Description Note Type 1 xx 0x01 Data 0x02 Command NACK Index 1 xx Command Index Data As defined for Command Index only for Type Data Downlink command network device Field Bytes Value...

Page 8: ...endian Minutes 1 10080 Query Set No Measurement interval in minutes Setting measurement interval resets the measurement timer 0x2B IWM data Counter Status Uint32 followed by Uint8 Big endian Count fol...

Page 9: ...is 1234HEX 4660 Status bit 0 is set indicating a reset has been detected Setting the reporting interval to 1440 minutes 24 hours Downlink command 012605A0 Reset the Status bits Downlink command 012D0...

Reviews: