Talgil DREAM 2 Manual Download Page 10

 

11

 

3.2.1 

THE LEDS AND THE BUZZER INDICATIONS     

 

The LEDs and the buzzer indications of the compact RTU are similar to the modular RTU. 
However there is a special ticking sound that can only be heard in the compact RTU which 
has digital inputs defined.  

3.2.2 

TESTING INPUTS AND OUTPUTS OF THE COMPACT RTU    

 

 

The unit is equipped with tools for testing the inputs and outputs under field conditions. There 
are  2  I/O  test  buttons,  when  number  1  is  pushed  the  first  input and  output  are  tested,  when 
number 2 is pushed the second input and output are tested.  
 
INPUT TEST 

– The test begins by pushing the appropriate test button and it is indicated by a 

long beep

 

Each change in the status of the selected input will generate a short beep of 

the buzzer

 

.  

 
OUTPUT TEST 

– While being in INPUT TEST, push the appropriate test button again, this will terminate 

the  INPUT  TEST  and  will  start  the  OUTPUT  TEST.    An  "open"  command  will  be  sent  to  the  selected 
output  followed  by  a  single  beep 

Another  push  of  the  test  button  generates  a  "close" 

command followed by a double beep

 



.  

Each push of the appropriate test button will switch the solenoid between "open" and "close" 
positions.  
 
The system will exit test mode and return to normal activity after 60 seconds without touching 
the buttons. 
 

3.2.3 

SELECTING THE DESIRED ANALOG INPUT TYPE     

 
The system can handle analog inputs of 4-20 mA or 0-2.5 volts. Next to the terminal block 
there is a jumper JP7 that when inserted as shown in the picture above makes the analog 
input to accept 4-20 mA signals. When the jumper is removed the accepted signal will be 0-
2.5 v 
 

3.3  

TECHNICAL INFORMATION 

 
 

The 2W interface 

 

Power supply 

12v DC 2.5 A 

Minimal supply voltage 

10.5v DC 

Load free consumption  

115-120 mA 

Consumption contributed by each RTU 

1.5 - 2.2 mA 

Output voltage

***

 

36v DC

***

 

Main fuse  

8A 

Line fuses 

2 x 1A 

 
 

The 2W RTU

 

Typical supply voltage

***

 

36v DC

***

 

Minimal supply voltage

***

 

 

20v DC

***

 

Consumption measured by 2W tester  

Test voltage    8v DC 

14v DC 
36v DC 

Compact RTU 

Economical RTU 

0 mA 

0 mA 

-

 

0.75 mA

 

0.5 mA

 

0.75 mA

 

Output voltage  

12-17v DC latch 

 pulse width 70 ms 

Digital inputs   

Dry contact 

Analog inputs  

4-20 mA or 0-2.5v externally energized 

*** in normal operation mode the output voltage of the 2W interface is varying in a high 
frequency and can not be measured by regular volt meters. The output voltage of 36v DC can 
only measured under special test mode. To put the 2W interface in special test mode, set the 
address switch to 000000 and press the RESET button. 

Summary of Contents for DREAM 2

Page 1: ...1 TALGIL COMPUTING CONTROL LTD NAAMAN CENTER HAIFA ACCO ROAD ISRAEL P O BOX 775 KIRYAT MOTZKIN 26119 TEL 972 4 8775947 8775948 FAX 972 4 8775949 2007 DREAM 2 WIRED RTU SYSTEM GUIDE...

Page 2: ...OF RTU UNITS 6 3 1 MODULAR RTUS 6 3 1 1 SETTING THE ADDRESSES OF THE DIGITAL AND ANALOG INPUTS 7 3 1 2 SETTING THE JUMPERS OF THE ANALOG PLUG IN BOARD 7 3 1 3 THE LEDS AND THE BUZZER INDICATIONS 8 3 1...

Page 3: ...low power consumption and may be powered by solar energy One DREAM may handle several single cable channels each channel may contain up to 60 RTUs all of them will be scanned second by second 1 1 THE...

Page 4: ...wired channels connected to the same Dream special wiring is required see appendix D 2 2 GROUND CONNECTIONS Inside the 2W RTU interface inside the lightning protection and in each RTU there are groun...

Page 5: ...MADE INSIDE THE DREAM 2 4 1 DECLARING THE 2W RTU INTERFACE During system configuration the DREAM has to be told about the 2W RTU interface that is connected to its Remote I O line This is done during...

Page 6: ...e can be up to 4 modules per RTU therefore the units may come with 0 2 4 6 or 8 outputs The digital inputs are built of plug in modules of 4 inputs there can be up to 2 modules per RTU and therefore w...

Page 7: ...8 N When there are both digital up to 4 and analog up to 2 inputs the digital inputs will be numerated as above but the analog inputs will occupy the addresses following RTU N as follows Analog input...

Page 8: ...le beep every 5 seconds indicating normal operation Otherwise there will be a long beep every 5 seconds During output test mode there is a short beep for open and 2 short beeps for close commands 3 1...

Page 9: ...n of the utility software includes additional information about the RTU including the number of available outputs and inputs analog or digital the pulse width and amplitude generated for opening and c...

Page 10: ...close positions The system will exit test mode and return to normal activity after 60 seconds without touching the buttons 3 2 3 SELECTING THE DESIRED ANALOG INPUT TYPE The system can handle analog i...

Page 11: ...1 0 0 1 0 19 1 1 0 0 1 0 20 0 0 1 0 1 0 21 1 0 1 0 1 0 22 0 1 1 0 1 0 23 1 1 1 0 1 0 24 0 0 0 1 1 0 25 1 0 0 1 1 0 26 0 1 0 1 1 0 27 1 1 0 1 1 0 28 0 0 1 1 1 0 29 1 0 1 1 1 0 30 0 1 1 1 1 0 31 1 1 1 1...

Page 12: ...1 The cable must be tested for continuity of its wires and for having good isolation between the wires and between each wire and the ground 2 Disconnect both ends of the cable under test including fr...

Page 13: ...he cable to the consumption of the interface unplug all the RTUs from the 2 wired line and reconnect the 2 wired line back to the interface At this stage the measured consumption of the interface may...

Page 14: ...Ah 12V Int 2W P N 12 V Rechargable battery 12V 7 Ah 12V 12V Int 2W N1 N1 N2 P S Int 2W N2 N3 Wiring of a DREAM system which is powered by AC and which contains multiple 2 wired interfaces P N P N 12 V...