5. INSTALLATION

4. WIRING

1. Loosen cover lock screw and detach the cover.

2. Open knockout hole.

3. Install the base on the wall.

*Two mounting pitches are available.

*When installed on wall corner, make use of knockouts on sides.

4. Connect wires to terminals (Refer to 4. WIRING)

*Plug up an opening of wiring hole .

5. Attach the cover, and tighten cover lock screw.

Model

PA-450EA

*The specifications are subject to change without notice.

6. OPERATION

Allowable wiring distance between

sensor and power source

     Size of wire used
AWG 20 (Dia. 0.80mm)
AWG 18 (Dia. 1.00mm)

Distance at 12VDC
   1,700m(5,600 ft.)
   2,700m(8,800 ft.)

The maximum wire length, when two or more units are connected, is the above distance divided by 

the number of units.

The protection circuit can be wired up to a distance of 1,000m(3,280 ft ) with AWG 22 (0.65mm dia.) 

wire.

1. Turn the power ON, and wait for approx. 1 minute until the alarm LED stops 

blinking.

2. Walk test in the protection area to check if an alarm is activated.  Check on 

both of the alarm LED and control panel.

It is important to check operation whenever the area of protection is changed.

3. After  correct  operation  has  been  confirmed,  turn  the  alarm  LED  OFF  with 

mode selector on PWB unit.  (When set at OFF, the alarm LED does not light 

even if an alarm is  activated.)

7. MODE SETTING

8. SPECIFICATIONS

9. EXTERNAL DIMENSIONS

PA-460EA

PA-450EA / PA-450PIA

PA-460EA

unit : mm(inch)

70(2.76")

45(1.77")

110(4.33")

70(2.76")

45(1.77")

110(4.33")

POWER

7to28VDC

8mA

non-polarity

N.C./N.O.

24V(AC/DC)

0.25A

N.C.

30V DC

0.1A

ALARM

TAMPER

29 Pairs

PA-450PIA

Body : resin(white)    Lens : resin(white)

90g (3.2oz)

Indoor use only (ceiling mount with optional attachment BCW-401)

without condensation

Autoreset : 3 minutes blinking, 47 minutes lighting and automatically reset

1/2/3/4 selectable

Vertically 3 steps

: Blinking at warming up

  

Lighting at alarm (LED disabled)

: Blinking at memory activated (3 min.)

       

Lighting at memory indication (47 min.)

N.C. 30V DC 0.1A 

Dry contact (Semi-Conductor) (N.C. / N.O. selectable)

Reset : Approx. 2sec.

Rating : 24V (AC/DC), 0.25A max. (protective resistance 3.3

Ω

8mA max. 

7 to 28V DC (non-polarity)

18 Pairs

Wide Angle

12m(

40

') max.

6 Pairs

Passive infrared

Wide Angle

12m(

40

'

)

max.

1/2 selectable

Vertical curtain

 18m(

60

') max.

Appearance

Weight

Mounting position

Ambient temperature range

Alarm memory

Pulse count

Sensitivity

Coverage adjustment

Alarm LED (Red)

Tamper output

Alarm output 

Current consumption

Supply voltage

Sensitive zone

Coverage

Detection system

60%/80%/100%/120% selectable

-15°C to + 55°C (+5°F to + 131°F)

In Japan

Takex America Inc.

Takenaka Engineering Co., Ltd.

https : // www. takex-eng. co. jp /

Takex America Inc.

https : // www. takex. com

Takex Europe Ltd.

https : // www. takex. com

In the U.S.

In the U.K.

In Australia

Aviary Court, Wade Road,

Basingstoke, Hampshire. RG24 8PE, U.K.

Tel  : (+44) 01256-475555

Fax : (+44) 01256-466268

4/15 Howleys Road, Notting Hill,

VIC, 3168

Tel  : +61 (03) 9544-2477

Fax : +61 (03) 9543-2342

https : // www. takex. com

83-1, Gojo-Dori, Sotokan Nishi-iru, Higashino,

Yamashina-ku, Kyoto 607-8156, Japan

Tel  : 81-75-501-6651

1810 Oakland Rd, Suite F, 

San Jose, CA 95131, USA

Tel  : 408-747-0100

Fax : 408-734-1100

Limited  Warranty  :

 

TAKEX  products  are  warranted  to  be  free  from  defects  in  material  and  workmanship  for  12  months  from  original  date  of 

shipment. Our warranty does not cover damage or failure caused by Acts of God (including inductive surge by lightning), abuse, misuse, abnormal usage, 

faulty installation, improper maintenance or any repairs other than those provided by TAKEX. All implied warranties with respect to TAKEX, including 

implied warranties for merchantability and implied warranties for fitness, are limited in duration to 12 months from original date of shipment. During 

the Warranty Period, TAKEX will repair or replace, at its sole option, free of charge, any defective parts returned prepaid. Please provide the model 

number of the products, original date of shipment and nature of difficulty being experienced. There will be charges rendered for product repairs made 

after our Warranty period has expired.

When  an  alarm  has  been  activated,  the  alarm  LED  blinking  for  3  min.  and 

then  remains  lit  for  47  min.  It  automatically  reset  and  memory  is  also 

canceled. In case that the sensor retriggers while its LED is lit, LED lights for 

further 47 min. after that.

count [1]       :  Most sensitive.

count [2]       :  Normally set to this position.

count [3]/[4]  :  Least sensitive, prevents false alarms caused by temperature

fluctuation.

Sensor operation can be changed by mode selector on PWB unit.

Auto reset operation : 

2 : Alarm memory

1 : Alarm LED

LED disabled  

Alarm LED OFF:

LED operates according to alarm memory function.

*Do not use count [3]/[4] for Vertical curtain(PA-460EA).

Factory set

1

2

3

4

5

6

7

8

ON

60%

80%

100%

120%

1

2

3

4

ON

Lights at alarm  

No operation

OFF

ON

Auto reset operation

3 : Selection of alarm contact

Open at alarm

N.C.

N.O.

Close at alarm

OFF

4,5 : Sensitivity

6,7 : Pulse count

8 : Walk test mode

ON

OFF

(*)

 : 

factory set

(*)

(*)

(*)

(*)

(*)

(*)

Walk test mode ON : 

After warming up or turning on the switch, the LED lights when the sonsor 

detects for 5 minutes, the alarm memory is not accepted for 5 minutes as well.

After 5 minutes, the LED function follows “Alarm LED” settings.

2021.8.26