④
The angle of detection area can be adjusted up to 30°
toward the direction of the ‘Front mark’ in 5° increments.
Adjust the angle to cover the desired area.
Move the area selector inside of the sensor unit, and set
the detection area based on the glass surface to be
protected. Whilst checking the indicator position.
■
Terminal configuration
DC 9 V to 28 V, 25 mA or less (no polarity)
Contact method : Dry solid-state contact
(N.O./N.C. selectable)
Contact operation : One-shot (approximately two seconds)
Contact rating : DC 30 V (AC 24 V)/0.25 A (resistive load)
EXLOWLQFRQWDFWSURWHFWLRQUHVLVWDQFHї
Contact method : Dry contact (N.C.)
Contact operation : Continuous output when the sensor unit
is detached
(until the sensor unit is mounted)
Contact rating : DC 30 V/0.1 A (resistive load)
Power
input
Alarm
output
Tamper
output
*Use for interconnected wiring.
Reserve
terminal
Power input
Alarm output
Tamper output
Reserve terminal
Release button
*When connecting two or more units to the same cable, the maximum
distance is the above value divided by the number of units.
*Signal wires can be connected in a distance of up to 3,300ft(1,000 m)
when telephone wires of
φ
0.03
”
(
φ
0.65 mm) are used.
●
When using single wires
■
Maximum allowable wiring distance
[between the sensor and power equipment]
■
Basic connection
[connection example when using multiple units]
Distance between
wall and sensor
Distance between
ceiling and center of glass
Area adjustment angle
(from 0° to 30°)
Center of
the area
Area selector
Indicator
Front mark
0°
30°
*The detection area has a spread. Set the area so that the center of the detection area is roughly to the center of the window.
●
Usable electric cables
Single wire :
φ
0.4mm
〜 φ
1.2mm
0.2m
㎡ 〜
1.0m
㎡
AWG24
〜
AWG16
・
can be interconnected. The terminals of same number are connected inside.
・
The terminal block is a screw-less type. To remove an electric cable, push the release button on the
terminal block, and pull out the cable.
・
When you strip insulation of the cables to be connected on the terminal block, refer to the strip
gauge provided on the label of the sensor unit.
Power
}
Signal input
Sensor
(N.C.)
Sensor
(N.C.)
Tamper input
6
DETECTION AREA ADJUSTMENT
7
WIRING
Distance between
wall and sensor
1.5
’
(0.5m)
3.3
’
(1.0m)
4.9
’
(1.5m)
6.6
’
(2.0m)
Distance between the ceiling
and center of glass
3.3
’
(1m)
30°
30°
30°
30°
6.6
’
(2m)
15°
30°
30°
30°
10
’
(3m)
10°
20°
25°
30°
13
’
(4m)
5°
15°
20°
25°
16.5
’
(5m)
5°
5°
15°
20°
(when DC 12 V is supplied) (when DC 24 V is supplied)
φ0.03
”
(φ
0.65mm) Up to 3,000ft( 900m) Up to 15,000ft( 4,600m)
φ0.04
”
(φ
0.9mm) Up to 5,600ft(1,700m) Up to 29,000ft( 8,800m)
φ0.05
”
(φ
1.2mm) Up to 10,000ft(3,100m) Up to 52,000ft(15,700m)