2 COMMON SPECIFICATIONS
11
2
2
COMMON SPECIFICATIONS
This chapter explains the common specifications of an option driver.
For the access specifications of each option driver, refer to the corresponding one of the following:
Page 29 Rockwell Connection, Page 33 Siemens Connection, Page 39 Omron Connection
Item
Specification
Access target device
Maximum number of settings (per option
driver)
64 devices
Device tag component
Maximum number of settings (per access
target device)
1024 components
Maximum size (per access target device)
81920 bytes
Data type
• Bit
• Word [unsigned]/Bit string [16-bit]
• Double word [unsigned]/Bit string [32-bit]
• Word [signed]
• Double word [signed]
• 16bit BCD
• 32bit BCD
• Single-precision real number
• Double-precision real number
• Character string [Unicode]
• Character string [ASCII/SJIS]
Array type of an array tag
Continuous array
Maximum size of an array tag (per access
target device)
81920 bytes
Job
Access type
General access
Access interval
• 1 to 9
×
100 ms
• 1 to 3600 s