Controlling with External Analog & Contact Signals
129
Toggling Output ON/OFF with External Contacts
*This function can not use 1000V type.
The output for HX-S-G4 power supplies can be toggled ON/OFF using outputs from small capacity contact or
photocoupler.
Use a photocoupler or a small signal relay or switch with a minimum contact capacity of 5V, 2.5mA.
FUNCTION settings must be changed to "Valid" for Output ON/OFF Control at External Contact Points to be used.
Factory default settings are set to "Invalid".
Connecting
Wire the cables to the external control connector (accessory) terminals No. 9 and 22.
The external control connectors can be simply removed by pushing down the lock levers on both sides.
External Control Connector
Photocupler or Contact
9
Twisted-Pair Wire
22
Open:Putput OFF
Closed:Output ON
Toggling Output ON/OFF with External Contacts
Not suited for power contacts such as main contacts for electromagnetic contactors or power
relays etc.
For output ON/OFF toggle contact, please use an insulated contact point or open collector.
!
CAUTION
The common for contact point signal (No. 22) is internally connected to the minus side of
the output terminal.
Isolation for the wire connecting to the external control should be more than the relative
ground voltage of this product.
Otherwise, the user may receive electric shock.
Please take note that OUPUT lamp may be lit by turning off the operating power supply during
the OUTPUTand it is not abnormal state.
!
CAUTION
Summary of Contents for HX-S-G4 Series
Page 157: ...Special Loads 157 This page is blank...
Page 161: ...Maintenance 161 This page is blank...
Page 197: ...Specifications 197 External Diagrams 1 HX S 030 200G4 F I...
Page 198: ...Specifications 198 2 HX S 030 400G4 F I...
Page 199: ...Specifications 199 3 HX S 060 100G4 F I...
Page 200: ...Specifications 200 4 HX S 060 200G4 F I...
Page 201: ...Specifications 201 5 HX S 0500 12G4 F I...
Page 202: ...Specifications 202 6 HX S 0500 24G4 F I...
Page 203: ...Specifications 203 7 HX S 01000 6G4 F I...