Tadiran Telecom TAD2U18MOU Installation Manual Download Page 15

16

31-5000001   Rev. 1

ENGLISH  

Step 3 - Installation of the Outdoor Unit (Cont.)

G.  System Evacuation

NOTE–

 Do not open service valve.

•   Remove the suction line cap and attach a manifold 

gauge, micron gauge, and vacuum pump to 

the suction line port using adapter AD-87 (see 

illustration).

•   Evacuate the system to at least 350 microns.

•   Close the vacuum pump valve and check the micron 

gauge.  If the gauge rises above 150 microns in 60 

seconds, the evacuation is incomplete or there 

is a leak in the system.  If the gauge does not rise 

above 150 microns in 60 seconds, the evacuation is 

complete.

•   Once evacuation is complete, remove the adapter 

and hose connection from the suction line port and 

replaced the cap.

F.  Leak Test 

FlexFit multi-zone models 2U18MS and 3U24MS do 

not have master service valves.  Perform the following 

steps for EACH line set.  

The FlexFit multi-zone model 4U36MS and Arctic multi 

models 2U20EH and 3U24EH have a master service 

valve.  Performing the following steps will test ALL line 

sets.

•   Remove the cap on the service valve.

•   Using a tank of dry nitrogen and approved regulator, 

charge the system with 150 psig of dry nitrogen 

using mini-split adapter to connect the valve. 

•   Check for leaks at the flare fittings using soap 

bubbles or another detection device.  If a leak is 

detected, make repairs to the fittings and recheck.  

If no leaks are detected within 3 minutes, proceed.

•   Using the same tank/regulator, charge the system 

to 300 psig.

•   Check for leaks as earlier.  If no leaks are detected 

within 3 minutes, proceed.

•   Using the same tank/regulator, charge the system 

to 500 psig.

•   Check for leaks as earlier.  Keep system pressurized 

for at least 20 minutes.

WARNING

 Do not use acetylene, oxygen or 

compressed air or mixtures 

containing them for pressure testing.  Do not use 

mixtures of hydrogen containing refrigerant and air 

above atmospheric pressure for pressure testing as 

they may become flammable and could result in an 

explosion.  Refrigerant, when used as a trace gas, 

should only be mixed with dry nitrogen for pressurizing 

units.  Failure to follow these recommendations could 

result in death or serious injury as well as equipment or 

property damage.

E.  Install Copper Lineset

•   The standard line set length is 25 feet.  If 

the installation length is different, adjust the 

refrigerant charge by 0.2 oz/ft if the liquid line 

is 1/4”, or 0.5 oz/ft if the liquid line is 3/8”.

•   See table on page 15.

•   Cut the line set to length.

•   Place nut over the pipe and then flare with the 

R-410A flaring tool.

 

NOTE: 

Follow standard practices for creating 

pipe flares.  When cutting and reaming the 

tubing, use caution to prevent dirt or debris 

from entering the tubing.  Remember to place 

nut over the tubing before flaring.

•   To join the line set, directly align the tubing 

flare to the fitting on the other pipe.  Slide the 

nut onto the fitting and hand tighten.

•   Torque the fittings according to the 

specifications shown in the torque chart below.

Half union

Flare nut

Torque wrench

Spanner

Forced fastening without careful centering may

damage the threads and cause a refrigerant leak.

Pipe Diameter(

ǿ

)

Fastening torque

Liquid side6.35mm(1/4")

18N.m/13.3Ft.lbs

Liquid/Gas side9.52mm(3/8") 42 N.m/30.1Ft.lbs

Gas side 12.7mm(1/2")

55N.m/40.6Ft.lbs

Gas side 15.88mm(5/8")

60 N.m/44.3Ft.lbs

•   Two wrenches are required to 

join the flare connection; one 

standard wrench and one torque 

wrench adjusted to the proper 

settings.

•   Repeat the process for 

attaching the other end of the 

line set.

Half union

Flare nut

Torque wrench

Spanner

Forced fastening without careful centering may

damage the threads and cause a refrigerant leak.

Pipe Diameter(

ǿ

)

Fastening torque

Liquid side6.35mm(1/4")

18N.m/13.3Ft.lbs

Liquid/Gas side9.52mm(3/8") 42 N.m/30.1Ft.lbs

Gas side 12.7mm(1/2")

55N.m/40.6Ft.lbs

Gas side 15.88mm(5/8")

60 N.m/44.3Ft.lbs

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

A

B

A

B

Outdoor unit

Indoor unit

Oil trap

CAUTION

Max. Elevation: A Max

= 33ft / 10m (09k / 12k)

= 50ft / 15m (18k / 24k)

In case the height of A is more than

15ft / 5m, an oil trap should be

installed every 16-23ft /5-7m

Max. Length: B Max

= 50ft / 15m (09k / 12k)

= 83ft / 25m (18k / 24k)

INSTALLATION INSTRUCTIONS

Summary of Contents for TAD2U18MOU

Page 1: ...Installation Manual Design may vary by model number Ductless Multi Zone with Highwall Indoor Unit...

Page 2: ...________ Serial number _______________________________________ Date of purchase IMPORTANT SAFETY INFORMATION 4 INSTALLATION INSTRUCTIONS 6 Step 1 9 Step 2 11 Step 3 13 Step 4 17 LIMITED WARRANTY 18 TA...

Page 3: ...less they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the app...

Page 4: ...ipes that have a collapsed deformed or discolored portion especially on the interior surface Otherwise the expansion valve or capillary tube may become blocked with contaminants Improper pipe selectio...

Page 5: ...tool Hex wrench Hole saw 2 1 4 Insulation Refrigerant scale Level Manifold gauge set Measuring tape Micron gauge Mini split adapter 5 16 F to 1 4 M Nitrogen Pipe cutter PVC pipe Razor knife Reamer Sa...

Page 6: ...6MOU Unit D Unit C Unit B Unit A 36K TWO 31K 24K 7K 27K 18K 9K 33K 24K 9K 30K 18K 12K 36K 24K 12K 36K 18K 18K 42K 18K 24K 48K 24K 24K THREE 32K 18K 7K 7K 38K 24K 7K 7K 28K 12K 9K 7K 34K 18K 9K 7K 40K...

Page 7: ...constructed with a solid material to block the sea breeze The height and the width of the wall should be 1 5 times larger than the size of the outdoor unit Also allow at least 28 700mm between the pr...

Page 8: ...ce solid enough to bear the weight and vibration of the OD unit and where the operation noise will not be amplified Choose a location where the hot air discharge and or noise will not create a nuisanc...

Page 9: ...ldren may climb onto the outdoor unit and fall off of the balcony Do not install the outdoor unit in thw following areas Area filled with mineral oil or containing a large amout of splashed oil or ste...

Page 10: ...stant pitch downward for proper water flow There should be no kinks or rises in the tubing which may cause a trapping effect of the water see illustration Optional Can use PVC pipe by connecting a 1 I...

Page 11: ...1in 126mm 1 614in 41mm 50 T 2 1 4in 57mm 1 614in 41mm 4 882in 124mm 2 1 4in 57mm 70 T 3 150in 80mm 1 85in 47mm 35 T 2 1 4in 57mm Capacity BTUh Bracket Style Part Number Factory Reference Number 07K 09...

Page 12: ...average snowfall B Attaching Drain Elbow to Outdoor Unit If required attach the supplied drain elbow to the outdoor unit Connect extension piping as needed not supplied see illustration NOTE The drain...

Page 13: ...onnections match the indoor connections wire for wire Ensure each wire is under the screw terminal plate and the plate is tightened Ensure the 14 4 wire cable is secured under the strain relief bracke...

Page 14: ...dicated by the corresponding LED for that circuit being lit constantly LED 1 piping circuit A LED 2 piping circuit B After the check has completed if all wiring is correct the numeric display will ind...

Page 15: ...used as a trace gas should only be mixed with dry nitrogen for pressurizing units Failure to follow these recommendations could result in death or serious injury as well as equipment or property damag...

Page 16: ...ant after evacuation using a digital scale NOTE Charge liquid only Fill out the refrigerant charge label using indelible ink Place the factory refrigerant charge found in table on page 15 in the box n...