
RF INITIALIZATION
(assign RF thermostat to zones)
To enter in RF init mode, you must enter in the INSTALLATION PARAMETER MENU (see above)
With
or
keys choose the
rf init
parameter. Now press
key, then “
01 init
” (fig 1) is
displayed and the first zone LED blinks in green.
Fig. 1
Fig. 2
Fig. 3
1.
You can activate this zone with the
key. The LED blinks very fast green (zone activated).
Use
&
keys to change and add further zones.
The LED of the activated zone before stops blinking and shines green.
With
key you assign the blinking zone.
If you press
a second time the zone is deselected.
Pleas
e keep in mind, that you don’t press the
or minus
keys. It can influence your pro-
gramming.
2.
Repeat step 1 till all wanted zones are choosen.
3.
When you have correctly selected the zones to be assigned to an RF thermostat, go to the
thermostat and activate its RF initialization (see RF user manual)
4.
The LED of the activated zone/s should go out. The LED of the next, not activated zone can blink
nevertheless. During the thermostat RF transmission you can see on the display 2 lines of
squares running. (see Fig. 2)
5.
If the RF thermostat has been assigned correctly to the zone/s, deactivate the RF initialization of
the thermostat ( switch it off). During the thermostat RF transmission you can see on the display 1
line of squares running. (see Fig. 3)
6.
If you d
on’t see any squares running, during step 4 or 5, the RF receiver could not identify a RF
signal. Check if the antenna has been connected correctly and / or repeat the steps 1
– 5.
7.
Repeat the Step 1 to 6 to assign the others thermostats to the remaining zones.
8.
To exit and save the configuration of the
rf init
mode and come back to the main menu press
key during 5 seconds.
You can now perform a radio range verification:
1.
Place your RF thermostat in the room where you need to regulate the temperature.
2.
Close the door and come back to the
TIMER RF
.
3.
Check if the green LED, of the assigned zone, blinks at each radio transmission. A transmission
happens every 3 minutes.
4.
If the LED, of the assigned zone, blinks 4 times a second the installation is correct.
5.
If the LED blinks irregulary, you are at the range limit. Install the thermostat closer to the receiver.
6.
If the LED doesn’t blink at all within 5 min, you are out of range. In this case the antenna has to be
installed vertical. It might be essential to install the antenna closer to the thermostat. It some cas-
es it helps to install the antenna closer out of the metal distribution box.
As an alternative you can use the alarm for a missing radio transmission signal (see
INSTALLATION PARAMETERS MENU, F.1). If the alarm is activated, let installation run for mini-
mum 30 min. If there is no alarm signal the installation is correct..
INSTALLATION PARAMETERS MENU
TECHNICAL CHARACTERISTICS
With
&
keys, go to
mode. Then press
continuously and press
at the same
time. You will enter in the installation parameters menu (
).
With
/
select the desired parameter to change. Press
to toggle the parameters.
After 30sec the TIMER will come back automatically in the main menu.
F.O Operation mode PROG/ EASY
select PROG for complete weekly programmable interface
select EASY for simple interface (only
,
,
and
modes)
F.1
Alarm BUZZ/no
select bUZZ for enabling the alarm sound if a zone is in Lost Thermostat Reception
Alarm.
F.2
Type of actuator NC/NO
select NC to use the system with Normally Closed actuator valves
select NO to use the system with Normally Open actuator valves
F.3
Valve protection ACtU/no,
select ACtU to perform a 5 minute actuator exercise each 12h00 only on the zones that
have not been heating since 24 Hours.
J.O
Temperature display °C/°F
Select °C for a temperature display in Celcius.
Select °F for a temperature display in Fahreneit.
J.1
Time display 12h/24h
Select 12H for AM/PM clock display.
Select 12H for 24H clock display.
J.2
Minutes regulation cycle --:15 / --:8
select --:8 minutes only if your installation as fast thermal reacting behavior
J.3
Proportional band for regulation 2.0°K/ 1.2°K
select 1.2°K for more precision only if your installation has fast thermal reacting behav-
ior.
Beware because selecting 1.2°K can result in a oscillating temperature regulation if the
system speed constant is to slow (temperature will constantly oscillate more than
1.2°K)
J.5
PUMP protection PUMP/no,
select PUMP to perform a 2 minute pump exercise each 12h00 only if the PUMP Relay
has not been activated since 24 Hours.
J.6
Intelligent Temperature Control System ItCS/no,
select ItCS to activate the Intelligent Temperature Control System. The Timer RF will
learn and start in advance the heating of the zones to assure that the desired tempera-
ture is already reached when following the program.
.Pr Clr Master Reset
Press
during 5sec to reset your system:
All parameter are reloaded with default values.
All RF configurations (Thermostat / Receiver) are erased.
rF Init
Press
to enter RF INITIALISATION MODE
(see the RF INITIALISATION part )
*NB: Default factory parameters are underlined
MASTER RF 6 ZONES
+
RF SLAVEBOX 4 ZONES + TIMER RF
Operating temperature
0 - 50 °C
Regulation
characteristics
Proportional Integral regulation (adjustable see installation
menu) Cycle: 15 min / 8 min
Anti-short cycle: 3min in OFF, 2min in ON.
Outputs:
Zone:
Relay 5A 250VAC.
Information: If a 24 VAC system with a 60 V/A trafo is used
it’s possible to connect max. 18 actuators.
RF TIMER and
connecting
boxes
All installations have to be equipped with a TIMER and a
MASTER box. (Extension module SB optional, max 12
zones)
Radio frequency
868 MHz, <10 mW
Range of approximately 180 meters in open space.
Range of approximately 50 meters in residential environ-
ment.
Certifications
CE. EN 300220-1, EN 301489-1
(Radio frequencies certifications)
Power Supply
230VAC -10 % (or 24VAC
–10%,
attention
: different
Timer)
Software Version
2.0x