background image

6

Motor Protection

See the motor nameplate for electrical connection/wiring
diagram.
Taco pumps must be used with the proper size and type of
motor starter to ensure protection against damage from low
voltage, phase failure, current imbalances, and overloads.
The overload should be sized to trip at the full-load current
rating of the motor.

OPERATION

Priming

Hazardous pressure.

Do not run the pump

with the discharge valve closed; the water in the pump may
boil, causing risk of explosion and steam burns to anyone
nearby.

Hazardous voltage.

Disconnect all power to

the pump before servicing or working on the pump. Make
sure that the power is locked out and that the pump cannot
be accidentally started.

NOTICE:

Under no circumstances should the pump be

operated without flow through the pump. 

Never 

operate

the pump dry.

Operation of closed systems or open systems with the
liquid level above the pump priming plug:

1. Close the discharge isolating valve and loosen the

needle valve in the vented priming plug in the pump
head (Figure 7). Do not remove the needle valve.

Risk of water damage and injury. Watch the

direction of the priming plug and make sure that the liquid
escaping from it does not injure persons nearby or damage
the motor or other components. In hot water installations,
pay particular attention to the risk of injury from scalding
hot water.

2. Slowly open the isolation valve in the suction pipe until

a steady stream of liquid runs out the vent in the priming
port.

3. Tighten the needle valve to 25 inch-pounds torque.

Completely open isolation valves.

NOTICE:

Please turn to “Starting”, Page 7, before proceeding

any further.

Operation of open systems with the liquid level below the
top of the pump:

NOTICE:

The suction pipe requires a check valve or

isolation valve.

1. Close the discharge isolation valve.
2. Remove the vented priming plug.
3. Pour liquid through the priming port until the suction

pipe and the pump are completely filled with liquid.

4. Replace the vented priming plug and tighten it securely.
5. Repeat steps 1-4 until the pump is primed.

NOTICE:

Please turn to “Starting”, Page 7, before proceeding

any further.

No-Flow Operation

This pump must not operate at no flow. To prevent no-flow
operation, install a bypass orifice, sized to allow the
minimum rate of flow to pass the pump at all times (see
Table III). Taco recommends a 3-inch long nipple-style
orifice, which will compensate for erosion and ensure the
correct minimum flow for extended time periods. Inspect
the orifice and bypass loop periodically to make sure that it
is not obstructed, eroded, or leaking and that the correct
minimum flow is maintained. See Table V to select the
correct orifice size for your installation.

Checking Direction of Rotation

NOTICE: 

Do not disconnect the motor from the shaft to

check the direction of rotation. If you remove the coupling,
then you must adjust the shaft position when you reinstall
it. This must be done before starting the pump.

Arrows on the pump head show the correct direction of
rotation. When seen from the motor fan, the pump should
rotate 

counterclockwise (

)

. For pump motors without a

fan remove one of the coupling guards and look at the
coupling to determine the direction of rotation. Turn off the
pump and replace coupling guard.

NOTICE: 

Do not check the direction of rotation until the

pump has been filled with liquid. See “Priming”, at left and
above.

1. Switch power off.
2. Remove the coupling guard and rotate the pump shaft to

be certain it can turn freely. Replace the coupling guard.

3. Verify that the electrical connections are in accordance

with the wiring diagram on the motor.

4. If the fan is visible, turn on and off to verify rotation.

Vented
Priming
Plug

Drain
Plug

Back off needle valve 
to vent air. Retighten 
to 25 in.-lbs. when vent 
port runs a steady stream 
of water.

FIGURE 7 - Priming and Drain Plugs

Number

Pump Model

of Stages

VM01

VM02

VM04

VM06

2 through 6

1/8”

1/8”

3/16”

1/4”

7-8

1/8” 1/8”

3/16”

3/16”

9 through 16

1/8” 

1/8”

1/8”

3/16”

17-18

1/8” –

TABLE V – Bypass Orifice Chart

Summary of Contents for VM0102

Page 1: ... and Three Phase 60 Cycle Record the following information from the motor and pump nameplates for future reference Pump Model No Bill of Material No Motor Model No Motor Serial No H P Volts Hz Ph Rated Amp Draw Taco Inc 1160 Cranston Ave Cranston RI 02920 BE807 TACO 12 5 06 ...

Page 2: ...y glasses at all times when working on pumps INSPECT THE SHIPMENT The vertical multistage centrifugal inline pump has been carefully inspected and packaged to assure safe delivery Inspect the pump and fittings and report to the carrier any items which are damaged or missing CONFIRM YOU HAVE THE RIGHT PUMP APPLICATIONS AND OPERATING RANGES Multistage in line centrifugal pumps are designed for liqui...

Page 3: ...12 3 8 11 1 8 5 1 4 2 25 5 8 7 1 8 VM0204 13 1 2 11 1 8 5 3 4 2 1 8 26 5 8 7 1 4 VM0205 14 1 2 12 5 3 4 2 1 8 28 5 8 7 1 4 VM0206 16 13 5 8 6 7 8 2 7 8 32 1 2 8 1 2 VM0207 18 1 8 13 5 8 6 7 8 2 7 8 34 5 8 8 1 2 VM0208 18 1 8 13 5 8 6 7 8 2 7 8 34 5 8 8 1 2 VM0210 20 1 4 15 1 4 8 3 3 8 38 7 8 10 5 8 VM0212 22 3 8 15 1 4 8 3 3 8 41 10 5 8 VM0214 24 1 2 15 1 4 8 3 3 8 43 1 8 10 5 8 VM0216 26 5 8 15 1...

Page 4: ...ling and lubrication of the pump See Table III Run the bypass relief valve and discharge pipe to a floor drain or a tank for collection Suction pipe should be adequately sized See Table IV and run as straight and as short as possible to keep friction losses to a minimum Pipes valves and fittings must have a pressure rating equal to or greater than the maximum system pressure Pressure check the dis...

Page 5: ...ied electrician in accordance with the National Electrical Code and all local codes and regulations Make sure that the motor voltage phase and frequency match the incoming electrical supply The proper operating voltage and other electrical information can be found on the motor nameplate These motors are designed to run up to 10 of the nameplate rated voltage The wiring connection diagram can be fo...

Page 6: ...tion pipe and the pump are completely filled with liquid 4 Replace the vented priming plug and tighten it securely 5 Repeat steps 1 4 until the pump is primed NOTICE Please turn to Starting Page 7 before proceeding any further No Flow Operation This pump must not operate at no flow To prevent no flow operation install a bypass orifice sized to allow the minimum rate of flow to pass the pump at all...

Page 7: ...lating Minimum Inlet Pressure Minimum inlet pressure is required to avoid cavitation in the pump and is calculated as follows H Pb NPSHR Hf Hv Hs H Minimum Inlet Pressure in Feet of Head Pb Barometric Pressure in Feet 1 Bar 29 92 inches of Mercury Hg 1 PSI 2 31 Ft of Head 1 Bar 33 5 Ft of Head NPSHR Net Positive suction head required To be read from the NPSHR curve Figure 8 at the highest flow the...

Page 8: ...ws that hold the motor and the motor bracket together then tighten evenly and diagonally See Table VIII Page 11 for torque specifications 12 Reinstall the coupling pin Key No 5 in the shaft 13 Reinstall the coupling halves Key No 2 on the pump and motor shaft Make sure to engage the couping pin Key No 5 NOTICE Be sure coupling surfaces are thoroughly clean prior to assembly 14 Snug up the socket h...

Page 9: ... only 12 Clean the O Ring seat and install a new O Ring Key No 21A VM01 and VM02 only 13 Install a new lower sleeve O Ring 14 Install the new stack without the stainless steel sleeve NOTICE Be sure to align either the small priming hole or the suction interconnector pin hole located on the bottom stage of the stack properly in the base of the Suction Discharge Key No 21 See Figure 11 15 Use a rubb...

Page 10: ...k and clean all sealing and gasket surfaces with a clean wet cloth Replace all seals gaskets and O Rings 1 Turn the motor bracket Key No 6 upside down 2 Moisten the seal seat in the motor bracket with a small amount of water 3 Lubricate the larger diameter O Ring Key No 15A with a small amount of water and install it on the stationary half of mechanical seal Key No 15B 4 Press the stationary half ...

Page 11: ...he pump meets required performance and is operating smoothly and quietly 2 There are no leaks 3 The motor is not overheating 4 Remove and clean all strainers and filters in the system 5 Verify amp draw check motor amperage 6 Pump wear rings and shaft require no regular maintenance 11 Coupling Motor Staybolt Stack Nut Socket Head Socket Head Socket Head Capscrew Capscrew Hex Hex Hex Hex Screw Screw...

Page 12: ...er 12 Lockwasher 13 Capscrew 14 Spring Ring 15 Seven Part Mechanical Seal Includes 15A thru 15G 15A O Ring Larger Diameter 15B Stationary Half of Mechanical Seal 15C Rotating Half of Mechanical Seal 15D O Ring Smaller Diameter 15E Flat Washer 15F Spring 15G Mechanical Drive Ring 16 Replacement Stack Kit Incl Key Nos 16A thru 16L Key No Description 16A Shaft 16B Stop Ring 16C Mechanical Seal Spacer...

Page 13: ... Plug 11 Flat Washer 12 Lock Washer 13 Capscrew 14 Conic Spring 15 Seven Part Mechanical Seal Includes 15A thru 15G 15A O Ring Larger Diameter 15B Stationary Half of Mechanical Seal 15C Rotating Half of Mechanical Seal 15D O Ring Smaller Diameter 15E Flat Washer 15F Spring 15G Mechanical Drive Ring Key No Description 16 Replacement Stack Kit Incl 16A thru 16L 16A Shaft 16B Stop Ring 16C Mechanical...

Page 14: ... OR FITNESS FOR USE AND THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION CONTAINED HEREIN TACO INC WILL NOT BE LIABLE FOR ANY SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES Taco Inc 1160 Cranston Street Cranston RI 02920 401 942 8000 14 TROUBLESHOOTING GUIDE Hazardous voltage and risk of sudden starts Disconnect all power to the pump before servicing or working on pump Make sure that power...

Page 15: ...15 ...

Page 16: ......

Reviews: