Dimensions
Operation
Overload Adjustment
Confirm nameplate Full Load Amperage (FLA) to ensure proper overload
protection. Using a flathead screwdriver, turn the adjustment dial to the desired
amperage setting. The starter is not rated to protect loads exceeding 16 amps @
120VAC, and 8.8A @ 230VAC.
LED Status Indicators
POWER (PWR)
Illuminates when voltage is applied to the input terminals and
main power switch is in the ON
(
)
position.
RUN
Under a RUN condition, the RUN LED will remain illuminated if
the TS-1P senses current providing status. The LED will flash
when the unit does not sense current.
FAULT (FLT)
- Overload Trip
The TS-1P indicates a fault condition by flashing the red FAULT
LED which will remain constant in the event of a fault trip. The LED
will also flash if a RESET attempt is made during the 180 second
overload cool down period.
Operation Modes
RESET
To reset the starter to normal operation following a Fault
condition, slide the 3-position switch to RESET and hold for
a minimum of 5 seconds (after 180 second cool down period
has elapsed). Once starter has been reset, return switch to the
desired mode.
MANUAL (HAND MODE)
In Manual or HAND mode, the TS-1P will function as a manual
motor controller. Select the ON
(
)
position on the main power
switch to engage motor.
AUTOMATIC (AUTO MODE)
When utilizing the starter in the AUTO mode, a signal sent via
the terminal inputs (located on rear of unit) determine motor
operation (ON or OFF).
Lockout Options
To lockout, slide the lower cover upward to reveal concealed locking grasp.
Insert a standard padlock to prevent unauthorized access or tampering. If
multiple padlocks are required, an optional padlocking attachment can be utilized
(not included). See Figure 2B.
Figure 2A
Figure 2B
HAND
RESE
T
AU
TO
PWR
RUN
FLT
Product Ratings
1
2
3
4
5
6
Overload Adjustment
Operation Mode Selector
Main Power Switch*
PWR
Power Status LED
RUN
Run
Status LED
FLT
Fault / Overload LED
UL 508 Horsepower
Short Circuit Protection
Interrupt
Current
Max Current
Overload
Reset
115VAC
230VAC
TS-1P
1HP
Suitable for use on a circuit capable of delivering not more
than 1kA RMS Symmetrical Amperes, 230 Volts maximum
when protected by Class RK5 fuses (30 Amp max) or
inverse time circuit breaker (40 Amp max)
I
k
≤ 1kA RMS
Symmetrical
16A @ 120VAC
8.8 @ 230VAC
I
2
t Class 10
Manual
1
2
3
4
5
6
*This device meets NFPA-70 (NEC) motor disconnect requirements per
paragraph 430.109 (C)(2) Stationary Motors of 2HP or Less.