All Settings
This screen displays all of the controller's settings and provides access to edit all parameters from a single screen.
Some parameters (defaulted as Structure) are described in individual tables below.
Pump Settings
This screen displays PSU1 settings related to this topic and allows access to all of these settings from a single screen.
Setting
Range
Default
Description
Pump Settings
Structure
N/A
General pump settings
Commissioning
Structure
N/A
Pump commissioning settings
Enable Alarm
Disabled,
Switch (open),
Switch (closed
Disabled
Enables monitoring and alarming associated
with the Pump Flow Proof switch
Flow Delay
0 to 180 seconds
15 seconds
Amount of time to wait without flow before
signaling pump failure
Thermistor Type
PreconII,
PreconIII
PreconIII
Selects the type of thermistor used for supply
and return water temp
Pump Mod Set
Structure
Pump modulation settings
Low Temp Setting
0.01 to 50 °F
0.01 °F
Sets the minimum temperature at which low
temperature circulation activates. If set to
0.01°F, then this feature is disabled.
Water Temp Alm
Structure
N/A
Auto Recovery
Structure
N/A
Auto Flow Recovery settings.
Setting
Range
Default
Description
Operational Mode
Standby,
Single,
Equal Runtime,
2 Stage
Single
Operating sequences of the two pumps
Const Pump Circ
Off, On
Off
Causes pumps to run continuously, regard-
less of demand
Lead Pump Sel
Pump 1,
Pump 2,
Lowest Hours,
Alternating
Pump 1
Determines the pump selection method to
use when a new pump must be started.
Pre Purge Time
0 to 100 seconds
10 seconds
Time primary pump runs before starting a
boiler stage (must be in sync with the BLMC)
to allow accurate temperature measurement.
Post Purge Time
0 to 255 minutes
5 minutes
Time primary pump runs after the demand is
off to dissipate heat and allow pump speed to
return to a minimum value.
Max Runtime
1 to 255 hours
168 hours
Amount of run time by which the lead pump
exceeds the lag pump before swapping lead
and lag.
Differential Temp
0 to 40
°F (0 to 22.2
°C)
40
°F
(22.2
°C)
Primary loop Delta T at which the second
pump is turned on or the desired primary loop
Delta T in single stage modulated mode. The
Absolute value of Delta T is always used
when comparing against this setting.
Pump Exercise
Off, On
Off
If “On,” pumps are run sequentially for 15
seconds every week.
Operational Type
Switching,
Modulated
Switching
Turns on modulated outputs. Not available in
2 Stage mode.