background image

(6)

Testing LWCO Mode Systems

1.

Turn off thermostat and ensure boiler system has power.

2.

Verify that the S1 mode switch is in LWCO mode and any DBF and HAW delays are set.

3.

Lower the boiler water level until the LWCO indicates a low water condition.

4.

Verify that the EWF feeds the boiler. Be sure to verify that any DBF delays occurred prior to the EWF starting a feed cycle.

5.

When the LWCO indicates a normal water level, verify the EWF stops feeding the boiler. Be sure that any HAW delays
occur before the EWF completes the feed cycle.

6.

Return thermostat to its normal setting.

Testing and Setting Fixed Feed Systems

1.

Turn off thermostat and ensure boiler system has power.

2.

For boilers with probe style low water cutoffs, lower the boiler water level approximately ½” below the probe. Be sure to
verify that any DBF delays occurred prior to the EWF starting a feed cycle.

3.

For boilers with float style low water cutoffs, lower the water level in the boiler until approximately ¼” is visible in the gauge
glass. Be sure to verify that any DBF delays occurred prior to the EWF starting a feed cycle.

4.

While using a stopwatch or a watch with a second hand, press the manual feed button on the EWF and measure the time
it takes for the boiler fill to a normal water level. (Use the boiler manufacture’s recommended normal operating level –
typically the middle of the gauge glass).

5.

Determine the number of gallons that were required to fill the boiler to a normal water level: The EWF feeds 1 gallon each
minute. Round up to the nearest gallon.

6.

Set the S1 mode switch to FF (Fixed Feed).

7.

Set the S3 (Fixed Feed Settings) mode switch to the number of gallons determined in step 5.

8.

Return thermostat to its normal setting.

•••••

Fixed feed settings will always feed the amount of water set on switch S3, even if the LWCO indicates a

normal water level before the feed cycle completes.

•••••

Improper fixed feed settings could result in flooding and property damage could result.

Summary of Contents for EWF-120-1

Page 1: ...er Feeder 102 170 SUPERCEDES REVISIONDATEDAUGUST1 2004 5401148 REVB EFFECTIVE NOVEMBER 10 2004 r e w o P t u p n I l e d o M e g a t l o V r e w o P n o i t p m u s n o C 1 0 2 1 F W E C A V 0 2 1 A V 2 1 1 4 2 0 F W E C A V 4 2 A V 0 1 Patent Pending 24 VAC to be supplied by an EXTERNAL Class 2 power source OPERATION LWCO Mode When the mode switch of S1 See fig 9a is set to the ON position the EW...

Page 2: ...as dispensed more water over the past 30 days than the setting of the Excess Feed switch S4 Pressing and holding switch S5 will reset the Excess Feed Condition See Fig 2 for location of Excess Feed Reset Button Once this reset button is pressed and held for 2 seconds the EWF briefly turns off the Feed Status Indicator indicating reset has occurred Once the EWF completes the reset process the Feed ...

Page 3: ...rces Failure to do so could result in flooding and property damage can occur INSTALLATION Piping Plumb the EWF water feeder as shown in Figure 4 The EWF must be installed with a manual bypass To permit ease of removal for servicing or replace ment install unions and isolation valves Install the EWF with the flow direction arrow toward the boiler Fill the boiler by manually opening the bypass valve...

Page 4: ...a c o L T x 1 2 0 x L T x 0 2 4 x G N D P B U R N E R C IR C U IT H O T N E U T R A L H N T a c o E W F 1 2 0 E W F 0 2 4 L W 1 2 0 V A C 2 4 V A C C I R C U I T FIG 5 FIG 6 b 4 a N C COM N O H N Taco L Tx120x G ND P BUR NER CIRC UIT 12 0 VAC CIRC UIT HO T NEU TR AL H N Ta co EW F0 24 LW 24 V AC CIRC UIT HO T NEU TR AL N C COM N O H N Taco LTx024x G ND P BUR NER CIRC UIT 12 0 VAC CIRC UIT HO T NEU...

Page 5: ...eriod Low Water Period Delay Before Feeding Period DBF Hold Period After Water OK HAW Normal Water Condition Low Water Condition Feed Valve Closed Feed Valve Open ON OFF 1 2 3 4 5 6 7 8 1 Min 0 5 Min 4 Mins 2 Mins 8 Mins 6 Mins FF LWCO 10 Mins OFF ON DELAY BEFORE FEED DBF MODE ALL OFF 0 DELAY S1 ON OFF 1 2 3 4 5 10 Gals 8 Gals 15 Gals 12 Gals 6 Gals OFF ON EXCESS FEED SETTING ALL OFF DISABLED S4 O...

Page 6: ...For boilers with float style low water cutoffs lower the water level in the boiler until approximately is visible in the gauge glass Be sure to verify that any DBF delays occurred prior to the EWF starting a feed cycle 4 While using a stopwatch or a watch with a second hand press the manual feed button on the EWF and measure the time it takes for the boiler fill to a normal water level Use the boi...

Page 7: ... o c t e s d n a d e l b a n e s i t i e r u s e b e r u t a e f e h t n o d e l l a t s n i s i t a h t O C W L e h t r o f s n o i t c u r t s n i s r e r u t c a f u n a m r e l i o b y a l e D f o g n i t t e s r e p o r p m I F B D g n i d e e F e r o f e B e b y a m F B D r e g n o l a r e l i o b e h t o t n r u t e r o t w o l s s i e t a s n e d n o c f I s t r a t s g n i d e e f e r o f...

Page 8: ...addition of petroleum based fluids or certain chemical additives to the systems or other abuse will not be covered by this warranty If in doubt as to whether a particular substance is suitable for use with a Taco product or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products ...

Reviews: