background image

Product Specifications:

Maximum Operating Pressure:

300 PSI (2,100 kPa)

Maximum Shutoff Pressure:

125 PSI (875 kPa)

Fluid Temperature Range:

20° to 240°F, (-7° to 115°C) @ 135°F (57°C) ambient
Installation must be in a non-condensing application.

Service:

Closed systems
Hot Water, up to 50% Glycol

Ball Rotation Speed:

Full Open to Full Close (90° turn), 4 seconds
Full Close to Full Open (90° turn), 6 seconds

Seat Leakage:

Drop-Tight Close-Off

Electrical Rating: 

24 VAC, 60 HZ, 0.54 Amps 
Do not exceed number of valves per transformer rating. Example:
Do  not use more than 12 zone valves per 40VA transformer.

Power Consumption, Charging:

12.84 Watts, 0.54 Amps Max

Power Consumption, Power On:

1.44 Watts, 0.06 Amps Max

Heat Anticipator Setting:

0.5 Amps

End Switch Rating:

3 Amps @ 24 VAC

Materials of Construction, Actuator:

Body:

High Performance Engineered Polymer

Gears:

High Performance Internally Lubricated Engineered Polymer

Materials of Construction, Valve:

Body:

Forged Bronze

Stem:

Brass

Press Ring:

Brass

Ball:

Brass (Chrome Plated)

Seat:

Modified Teflon

O-rings:

EPDM

VALVE SIZE

A

B

E

WEIGHT

(valve + actuator)

1

2

3”

2

3

8

3

9

16

2

9

16

3

1

8

1.15 lbs

3

4

3”

2

3

8

3

3

4

2

5

8

3

1

8

1.20 lbs

1”

3”

2

3

8

3

11

16

2

5

8

3

1

8

1.55 lbs

C

A

E

C

G

F

B

Dimensions:

F

G

1

9

16

1

9

16

1

9

16

1

1

2

" MIN.

OPERATOR

REMOVAL

CLEARANCE

W

A

L
L

“QUICK ORDER” PART NUMBERS

E050C2-1  >  

1

2

" 2-Way, Sweat, 24 VAC, Normally Closed, 4 Input Quick Connects

E075C2-1  >  

3

4

" 2-Way, Sweat, 24 VAC, Normally Closed, 4 Input Quick Connects

E100C2-1  >   1" 2-Way, Sweat, 24 VAC, Normally Closed, 4 Input Quick Connects
E050T2-1  >  

1

2

" 2-Way, Threaded, 24 VAC, Normally Closed, 4 Input Quick Connects

E075T2-1  >  

3

4

" 2-Way, Threaded, 24 VAC, Normally Closed, 4 Input Quick Connects

E100T2-1  >   1" 2-Way, Threaded, 24 VAC, Normally Closed, 4 Input Quick Connects

Summary of Contents for 102-111

Page 1: ... mounted to the valve body in either direction see figure A great for those tight baseboard jobs Snap in quick connects on the back of the valve make for a secure and fast hook up A green LED light shows full functionality of the valve s operation and thermostat status As noted above under a no power situation the manual override button locat ed on the top of the valve allows the ball to be rotate...

Page 2: ...180 depending on the initial ball position If it rotates past a 90 point it will close the end switch T T terminals to verify connec tion This may make it seem as if the device i e boiler connected to the end switch terminals has short cycled while the valve finds its home This will only occur once on initial start up 4 Once the valve finds its home the green LED will remain ON as long as the ther...

Page 3: ...f Construction Actuator Body High Performance Engineered Polymer Gears High Performance Internally Lubricated Engineered Polymer Materials of Construction Valve Body Forged Bronze Stem Brass Press Ring Brass Ball Brass Chrome Plated Seat Modified Teflon O rings EPDM VALVE SIZE A B E WEIGHT valve actuator 1 2 3 23 8 39 16 29 16 31 8 1 15 lbs 3 4 3 23 8 33 4 25 8 31 8 1 20 lbs 1 3 23 8 311 16 25 8 3...

Page 4: ...ch Rh Rc w y Rh Rc w y Rh Rc w y w y c w y c w y c L1 Hot L2 Thermostat To T Terminals Motor See Chart See Chart Red Red End Switch Motor Wire Color Honeywell Yellow Erie Black Sparco Orange Yellow Honeywell Erie and Sparco Wire Leads Wiring a Taco EBV Zone Valve to Replace a Honeywell Erie or Sparco Valve Honeywell and Erie Terminal Block L1 Hot L2 Thermostat To T Terminals Motor End Switch TH TR...

Reviews: