VI, V2, V3 = SHUT-OFF ISOLATION VALVE

P = TACO CIRCULATOR WITH IFC

FF = FAST FILL BOILER FEED VALVE

PV4 = PURGE VALVE

RECOMMENDED PURGING STEPS:

1. CLOSE V1, PV4, V2

2. OPEN V3

3. OPEN FF VALVE

4. OPEN V2, PV4, TO PURGE LAST ZONE

FIRST (ZONE 3)

5. CLOSE FF VALVE

6. CLOSE V2, PV4

7. REPEAT STEPS 1 TO 6 FOR EACH

ADDITIONAL ZONE, PURGE ZONE 1 LAST

8. OPEN V1 WHEN ALL ZONES ARE

PURGED

9. ADJUST SYSTEM TO DESIRED OPERATING

FILL PRESSURE IF REQUIRED

Figure 2:

-2-

Summary of Contents for 0015e3-2

Page 1: ...equired Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking and air purging mode Optional 2 way universal flange model for easy fit up to any flange orientation See Figure 1 Integral Flow Check IFC included Field installed Green Mode active system monitoring and power optimization WARNING Do not use in swimming pool or spa areas Pump has no...

Page 2: ...MMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED Figure 2 2 ...

Page 3: ...NG STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION Figure 3 3 ...

Page 4: ... the arrow on the casing body to determine flow direction CAUTION To reduce the possibility of noise transmission be sure to add vibration dampeners to piping when mounting circulator to wall or floor joists ATTENTION Pour réduire la possibilité de transmission de bruit veillez à ajouter des amortisseurs de vibration à la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de pla...

Page 5: ... circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter NEUTRAL TERMINAL BOX L N No ground wire is required Green Terminal Plug Spring Tabs WIRE NUT WHITE BLACK LINE WARNING SERVICING OF DOUBLE INSULATED APPLIANCES A double insulated appliance is marked with one or more of the following The words DOUBLE INS...

Page 6: ...ettings LOW 5 feet of head constant pressure variable speed MEDIUM 10 feet of head constant pressure variable speed HIGH 18 feet of head max full fixed speed 7 Programming your 0015e3 circulator Modify the performance of the circulator as needed by rotating the dial using a flat screw driver An orange LED will illuminate when the circulator is powered on The LED will flash each time a setting is c...

Page 7: ... Listed below are potential diagnostic error codes which will appear on the LED display in case of a malfunction 9 Unlocking Procedure A red LED indicates the circulator is locked or sticking Disconnect and connect power supply to start the automatic release process The circulator makes 100 attempts to restart process lasts approximately 15 minutes Every restart is signalled by a short white flash...

Page 8: ...per bag 0010 025 RP Integral Flow Check IFC 007 007 RP Flange gasket set Replacement Parts List 2021 LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without charge at the company s option any Taco High Efficiency circulator or circulator part which is proven defec tive under normal use within three 3 years from the date of manufacture In order to obtain service under this warranty it is...

Reviews: