0015e3-2 

ECM High-Efficiency Circulator

DESCRIPTION:
The 0015e3 is a variable speed ,high-efficiency, wet rotor circulator with an ECM, permanent magnet

motor. With 3 easy settings, its performance curves are equivalent to the versatile Taco 0015 3-speed and

ideal for hydronic systems zoned with circulators or zone valves. The 0015e3 reduces power consump-

tion by up to 85% compared to equivalent AC permanent split capacitor circulators.
APPLICATION:

• Maximum operating pressure: 125 psi (8.6 bar)

• Maximum water temperature: 230°F (110ºC)

• Electrical specifications:

Voltage: 110-120V, 50/60 Hz, single phase

             Maximum operating power: 44W

             Maximum amp rating: 0.54

• Equipped with a cast iron casing and should be used for closed loop systems only

• Not suitable for open loop potable water or chilled water systems

• Taco circulator pumps are for indoor use only – employer uniquement a l’interieur

• Acceptable for use with water or maximum of 50% water/glycol solution

FEATURES:

• Three easy settings to match system requirements - LOW, MEDIUM, HIGH

• Replaces all single speed and 3-speed circulators in its class

• ECM performance equivalent to the versatile Taco 0015 3-speed circulator

• Multi-color LED display showing power on and error code diagnostics

• Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation

• Nut capture feature on flanges for easier fit up

• Dual electrical knockouts and 6” stranded wire leads for easy wiring

• Double insulated - no ground-wire required

• Whisper quiet operation

• BIO Barrier

®

protects the pump from system contaminants

• SureStart

®

- automatic unblocking and air purging mode

• Optional 2-way universal flange model for easy fit-up to any flange orientation. See Figure 1.

• Integral Flow Check (IFC

®

) included - Field installed

• Green Mode - active system monitoring and power optimization

WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.

AVERTISSEMENT : Ne pas utiliser dans une piscine ou un spa. La pompe n'a pas été étudiée pour ces applications.

CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment

voids the warranty. Consult factory for fluid compatibility.

ATTENTION : L'ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un

équipement TACO annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.

CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent

pump cavitation and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. A

larger size expansion tank may be required.

ATTENTION : Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplis-

sage plus élevée de 20 psi au minimum afin d'éviter toute cavitation ou flashing de la pompe. Une défaillance pré-

maturée peut en résulter. Réglez la pression du réservoir d'expansion de façon qu'elle soit égale à la pression de

remplissage. Un réservoir d'expansion d'une taille supérieure peut être nécessaire.

Instruction Sheet

®

INSTALLATION:

Standard flange model:

0015e3-2F2

Optional 2-way flange model: 

0015e3-2F4

Figure 1:

®

-1-

Summary of Contents for 0015e3-2

Page 1: ...equired Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking and air purging mode Optional 2 way universal flange model for easy fit up to any flange orientation See Figure 1 Integral Flow Check IFC included Field installed Green Mode active system monitoring and power optimization WARNING Do not use in swimming pool or spa areas Pump has no...

Page 2: ...MMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED Figure 2 2 ...

Page 3: ...NG STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION Figure 3 3 ...

Page 4: ... the arrow on the casing body to determine flow direction CAUTION To reduce the possibility of noise transmission be sure to add vibration dampeners to piping when mounting circulator to wall or floor joists ATTENTION Pour réduire la possibilité de transmission de bruit veillez à ajouter des amortisseurs de vibration à la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de pla...

Page 5: ... circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter NEUTRAL TERMINAL BOX L N No ground wire is required Green Terminal Plug Spring Tabs WIRE NUT WHITE BLACK LINE WARNING SERVICING OF DOUBLE INSULATED APPLIANCES A double insulated appliance is marked with one or more of the following The words DOUBLE INS...

Page 6: ...ettings LOW 5 feet of head constant pressure variable speed MEDIUM 10 feet of head constant pressure variable speed HIGH 18 feet of head max full fixed speed 7 Programming your 0015e3 circulator Modify the performance of the circulator as needed by rotating the dial using a flat screw driver An orange LED will illuminate when the circulator is powered on The LED will flash each time a setting is c...

Page 7: ... Listed below are potential diagnostic error codes which will appear on the LED display in case of a malfunction 9 Unlocking Procedure A red LED indicates the circulator is locked or sticking Disconnect and connect power supply to start the automatic release process The circulator makes 100 attempts to restart process lasts approximately 15 minutes Every restart is signalled by a short white flash...

Page 8: ...per bag 0010 025 RP Integral Flow Check IFC 007 007 RP Flange gasket set Replacement Parts List 2021 LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without charge at the company s option any Taco High Efficiency circulator or circulator part which is proven defec tive under normal use within three 3 years from the date of manufacture In order to obtain service under this warranty it is...