background image

1. Using teflon tape or high quality thread sealant, install

Taco companion flanges on threaded pipe ends to
ensure proper fit-up and leak protection.

2. Minimize pipe strain on pump by using pipe hangers

on the suction and discharge lines.

3. Position vertical and horizontal piping so bolt-holes on

pump and companion flanges match. Do not force the
suction and discharge lines into position. This may cre-
ate excess stress on the pump casing and flanges. 

B. Mounting Position:

• Always install pump with the motor shaft in the hori-

zontal position and the capacitor/conduit box oriented
on top of the motor housing, as shown in Fig. 1.

• Standard pump body mounting position is with the flow

in the up-discharge direction (body position #3). The
pump body may be field-rotated in any direction to
accommodate system piping and flow direction.

• Be sure to align the arrow on the casing with desired

flow direction.

C. Electrical Wiring:

• All electrical wiring must be installed by a licensed

electrician in accordance with local and national codes
and regulations.

• Electrical supply and grounding wires must be suitable

for at least 90ºC (194ºF).

• Wood Boiler Series circulators are thermally protected

and do not require external overload protection.

1. Be sure all electrical power to pump is disconnected

and locked-out before proceeding with wiring. 

2. Loosen capacitor/conduit box screw and remove cover.

3. Attach appropriate size connector to one of the two

knock-out holes in the capacitor/conduit box.

4. Using minimum 18 AWG wire, connect the hot and

neutral leads from the electrical supply to the respec-
tive black and white leads in the capacitor box.

5. Connect the ground wire to the green ground screw in

the capacitor box.

6. Replace capacitor/conduit box cover.

7. Insert plastic plug provided in unused knock-out hole.

FLOW

NOT RECOMMENDED

RECOMMENDED

FLOW

FLOW

FLOW

CAUTION: Do not support, suspend or brace
pump motor or early failure may result.
Support provided by casing is sufficient for
structural integrity of pump

Fig. 1 – Installation Positions

CONNECTION

3

4

"

1

"

1

1

4

"

1

1

2

"

Iron NPT

110-251F

110-252F

110-253F

110-254F

Stainless
Steel NPT

110-251SF

110-252SF

110-253SF

110-254SF

Bronze SWT

110-523BSF 110-524BSF 110-525BSF 110-526BSF

Shut-Off NPT

SF-075T

SF-100T

SF-125T

SF-150T

Shut-Off SWT

SF-075S

SF-100S

SF-125S

SF-150S

WOOD BOILER SERIES COMPANION FLANGE SETS

Summary of Contents for 001-3914

Page 1: ...ghest net positive suc tion head available NPSHA usually at the boiler supply outlet Instruction Sheet Outdoor Wood Boiler Series Hi Capacity Circulator 102 349 SUPERSEDES November 10 2009 EFFECTIVE May 1 2010 Plant ID 001 3914 INSTALLER Please leave these instructions for owner s use CAUTION Taco Wood Boiler circulators are designed for indoor use only Be sure boiler enclosure is weather tight if...

Page 2: ... wires must be suitable for at least 90ºC 194ºF Wood Boiler Series circulators are thermally protected and do not require external overload protection 1 Be sure all electrical power to pump is disconnected and locked out before proceeding with wiring 2 Loosen capacitor conduit box screw and remove cover 3 Attach appropriate size connector to one of the two knock out holes in the capacitor conduit ...

Page 3: ... with soapy water and install new parts in the face plate recess Replace the face plate to its original posi tion Carefully tap the face plate evenly into the recess in the motor housing 7 Clean the impeller shaft before installing the new seal 8 Lubricate the impeller shaft with soapy water Do not install new seal on a dry impeller shaft or damage to seal may result 9 Slide the new carbon seal an...

Page 4: ...01 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY ...

Reviews: