If the IAQ Mode is set to Analog, this parameter structure needs to be configured.
OAT Cutoff
The OAT cutoff temperatures are temperatures above or below heating or cooling function is disabled and the econo-
mizer is reduced to the MinAir position.
Note: A value of -4
°F disables this cutoff temperature setting. All other values within the range are valid cutoff temperatures.
Alarms
The table below describes the alarms you may encounter and how they are reset.
Setting
Range
Default
Description
Min
0 to 4000 ppm
0 ppm
Minimum ppm sensor setting
Max
0 to 4000 ppm
0 ppm
Maximum ppm sensor setting
Setpoint
0 to 4000 ppm
0 ppm
Setpoint
Offset
0 to 4000 ppm
0 ppm
Offset to the sensor reading
Setting
Range
Default
Description
Max OAT Heat
-7.6 to 122
°F
(-22 to 50
°C)
-4
°F
(-20
°C)
Outside Air Temperature above
which heating is disabled. See Note
below.
Min OAT Cool
-7.6 to 122
°F
(-22 to 50
°C)
-4
°F
(-20
°C)
Outside Air Temperature below which
cooling is disabled. See Note below.
Max OAT Econ
-7.6 to 122
°F
(-22 to 50
°C)
-4
°F
(-20
°C)
Outside Air Temperature above
which economizer is disabled. See
Note below.
Min OAT Econ
-7.6 to 122
°F
(-22 to 50
°C)
-4
°F
(-20
°C)
Outside Air Temperature below which
economizer is disabled. See Note
below.
SAT Cooling Limit
45 to 75
°F
(7.2 to 23.9
°C)
55
°F
(12.8
°C)
Supply air temperature below which
additional cooling will not be enabled.
See Note below.
Alarm
Range
Alarm Trigger
Alarm Reset
Fan Failure
Normal, Alarm
Occurs when the fan input detects
that the fan is not running after a
30-second grace period after the
fan has been activated.
The cause of the emergency condition
must be resolved and the controller
must be reset.
Smoke
Normal, Alarm
Occurs when the smoke alarm
input detects the presence of
smoke.
The cause of the emergency condition
must be resolved and the controller
must be reset.
Mixed Air Low Limit
Normal, Alarm
Occurs when the mixed air tem-
perature drops below the Low
Limit that has been set, indicating
a freeze condition.
The cause of the emergency condition
must be resolved and the controller
must be reset.
Filter
Normal, Alarm
Occurs when the Filter Alarm input
detects that the filter needs to be
replaced.
Automatic when the dirty filter is
replaced.
Indoor Air Quality
Normal, Alarm
Occurs when the IAQ sensor
detects inadequate indoor air qual-
ity.
Automatic when air quality returns
within normal parameters.