Adding Enthalpy Economizer

Controlled:

 0-10VDC Modulated or 2-pos Economizer 

Damper Actuator

Added Module Required: 

Add ASM Module to net-

work with OA Temp and Humidity Sensors

Added Sensors Required:

 Mixed Air Temp, Return 

Air Humidity

Existing Sensors Required: 

Return Air Temp, Supply 

Air Temp, Fan Proof, Filter Status

Setup Instructions

 

1.Press 

Controllers

 from main screen.

2.Select required MPU from controller list and press 

appropriate controller.

3.Press 

All Settings

4.Press 

Next 14

5.Press 

Economizer

6.The 

Economizer

 menu opens.

a.Select 

Type

 of economizer control:

-2 st (2 position), Unocc ON

-2 st (2 position), Unocc OFF

-Mod (modulating), Unocc ON

-Mod (modulating), Unocc OFF

NOTE:

 Unocc ON/OFF specifies whether you 

want the economizer enabled (ON) or dis-
abled(OFF) during the unoccupied time peri-
ods.

b.Select economizer 

setpoint

, which specifies the 

outside air temperature at which the economizer is 
enabled.

c. Select 

Min Fresh Air %

. The minimum required 

damper position for ventilation specified.

d.Select 

Min AO

 (Output) Voltage (0-10VDC) for 

damper actuator. 0.0VDC Shown as Example.

e.Select 

Max AO

 (Output) Voltage (0-10VDC) for 

damper actuator. 10.0VDC shown as example. If a 
reverse action damper is used then reverse the 
min and max voltages.

f. Press 

Save

.

g.Note: DO NOT change factory KP/KI settings. 

Please review Factory KP/KI Setting White Paper # 
508-001.

7.Press 

Free Cooling

8.8.The 

Free Cooling

 menu opens.

a.Select 

Type

 of economizer control:

-Return Air Humidity (Enthalpy)

-Global Humidity (not used)

-Dry Bulb

b.Select 

Enthalpy Offset

 (Humidity Ratio) in BTU/lb

c. Select 

Dry Bulb Offset

 in degrees.

d.Press 

Save

.

e.Note: Setting as per engineered documents. If spe-

cific settings are not known, leave at factory 
defaults shown above.

9.Press 

Next 4

.

Summary of Contents for iWorx MPU2

Page 1: ...Stage 2 Cooling Stage 3 Cooling Stage 4 Digital Economizer 24 Volts AC 1A 50C 0 5A 60C limited by the Class 2 supply rating Modulated Heating Modulated Cooling Modulated Economizer Bypass Damper 0 10...

Page 2: ...er source current requirements add the power consumption of all peripheral devices to that of the control ler The controller and sensor power supplies can use the same power source If both are using t...

Page 3: ...d Consult the equipment supplier or an experienced radio TV technician for help You are cautioned that any changes or modifications to this equipment not expressly approved in these instructions could...

Page 4: ...iWorx MPU2 MPU3 4 502 009 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 5: ...iWorx MPU2 MPU3 502 009 Effective April 17 2013 5 2013 Taco Electronic Solutions Inc...

Page 6: ...iWorx MPU2 MPU3 6 502 009 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 7: ...iWorx MPU2 MPU3 502 009 Effective April 17 2013 7 2013 Taco Electronic Solutions Inc...

Page 8: ...er Status Air Differential Pressure Transmitter Added Module Required At least 1 VAVD up to 32 on Taco LON Bus Setup Instructions 1 Press Controllers from main screen 2 Select required MPU from contro...

Page 9: ...etp High g Press Save 12 Press Pressure Settings 13 The Pressure Settings menu opens a Select Static Pressure Setpoint in Inches of WC b Select the IAQ Setpoint if applicable c Select Min Output Volta...

Page 10: ...g or cooling c Press Save 16 Press Staged Cooling 17 The Staged Cooling menu opens a Select number of stages of equipment 0 4 b Select the stage control band in degrees Cannot be set to 0 c Select the...

Page 11: ...e menu opens Select a ON fan is on in Occupied mode but cycles with Heat Cool call in Unoccupied b Auto fan always cycles with Heat Cool call c Press Save 23 Press Economizer 24 The Economizer menu op...

Page 12: ...iWorx MPU2 MPU3 12 502 009 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 13: ...iWorx MPU2 MPU3 502 009 Effective April 17 2013 13 2013 Taco Electronic Solutions Inc...

Page 14: ...tial Pressure Transmitter Added Module Required At least 1 VAVD up to 32 on Taco LON Bus Note For Floating Point Valve Setup and Wir ing See MPU2 Application Guide 505 009 Setup Instructions 1 Press C...

Page 15: ...Setp High g Press Save 12 Press Pressure Settings 13 The Pressure Settings menu opens a Select Static Pressure Setpoint in Inches of WC b Select the IAQ Setpoint if applicable c Select Min Output Volt...

Page 16: ...ed Cooling menu opens a Select Min AO Output Voltage 0 10VDC 2 0VDC Shown as Example b Select Max AO Output Voltage 90 10VDC 10 0VDC shown as example c Press Save d Note DO NOT change factory KP KI se...

Page 17: ...Fan Type menu opens Select a ON fan is on in Occupied mode but cycles with Heat Cool call in Unoccupied b Auto fan always cycles with Heat Cool call c Press Save 23 Press Economizer 24 The Economizer...

Page 18: ...iWorx MPU2 MPU3 18 502 009 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 19: ...iWorx MPU2 MPU3 502 009 Effective April 17 2013 19 2013 Taco Electronic Solutions Inc...

Page 20: ...conomizer enabled ON or dis abled OFF during the unoccupied time peri ods b Select economizer setpoint which specifies the outside air temperature at which the economizer is enabled c Select Min Fresh...

Page 21: ...ive April 17 2013 21 2013 Taco Electronic Solutions Inc 10 Press Cutoff Temps 11 The Cutoff Temps menu opens a Specify Max OAT Heating b Specify Min OAT Cooling c Specify Max OAT Economizer d Specify...

Page 22: ...iWorx MPU2 MPU3 22 502 009 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 23: ...iWorx MPU2 MPU3 502 009 Effective April 17 2013 23 2013 Taco Electronic Solutions Inc...

Page 24: ...screen 2 Select required MPU from controller list and press appropriate controller 3 Press All Settings 4 Press Next 14 5 Press Next 4 6 Press IAQ Mode 7 The IAQ Mode menu opens 8 Select IAQ sensor i...

Page 25: ...iWorx MPU2 MPU3 502 009 Effective April 17 2013 25 2013 Taco Electronic Solutions Inc d Select Offset calibration PPM e Press Save...

Page 26: ...can cycle power to the controller Refer to the LCI documentation for more infor mation on resetting the controller using the LCI Can my iWorx system contain multiple MPU controllers Yes provided that...

Page 27: ...the Document and instructions or which has been subject to accident disaster neglect misuse misapplication inadequate operating environment repair attempted repair modification or alteration or other...

Page 28: ...be covered by this warranty TES products are not intended for use to support fire suppression systems life support systems critical care applications commercial aviation nuclear facilities or any othe...

Reviews: