SUPERSEDES: September 15, 2015

Effective: June 13, 2022

402-080

Plant ID No. 001-5043

Instruction Sheet

4900 Series Air Separators

4900 Series Air & Dirt Separators

Taco 4900 series separators are designed and fabricated to ASME Code 

for Unfired Pressure Vessels, Sect. VIII Div. 1.
Prior to shipment all separators are hydrostatically tested to 1.3 times their 

rated working pressure and certified by an independent Authorized inspec-

tor.
Upon receipt of each separator, the ship-

ping container should be examined for 

external damage. If the shipping container 

has been damaged in transit, the contents 

of the packaging should also be examined 

prior to acceptance of the shipment. If the 

separator appears to be damaged the 

shipment should be refused and or signed 

for as damaged. If the separator is dam-

aged, the local Taco representative should 

be contacted for further instructions.

WARNING: DO NOT BRAZE PIPING TO THE NOSE OF THE VENT; 

PERMANENT DAMAGE WILL OCCUR TO THE AIR VENT INTERNAL 

PARTS. 

INSTALLATION

TO BE INSTALLED BY PROFESSIONAL INSTALLERS ONLY

4900A – Air Separators

Taco 4900A series separators are designed for installation in hydronic 

systems. The purpose of the 4900A separator is the removal of air from 

the heating or chilled water system. In a heating system application the 

separator should be mounted in the piping as close as possible to the exit 

of the boiler and upstream of the pumps in the system. These units are 

not designed to withstand external piping loads which may be transmit-

ted to the nozzles from the piping system. Should external piping loading 

requirements  be  present,  confirmation  from  Taco’s  Design  Engineering 

department regarding the suitability of the separator’s design should be 

obtained prior to installing this product. External piping must be supported 

within the design of the external piping system.
When separators are installed, care should be taken to allow access to 

the ASME name plates, air vent (located at the top of each separator), 

flushing cock (located at the side of each unit) and drain plug (installed in 

the bottom of each unit).
All piping to each separator should be installed full size, to match the ves-

sel’s connections, isolation valves on each side of the unit should be in-

stalled for future maintenance. The isolation valves are used during main-

tenance to reduce the loss of system fluid. 

See Warning under General section.

4900AD – Air and Dirt or Dirt (D) Separators with or without  

Switchable On/Off Magnet

Installation notes from 4900A - Air Separators in previous paragraphs ap-

ply to 4900 Air and Dirt Separators as well. On 4900AD air and dirt sep-

arators the drain/blowdown valve located at the bottom of the unit should 

be piped to drain. This connection should be piped with a full port shutoff 

valve to a nearby drain during installation.

WARNING: FAILURE TO COMPLY WITH THESE 

INSTRUCTIONS REGARDING THIS PRODUCT CAN 

RESULT IN SERIOUS PERSONAL INJURY OR DEATH AND/

OR SEVERE PROPERTY DAMAGE.

DIAGRAM 1 – LOCATION OF TANK FITTINGS

SUPERCEDES: December 8, 2014     

    EFFECTIVE: September 15, 2015

4900 Series Air Separators

4900 Series Air and Dirt Separators

Installation, Operation & Maintenance Manual

402-080

GENERAL

All Taco 4900 series separators are designed and fabricated in

accordance with the ASME Code for Unfired Pressure Vessels,

Sect. VIII Div. 1.

Prior to shipment all separators are hydrostatically tested to 1.3

times their rated working pressure and accepted by an indepen-

dent insurance inspector.

Upon receipt of each separator, the shipping container should be

examined for external damage. If the shipping container has been

damaged in transit, the contents of the packaging should also be

examined  prior  to  acceptance  of  the  shipment.  If  the  separator

appears to be damaged the shipment should be refused and or

signed for as damaged. If the separator is damaged, the local Taco

representative should be contacted for further instructions.
WARNING:  DO  NOT  BRAZE  PIPING  TO  THE  NOSE  OF  THE

VENT;  PERMANENT  DAMAGE  WILL  OCCUR  TO  THE  AIR

VENT INTERNAL PARTS.      

INSTALLATION

TO BE INSTALLED BY 

PROFESSIONAL INSTALLERS ONLY 

4900A – Air Separators

Taco  4900A  series  separators  are  designed  for  installation  in

hydronic  systems.  The  purpose  of  the  4900A  separator  is  the

removal of air from the heating or chilled water system. In a heating

system application the separator should be mounted in the piping

as close as possible to the exit of the boiler and upstream of the

pumps in the system. These units are not designed to withstand

external piping loads which may be transmitted to the nozzles from

the piping system. Should external piping loading requirements be

present, confirmation from Taco’s Design Engineering department

regarding  the  suitability  of  the  separator’s  design  should  be

obtained prior to installing this product. External piping must be

supported within the design of the external piping system.

When  separators  are  installed,  care  should  be  taken  to  allow

access to the ASME name plates, air vent (located at the top of

each separator), flushing cock (located at the side of each unit)

and drain plug (installed in the bottom of each unit).

All piping to each separator should be installed full size, to match

the vessel’s connections, isolation valves on each side of the unit

should be installed for future maintenance. The isolation valves

are used during maintenance to reduce the loss of system fluid.

See Warning under General section.

4900AD – Air and Dirt or Dirt (D) Separators

Taco  4900AD  series  separators  are  designed  for  installation  in

hydronic  systems.  The  purpose  of  the  4900AD  separator  is  the

removal of air and dirt from the heating or chilled water system. In

a heating system application, the separator should be mounted in

the piping as close as possible to the exit of the boiler and upstream

of the pumps in the system. These units are not designed to with-

stand external piping loads which may be transmitted to the nozzles

from  the  piping  system.  Should  external  piping  loading  require-

ments  be  present,  confirmation  from  Taco’s  Design  Engineering

department  regarding  the  suitability  of  the  separator’s  design

should be obtained prior to installing this product. 

When separators are installed, care should be taken to allow access

to the ASME name plates, air vent (located at the top of each sepa-

rator),  and  flushing  cock  (located  at  the  side  of  each  unit).  On

4900AD air and dirt separators the drain/blowdown valve located at

the  bottom  of  the  unit  should  be  piped  to  drain.  This  connection

should be piped with a full port shutoff valve to a nearby drain during

installation.

All piping to each separator should be installed full size, to match

the vessel’s connections, isolation valves on each side of the unit

should be installed for future maintenance. The isolation valves

are used during maintenance to reduce the loss of system fluid.

See Warning under General section.

WARNING: FAILURE TO COMPLY WITH THESE INSTRUCTIONS

REGARDING THIS PRODUCT CAN RESULT IN SERIOUS PER-

SONAL INJURY OR DEATH AND/OR SEVERE PROPERTY DAMAGE.

SUPERCEDES: December 8, 2014     

    EFFECTIVE: September 15, 2015

4900 Series Air Separators

4900 Series Air and Dirt Separators

Installation, Operation & Maintenance Manual

402-080

GENERAL

All Taco 4900 series separators are designed and fabricated in

accordance with the ASME Code for Unfired Pressure Vessels,

Sect. VIII Div. 1.

Prior to shipment all separators are hydrostatically tested to 1.3

times their rated working pressure and accepted by an indepen-

dent insurance inspector.

Upon receipt of each separator, the shipping container should be

examined for external damage. If the shipping container has been

damaged in transit, the contents of the packaging should also be

examined  prior  to  acceptance  of  the  shipment.  If  the  separator

appears to be damaged the shipment should be refused and or

signed for as damaged. If the separator is damaged, the local Taco

representative should be contacted for further instructions.
WARNING:  DO  NOT  BRAZE  PIPING  TO  THE  NOSE  OF  THE

VENT;  PERMANENT  DAMAGE  WILL  OCCUR  TO  THE  AIR

VENT INTERNAL PARTS.      

INSTALLATION

TO BE INSTALLED BY 

PROFESSIONAL INSTALLERS ONLY 

4900A – Air Separators

Taco  4900A  series  separators  are  designed  for  installation  in

hydronic  systems.  The  purpose  of  the  4900A  separator  is  the

removal of air from the heating or chilled water system. In a heating

system application the separator should be mounted in the piping

as close as possible to the exit of the boiler and upstream of the

pumps in the system. These units are not designed to withstand

external piping loads which may be transmitted to the nozzles from

the piping system. Should external piping loading requirements be

present, confirmation from Taco’s Design Engineering department

regarding  the  suitability  of  the  separator’s  design  should  be

obtained prior to installing this product. External piping must be

supported within the design of the external piping system.

When  separators  are  installed,  care  should  be  taken  to  allow

access to the ASME name plates, air vent (located at the top of

each separator), flushing cock (located at the side of each unit)

and drain plug (installed in the bottom of each unit).

All piping to each separator should be installed full size, to match

the vessel’s connections, isolation valves on each side of the unit

should be installed for future maintenance. The isolation valves

are used during maintenance to reduce the loss of system fluid.

See Warning under General section.

4900AD – Air and Dirt or Dirt (D) Separators

Taco  4900AD  series  separators  are  designed  for  installation  in

hydronic  systems.  The  purpose  of  the  4900AD  separator  is  the

removal of air and dirt from the heating or chilled water system. In

a heating system application, the separator should be mounted in

the piping as close as possible to the exit of the boiler and upstream

of the pumps in the system. These units are not designed to with-

stand external piping loads which may be transmitted to the nozzles

from  the  piping  system.  Should  external  piping  loading  require-

ments  be  present,  confirmation  from  Taco’s  Design  Engineering

department  regarding  the  suitability  of  the  separator’s  design

should be obtained prior to installing this product. 

When separators are installed, care should be taken to allow access

to the ASME name plates, air vent (located at the top of each sepa-

rator),  and  flushing  cock  (located  at  the  side  of  each  unit).  On

4900AD air and dirt separators the drain/blowdown valve located at

the  bottom  of  the  unit  should  be  piped  to  drain.  This  connection

should be piped with a full port shutoff valve to a nearby drain during

installation.

All piping to each separator should be installed full size, to match

the vessel’s connections, isolation valves on each side of the unit

should be installed for future maintenance. The isolation valves

are used during maintenance to reduce the loss of system fluid.

See Warning under General section.

WARNING: FAILURE TO COMPLY WITH THESE INSTRUCTIONS

REGARDING THIS PRODUCT CAN RESULT IN SERIOUS PER-

SONAL INJURY OR DEATH AND/OR SEVERE PROPERTY DAMAGE.

INITIAL SYSTEM FILL

WARNING: 

Prior to the initial filling of the system the automatic air vent 

installed in the top of the separator should be closed to prevent system 

debris from fouling the venting mechanism. The automatic air vent may 

be manually closed by turning the orifice screw located in vent face 

clockwise until seated. Additionally, the flushing cock installed on the side 

of the separator should be opened to allow the air within the system to 

exit during the system filling process. The flushing cock should be closed 

when system fluid first appears to exit the separator from the flushing 

cock.

Upon the completion of the system filling process the orifice of the 

automatic vent should be re-opened by turning the screw 1 to 1½ turns 

counter-clockwise. Do not overturn the screw beyond 1 to 1½ turns.