background image

6. Remove the old seal seat and cup from the seal face

plate.  Lubricate  the  new  cup  with  soapy  water  and

install new parts in the face plate recess. Replace the

face plate to its original position. Carefully tap the face

plate evenly into the recess in the motor housing.

7. Clean the impeller shaft before installing the new seal.
8. Lubricate the impeller shaft with soapy water. Do not

install new seal on a dry impeller shaft or damage to

seal may result.

9. Slide  the  new  carbon  seal  and  spring  assembly  onto

the shaft until it contacts the seal seat.

10. While holding the rotor in place as in Step 3, thread the

impeller onto the shaft in a counter-clockwise direction

until it stops. Check to make sure the pump will rotate.

If the impeller will not spin freely, contact Taco Technical

Support at 1-401-942-8000.

11. Remove old body gasket and replace with new gasket

provided in seal kit. Press gasket into seal face plate,

then attach motor to casing. Use caution not to pinch

body gasket or leaks may result.

12. Attach  the  pump  casing  to  the  motor  housing  and

secure with the four body bolts. Be sure flow arrow on

casing is pointing in proper direction. Tighten the four

bolts  evenly  in  a  criss-cross  pattern  to  70  in-lb  of

torque. There should be a small, even gap between the

casing and the motor mounting bracket.

13. Re-install  circulator  into  system  using  new  flange

gaskets, if required. 

14. Reconnect electrical wiring. Do not open electrical sup-

ply to pump until “System Start-Up” steps are complete.

SYSTEM START-UP:

1. Prior to pump start-up, closed heating and cooling sys-

tems should be thoroughly cleaned, flushed and drained.

2. Open isolation valves and re-fill system with clean water.

Check for any leaks.

3. Vent all air  from system at an  air  vent located  at  the

high point in the system.

4. Start circulator to check for proper operation.

PERIODIC INSPECTION, MAINTENANCE:

Taco 2400 Series Hi-Capacity circulators are designed to

provide  years  of  trouble-free  service.  However,  periodic

inspection and routine maintenance is recommended for all

hydronic  systems  and  mechanical  equipment.  If  any  evi-

dence  of  leakage  or  damage  is  present,  take  preventive

steps to repair or replace the circulator immediately.

CAUTION: Do not start the pump until the sys-

tem  has  been  completely  filled  and  vented.

Running  the  pump  dry  may  damage  the

mechanical seal and void warranty.

CAUTION: Do not allow screwdriver to make

contact  with  motor  windings  or  insulation.

Permanent damage to motor may result.

Fig. 1: Exploded View of Pump

SEAL SPRING

BODY GASKET

SEAL RETAINER

CASING

MOTOR ASSEMBLY

FACE PLATE

ROTATING SEAL

IMPELLER

BODY BOLTS (4)
TORQUE TO
65 15 IN-LBS

STATIONARY SEAL

2400 (3P MODELS)

TACO, INC.

, 1160 Cranston Street, Cranston, RI 02920    Telephone: (401) 942-8000    FAX: (401) 942-2360.

TACO (Canadá), Ltd.

, 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8.    Telephone: 905/564-9422.    FAX: 905/564-9436.

Visit our web site at: 

http://www.taco-hvac.com

Printed in USA

Copyright 20150

TACO, Inc.

Reviews: