APPLICATION:

The Taco 2400 Series Hi-Capacity circulators are designed

for  use  on  a  wide  range  of  hydronic  heating,  cooling  or

domestic water re-circulating systems. Features include a

quiet  running,  close-coupled,  thermally  protected  motor

assembly with permanent split-capacitor and permanently

lubricated bearings. A stainless steel face plate and  shaft,

carbon/silicon-carbide  mechanical  seal  and  non-ferrous

impeller make the 2400 series an ideal choice for years of

maintenance-free operation on open or closed systems.

Note: Always use Stainless Steel body circulators on

open, fresh water systems.

OPERATING SPECIFICATIONS:

• Maximum Working Pressure: 150 psi (1000 kPa)
• Maximum Operating Temperature: 225ºF (107ºC)
• Electrical Rating: 115V/60Hz/1Ph or 230V/60Hz/1Ph

REMOVAL OF EXISTING PUMP FROM SYSTEM PIPING:

1. Disconnect and lock-out electrical supply to pump.
2. Close isolation valves on suction and discharge sides

of  pump.  If  valves  are  not  installed,  the  system  may

need to be drained.

3. Remove capacitor box cover and disconnect electrical

supply lines to pump.

4. Loosen  flange  bolts  and  shift  pump  body  slightly  to

relieve any remaining system pressure. 

5. Remove flange nuts/bolts and pump from system.

REPLACING THE MECHANICAL SEAL: 

Refer to Fig. 1

on back page.

1. Follow steps 1 thru 5 in section “Removal of existing

pump from system piping”.

2. Loosen the four body bolts that attach the motor hous-

ing to the casing. While supporting the motor, remove

the  four  bolts  and  carefully  remove  the  motor  and

impeller assembly from the casing.

3. To remove  the  impeller,  first  insert  a  screwdriver  into

the motor ventilation slots to make contact with one of

the rotor cooling fins. While holding the rotor in place

with  the  screwdriver,  turn  the  impeller  clockwise  to

loosen and remove from shaft.

4. Remove the seal assembly from the impeller shaft.

Note:

2400 models with suffix “3P” are provided with a

3-piece rotating seal.

5. Remove  the  seal  face  plate  by  gently  prying  it  away

from the housing.

Instruction Sheet

Mechanical Seal Replacement

2400 Series Hi-Capacity Circulator

102-414

SUPERSEDES: December 19, 2014

EFFECTIVE: March 2, 2015

Plant ID# 001-3933

INSTALLER: Please leave these instructions for 

                     owner’s use.

CAUTION: Taco “2400 Series” circulators are

designed for indoor use only.

CAUTION:  To  prevent  injury,  allow  system

water  to  cool  to  100ºF  before  removing  old

pump or draining system. Leave drain valve

open until service/replacement is complete.

* Includes new body gaskets

CAUTION: Do not allow screwdriver to make

contact  with  motor  windings  or  insulation.

Permanent damage to motor may result.

MECHANICAL SEAL

OPTIONS

SEAL KIT NUMBER*

Standard Seal

Carbon/Silicon-Carbide

2400-029RP

CAUTION:  The  majority  of  mechanical  seal

failures are due to poor media (fluid) quality

in  the  system.  To  maximize  seal  life,  media

quality  must  be  maintained  in  the  system,

and TDS (Total Dissolved Solids)/TSS (Total

Suspended  Solids)  should  not  exceed

500ppm  with  standard  Carbon/Silicon-

Carbide  seals.  The  use  of  inhibitor  based

glycols  is  acceptable,  but  additional

inhibitors  should  not  be  added. Always  fol-

low  the  glycol  manufacturer’s  specification

for  system  preparation  and  water  quality.

Treatment with silicates should not be used.

Failure to maintain media quality will void the

standard Taco warranty.

STAINLESS STEEL 

MODELS ONLY

FOR INDOOR 

USE ONLY