00e

series VT2218

Instruction Sheet

102-510

SUPERSEDES: NEW

EFFECTIVE: June 14, 2016

Plant ID No. 001-4267

Delta-T Variable Speed, ECM High-Efficiency Circulator

DESCRIPTION:

The 00e

series VT2218 circulator is a temperature sensing, self-adjusting, variable speed

wet  rotor  circulator  with  an  ECM,  permanent  magnet  motor.  Operating  modes  include

Delta-T,  constant  speed,  set  point  heat,  set  point  cool,  and  boiler  protection.  Its  high

efficiency motor reduces power consumption by up to 85% compared to equivalent AC

permanent split capacitor circulators.

APPLICATION:

     •   Maximum operating pressure: 125 psi (862 kPa)
     •   Minimum water temperature: 36ºF (2ºC)
     •   Maximum water temperature: 230°F (110ºC)
     •   Electrical specifications:

             Voltage: 110-120V, 50/60 Hz, single phase

             Maximum operating power: 58W

             Maximum amp rating: 0.67

     •   Equipped with a cast iron casing and should be used for closed loop systems only.
     •   Taco circulator pumps are for indoor use only – employer uniquement a l’interieur.
     •   Acceptable for use with water or maximum of 50% water/glycol solution.

FEATURES:

     •   5 operating modes:

             - Delta-T - variable speed, maintains constant ∆T, provides exact GPM flow required

             - Constant Speed - 4 fixed speeds, maintains constant flow for zoning

             - Set Point Heat - variable speed with boiler protection option, decreases speed on temperature rise

             - Set Point Cool - variable speed, increases speed on temperature rise

             - Boiler Protection - protects boiler from low return temperature and flue gas condensation

     •   Illuminated LCD displays:

               - Operating mode, speed or temperature setting, watts, gpm, supply temperature, return temperature, and

                error code diagnostics.

     •   Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation.
     •   Integral Flow Check (IFC) is included in carton. Simply press into discharge flange if required.
     •   Nut capture feature on flanges for easier fit up. 
     •   Whisper quiet operation.
     •   BIO Barrier

®

protects the pump from system contaminants.

     •   

SureStart

automatic unblocking mode.

     •   Optional, 2-way flange model available to reduce SKU’s and provide universal fit-up to any flange position.

INSTALLATION:

WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.

AVERTISSEMENT: Ne pas utiliser dans une piscine ou un spa. La pompe n'a pas été étudiée pour ces applications.
CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment voids the 

warranty. Consult factory for fluid compatibility.

ATTENTION: L'ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO

annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.
CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent pump cavitation

and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. A larger size expansion tank may

be required.

ATTENTION: Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée

de 20 psi au minimum afin d'éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez

la pression du réservoir d'expansion de façon qu'elle soit égale à la pression de remplissage. Un réservoir d'expansion d'une taille

supérieure peut être nécessaire.

For more information, visit

www.TacoComfort.com

Use for pumps with

date code TBD 

or after

.

Summary of Contents for 00e VT2218 Series

Page 1: ...one Valve Control or SR Switching Relay for ON OFF operation Integral Flow Check IFC is included in carton Simply press into discharge flange if required Nut capture feature on flanges for easier fit up Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking mode Optional 2 way flange model available to reduce SKU s and provide universal fit up...

Page 2: ...E RECOMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED ...

Page 3: ... PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRES SURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION ...

Page 4: ...rential T Set Point Heat Varies speed to maintain a fixed temperature Boiler Protection Option Decreases speed to protect boiler from low return water temperature and flue gas condensation Boiler Protection Increases speed to protect boiler from low return water temperature and flue gas condensation Heating or Chilled Water Cooling Set Point Heat Decreases speed on temperature rise Set Point Cool ...

Page 5: ...ta T operating mode with a 20 F temperature differential setting If this is your desired operating mode and Delta T setting no programming changes are required CAUTION Never run the circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter The VT2218 has 5 Operating Modes Delta T Varies speed to maintain a fix...

Page 6: ...Start Cycle to its highest speed until target T is reached Start Cycle will dis play on the LCD screen in place of Watts If T is GREATER than target the pump will immediately go into Variable Speed operation and vary speed to maintain the target T Constant Speed Mode Speeds 1 2 3 4 default Speed 4 In Constant Speed mode the VT2218 will always start and run at the pre set Speed Level 1 through 4 On...

Page 7: ...n ERROR CODE DESCRIPTION CORRECTIVE ACTION SENSOR 1 MISSING Supply sensor disconnected Reconnect sensor SENSOR 2 MISSING Return sensor disconnected Reconnect sensor SENSOR 1 SHORTED Bad sensor Replace sensor SENSOR 2 SHORTED Bad sensor Replace sensor AC INPUT UNDER VOLTAGE Low voltage problem Check power supply AC INPUT OVER VOLTAGE High voltage problem Check power supply LOCKED ROTOR Probable loc...

Page 8: ...t or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its prod...