TAC Xenta 555, Supplement Manual
4 Connecting the TAC Xenta 555 to Your Network
TAC AB, Oct 2006
29 (82)
04-00054-01-en
4.3
Connecting the TAC Xenta 555 to a MicroNet
Controller LAN
The method of connecting the Xenta 555 to a MicroNet controller LAN
depends on the MicroNet LAN type. These networks are:
•
MicroNet NCP network, that is, MicroNet controllers using the
Native Communications Protocol. A MicroNet Manager Interface
(MN MI) must not be used.
•
MicroNet ARCNET network, that is, MicroNet controllers using
the Attached Resource Computer Network protocol. An MN MI
must be used.
•
Satchnet network, that is, older products using the Satchwell Net-
working Protocol (SNP). A Modem Interface Unit (MIU) must not
be used.
!
Note
Auto dial remote sites are not supported by the Xenta 555.
Tip
The MN MI and the MIU are not required for NCP and SNP networks
and can be removed when installing the Xenta 555.