TAC 2112, Manual
Commissioning Protocol / List of Parameters
TAC AB, 1999-08-01
0-004-7459-3 (GB), A:5(6)
P No. Parameter
Min.
Max.
Step
Default
Change Comments
P 74
Supply temp. pump stop
0°C
120°C
1°C
20°C
P 75
Exercise on/off
0 (off)
1 (on)
1
1 (on)
0=off, 1=on
P 76
Min. off time for pump
0 h
12 h
0,5 h
2 h
h=hours
P 77
Adjustment, outdoor sensor -5 °C
5 °C
0,25 °C
0°C
P 78
Adjustment, ref. sensor
–5 °C
5 °C
0,25 °C
0 °C
With ref. sensor only
P 79
Damping const., outd. temp 0 h
20 h
1 h
4 h
0=no damping, h=hours
P 80
Current SPC effect
(-1)
•
P81 P 81
0,1 °C
P 81
SPC effect at +10 V
0 °C
40 °C
1 °C
0 °C
-40
0
5
7
8
6
9
10
4
3
2
+40
Effect on
setpoint (°C)
SPC signal
(V)
P 81
P 82
Alarm, pump
0
1
1
0=no alarm, 1=alarm
P 83
Alarm, supply temp.
0
1
1
0=no alarm, 1=alarm
P 84
P 85
P 86
P 87
P 88
P 89
Man. cont., outd. sensor sig.
(Y2)
0 V
10 V
0,1 V
P 90
Man. cont. of pump (K1)
0
1
1
0=off, 1=on
P 91
Man. cont., output (K2)
0
1
1
0=off, 1=on
P 92
Man. cont., buzzer alarm
(K3)
0 1 1
0=off, 1=on
P 93
Man. cont., weekly program
2 (K4)
0 1 1
0=off, 1=on
P 94
Man. cont., heating (K5/K6)
0
1
1
–1=close, 1=open, 0=off
P 95
Serial number (part 1)
0000
9999
1
*
* as per type label
P 96
Serial number (part 2)
0000
9999
1
*
* as per type label
P 97
P 98
P 99
Display test, etc.
-
-
-
Summary of Contents for 2112
Page 1: ...TAC 2112 Manual 0 004 7459 3 GB 1999 08 01 T1 P1...
Page 2: ......
Page 66: ...TAC 2112 Manual Index Index 4 4 0 004 7459 3 GB TAC AB 1999 08 01...
Page 68: ...TAC 2112 Manual Reply form 1999 08 01 TAC AB...
Page 69: ......
Page 70: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 www tac se...