Measure Valve

23

Measure Valve

TA-CMI

22

18. Press Done.

The appropriate flow value is now displayed.

The temperature displayed in the Measure Valve
menu is in this case without importance.

17. Confirm the entered value.

If the selected valve is any other than TA valve types STAD, STAF or TBV
and you try to set the media to anything other than water, this error
message is displayed and the media setting is automatically changed to
water. The reason for this is that the correction method that TA-CMI uses
to calculate the flow when using media types other than water, can only be
made with these valve types.

If the system contains water, ethylene glycol or propylene glycol you can stop reading here.
The appropriate flow value is now displayed.

If the system contains any other media type, enter the density and the viscosity of the media
according to below.

12. Open the Media density dialog by pressing

the down key, then pressing Enter.

13. Enter the appropriate media density, by using

the up, down and right keys.

14. Confirm the entered value.

15. Open the Media viscosity dialog by pressing

the down key, then pressing Enter.

16. Enter the appropriate viscosity, by using the

up, down and right keys.

While measuring differential pressure (and flow)
or temperature (see pages 24 – 25) you can freeze
measurements by pressing Freeze.

The measured values will be freezed, i.e. so that
you will have time to make a note of them.

Press Start when you want to restart measurement.

Freezing measurements

Summary of Contents for CMI

Page 1: ...TA CMI 307 161 50 2004 xx User Manual...

Page 2: ...ument 9 Connection to measuring points 10 Disconnection from measuring points 12 Measure Valve 14 Entering the valve factor Kv value for other valve types 18 Define media 20 Freezing measurements 23 M...

Page 3: ...r AnderssonAB authorised service centre with a description of the problem TA does not accept the risk of damage to the product during transport After repair under guarantee the product will be returne...

Page 4: ...nter Storage above 40 C reduces battery life Unpacking Check that these items are delivered Unpacking TA CMI Dok nr 01 2003 06 GB Manual 1 SE Manual xx TA CMI 1 2 3 4 5 6 7 8 9 10 11 12 1 Instrument u...

Page 5: ...shows how you set or determine the number of valve turns on a TA valve The valve s opening position can be read on the digital handwheel Closed valve Valve open to 2 3 turns Keyboard two keys Functio...

Page 6: ...The main function menu of the TA CMI is displayed You select different functions from the main function menu by pressing the down or up key repeatedly and then pressing Enter on the desired selection...

Page 7: ...ng points 3 Connectiontomeasuringpoints 2 Connect the measuring needles to the measuring hoses Connection to measuring points 1 Connect the measuring hoses to the sensor unit Note The connections with...

Page 8: ...ways disconnect the measuring needles from the measuring points 1 before disconnecting the bayonet couplings at the measuring hoses and the sensor unit 2 3 Disconnectionfrommeasuringpoints 1 Disconnec...

Page 9: ...for STAF 125 this error message is displayed MeasureValve 1 Connect the sensor unit to the measuring points on the valve according to pages 10 11 Risk of burn if the media is hot Always connect the m...

Page 10: ...ensor unit 11 When the correct valve setting is specified press Done If an error message is displayed press OK The setting is automatically changed to the maximum value possible or if you have tried t...

Page 11: ...ey then pressing Enter 9 Confirm the entered valve name 4 Enter the appropriate valve factor by using the up and down keys Use the right key to move the cursor to the next digit 5 Confirm 10 After you...

Page 12: ...pe displayed in the Measure Valve menu does not correspond to actual media type you have to define appropriate media according to below 1 Navigate to the media type line by repeatedly pressing the dow...

Page 13: ...ethylene glycol or propylene glycol you can stop reading here The appropriate flow value is now displayed If the system contains any other media type enter the density and the viscosity of the media...

Page 14: ...media for flow calculations see pages 20 21 Save the measured temperature as media temperature according to below 1 In the Measure Temp menu press Functions 2 Select Save as media temp by pressing En...

Page 15: ...calculation HandwheelSettingcalculation This function is used to calculate the valve setting that corresponds to a given flow and differential pressure for a specific valve The function includes no me...

Page 16: ...rns is displayed If the pressure value is out of the pressure range 0 5 200 kPa for TA CMI an error message is displayed press OK Finally enter the appropriate differential pressure and press Enter Th...

Page 17: ...is off until the sensor unit has been connected to the instrument unit via the cable Instrument Setup and Information Information In the Information menu you can access information about The instrume...

Page 18: ...sensor unit to communicate with your instrument unit Incorrect function If the instrument works incorrectly i e due to static electricity discharge keep the start key depressed and within one second a...

Page 19: ...on tread 1 2 52 197 303 Connection tread 3 4 52 197 304 TA No Measuringhoses 3 m extension red with shut off valve 52 197 093 3 m extension blue 52 197 094 150 mm with twin needle 52 198 801 Spanners...

Page 20: ...36 TA CMI...

Page 21: ...on of Registration Number 2125 and 2125 M Certified by SP Q U A L I T Y AND ENVIRONMENT S Y S T E M TOUR ANDERSSONAB X X Sweden Tour Andersson AB Norra Gubberogatan 32 Box 6281 SE 400 60 G teborg Tel...

Reviews: