background image

Shut-off and drain  

To shut the STAP completely, use a 5 mm allen key on the spindle 

. STAM ,or STAD, can be shut off 

using the handwheel. The valves can be drained by using a 5 mm allen key on spindel 

 on STAP and 

on spindle 

 on STAM ,or STAD. 

Accessories

 (Figures 3 and 4)

Allen keys 

3 mm 

52 187-103 

For adjusting 

p

L

 at 

 

 

5 mm 

52 187-105 

Shut-off at 

, drain at 

 and 

 

Probes 

Pair 

52 196-312  

at 

 and 

 

 

Single 

52 196-313 

at 

 and 

 

 

Single with valve  52 196-314 

at 

 and 

 

Fig. 4  Measurement probes

52 196-312  52 196-313 

52 196-314

Pair 

Single 

Single with 

  

 

valve

p

L

1

4

3

2

Fig. 1

Return

Inlet

5

Fig.3 Kv

STAM

   No. of turns
 

 

DN15 DN20 DN25 DN32 DN40 DN50

 

0.36 2.19 3.07  

4.45 6.92 9.49

 

1.02 4.13 5.82  

9.75 13.4 18.4

 

3.00 5.15 7.51 12.9 18.2 26.2

 
 

4.01 5.95 8.26 14.6 20.7 32.9

5D

2D

STAM (STAD)

Fig. 2

  

General

STAP is a self-acting differential pressure controller for use in variable flow systems, both in heating and 
cooling. When the available differential pressure is too high for some components (eg control valves, 
thermostatic valves), STAP limits the differential pressure, 

p

L,

 across the circuits, at a suitable value. 

STAP can also be used to stabilise the differential pressure across a control valve, maintaining its authority 
close to 1 for a good and stable control. STAP is available for the ranges 5-25 kPa and 20-60 kPa with 
factory presetting of 10 and 30 kPa respectively.

Features

STAP also provides drain, shut-off and differential pressure measurements facilities. STAP is comple-
mented by STAM (or STAD) which is used for flow measurement and connection of the signal pipe from 
STAP. They also provides drain and shut-off functions.

Installation

Install the valves so that the flow is in the direction shown in figure 1. The valves can be mounted in any 
orientation but take care about the distances shown in figure 2 for STAM (or STAD). Connect the signal 
pipe 

 between the two valves (the connections are turnable), then open the drain valve spindle 

 fully.

The plant should be equipped with strainers. (Do not fit the insulation until the system has been commis-
sioned). If it is necessary to remove the valve bonnet when installing STAP, make sure that the o-ring is 
undamaged when refitting it.

Pressure-testing the system 

The maximum test static pressure is 2 MPa (20 bar).

Commissioning  

Radiator valves or other devices must be adjusted to give the design flow for the desired differential pressure 

p

L

. Open fully the control valves or thermostatic heads. Deaerate the system and deaerate also the signal 

pipe by inserting a CBI measuring probe through the nipple 

, leaving it open until only water emerges. 

Flow measurement

Measure the flow through the STAM (or STAD) using a CBI, connected betwen 

 and 

. If the pres-

sure drop is too low (which will be indicated by the CBI), close STAM by the whole number of turns that 
will allow flow measurement. STAD can be closed to any position. Re-open the valve after measuring to 
avoid an unnecessary pressure drop. Note the flow on the label fitted to the valve, eg q=0,2 l/s  (

P=10 

kPa). If the design flow cannot be achieved, it may be due to blockages in the system. Find and rectify 
the fault and measure again. If the circuit requires a 

p

L

 that differs from the factory setting, follow the 

instructions below. 

Setting differential pressure, 

p

L

STAP is delivered with a factory setting of 10 respectively 30 kPa, which can be adjusted at site in order 
to achieve the design flow. Use a 3 mm allen key, inserting it carefully through the whole in the rubber 
seal at 

. When the key has been fully inserted and engaged with the end of the inner spindle of  STAP, 

turn it clockwise to increase 

p

L

 (or anti-clockwise to decrease ). To change the setting of 1 kPa it takes 

1,5 turns for the range 5-25 kPa and 0,5 turns for 20-60 kPa.
Example:
Factory setting = 30 kPa
Required differential pressure = 46 kPa
Turn the inner spindle 0,5 x (46-30) = 12 turns clockwise
The actual differential pressure can be checked using a CBI. Measure it between 

 and 

 or between 

 and 

. Note that it takes 2-3 minutes from changing the setting until the required value is obtained.

Systems without pre-settable radiator valves

Use a STAD in the supply pipe in the opposite direction to figure 1. In this case, the pressure drop across 
the STAD is included in the controlled circuit (

p

L

). Preset the STAD for a pressure drop of 11 kPa for 

design flow. Connect a CBI to the valve, measure the flow and adjust 

p

L

 on STAP as described until the 

design flow is achieved (with all thermostatic heads fully open).  

4

English

Summary of Contents for STAP

Page 1: ...20 C Min Betriebstemperatur 5 C Werkstoffe Ventilgehäuse und Oberteil aus AMETAL O Ringe aus EPDM Gummi Sitzdichtung Kegel mit O Ring aus EPDM STAP Membran aus EPDM Gummi und Feder aus rostfreiem Stahl STAM Handrad aus Polyamid Kunststoff Kennzeichnung Gehäuse PN 20 150 DN Zoll Angabe STAP pL 5 25 kPa bzw 20 60 kPa STAM Handrad Ventilbauart und DN Gewinde Innen G1 2 G2 Entleerung Entleerungsnippel...

Page 2: ...ipe 52 165 901 cover with nipple 52 179 881 are included Einschließlich 1 m Impulsleitung 52 165 901 sowie Kappe mit Nippel 52 179 881 Y compris un capillaire de 1 m 52 165 901 et son raccord 52 179 881 TA No TA Nr No TA DN L H1 D Kvs d 1 2 d 3 4 52 149 315 52 149 815 15 90 100 G1 2 4 01 52 149 320 52 149 820 20 97 100 G3 4 5 95 52 149 325 52 149 825 25 110 105 G1 8 26 52 149 332 52 149 832 32 124...

Page 3: ...anne STAM permet de s assurer que le débit est correct Cette mesure étant faite la STAM est réouverte complètement Einregulierung Zur Beschreibung der verschiedenen Einregulierungsverfahren siehe Handbuch Nr 1 Die hydraulische Einregulierung von Regelkreisen Handbuch Nr 2 Die hydraulische Einregulierung von Verteilungssystemen Handbuch Nr 3 Einregulierung von Heizkörpersystemen Einregulierung Tota...

Page 4: ...a 25 kPa 30 kPa 35 kPa 40 kPa 45 kPa 50 kPa 55 kPa 60 kPa 15 70 300 900 1150 1400 1620 1830 2050 2270 2480 2700 20 80 500 1560 1920 2270 2640 3010 3390 3760 4130 4500 25 90 1000 2060 2470 2880 3250 3620 3990 4360 4730 5100 32 100 2000 3660 4280 4900 5560 6220 6880 7540 8200 8860 40 110 3600 5320 5940 6570 7290 8020 8750 9470 10200 10900 50 120 5400 8120 9190 10300 11400 12500 13600 14700 15800 169...

Page 5: ...atsächlicher Volumenstrom Obiges gilt für Flüssigkeiten mit im großen und ganzen gleicher Viskosität 20 cSt 3 E 100 S U wie Wasser d h für die meisten Wasser Glykol mischungen und Salzwasserlösungen bei Raumtemperatur Bei geringeren Temperaturen steigt die Zähigkeit an und es kann bei einigen Ventilen lami nare Strömung entstehen das Risiko steigt bei kleineren Ventilen geringeren Einstellungen un...

Page 6: ... 25 kPa 20 60 kPa 15 52 166 015 52 166 115 20 52 166 020 52 166 120 25 52 166 025 52 166 125 32 52 166 032 52 166 132 40 52 166 140 50 52 166 150 Cover with nipple Kappe mit Nippel Raccord entre le capillaire d TA No TA Nr No TA d 1 4 52 179 881 1 2 52 179 886 3 4 Included in STAP Im STAP inbegriffen Livré avec la STAP Rating plate Kennzeichnungsschild Plaque de marquage TA No TA Nr No TA 52 161 9...

Page 7: ... ring is undamaged when refitting it Pressure testing the system The maximum test static pressure is 2 MPa 20 bar Commissioning Radiator valves or other devices must be adjusted to give the design flow for the desired differential pressure pL Open fully the control valves or thermostatic heads Deaerate the system and deaerate also the signal pipe by inserting a CBI measuring probe through the nipp...

Reviews: