7 (10)
DIM119E
F-27506-1
VB-72XX Two Way Globe Valve, Forta Proportional Control Setup Reference
VB-73XX Three Way Globe Valve, Proportional Control Setup Reference
Valve Type
Valve position
at low signal
input
Switch 1 Switch 2
Switch 7
Power up
Position
Input
Signal
Action
Low end
of signal
input
range
Feedback signal
action
DA
Table 1
VB-72xx 2 way valves
Forta M400A / M800A Base Proportional Configuration
Program Switch Position
Desired Valve Operations
VB-722x stem
up closed
OFF
OFF
OFF
Retract
No Flow
Extend
Full Flow
10 vdc Full Flow
2 vdc No Flow
Retract
No Flow
Retract
No Flow
2 vdc No Flow
10 vdc Full Flow
DA
RA
VB-722x stem
down open
OFF
OFF
ON
VB-722x stem
up closed
ON
OFF
ON
Extend
Full Flow
Extend
Full Flow
2 vdc Full Flow
10 vdc No Flow
Extend
Full Flow
Retract
No Flow
10 vdc No Flow
2 vdc Full Flow
DA
RA
VB-722x stem
down open
ON
OFF
OFF
VB-721x stem
up open
ON
OFF
ON
Extend
No Flow
Extend
No Flow
2 vdc No Flow
10 vdc Full Flow
Extend
No Flow
Retract
Full Flow
10 vdc Full Flow
2 vdc No Flow
RA
DA
VB-721x stem
down closed
ON
OFF
OFF
Retract
Full Flow
Retract
Full Flow
2 vdc Full Flow
10 vdc No Flow
VB-721x stem
up open
OFF
OFF
OFF
RA
Programming Note:
The above switch positions are the base programming configurations, in the base
configurations all other switches should be
switched off
. Once the base programming configuration has
been set up you may wish to add additional program features and functions that are listed below.
DA = Full open, full flow, 10vdc output / Full closed, no flow, 2vdc output
RA = Full open, full flow, 2vdc output / Full closed, no flow 10vdc output
VB-721x stem
down closed
OFF
OFF
ON
Retract
Full Flow
Extend
No Flow
10 vdc No Flow
2 vdc Full Flow
Valve Type
Valve position at
low signal input
Switch 1
Switch 2 Switch 7
Power up
Position
Low end of signal
input range
Feedback signal
action @ port B
Table 2
VB-73x3 3 way valves
Forta M400A / M800A Base Proportional Configuration
Program Switch Position
Desired Valve Operations
VB-731x stem up
open B to AB
OFF
OFF
OFF
Retract Full Flow
B to AB
Extend No Flow
B to AB
10 vdc No flow
2 vdc Full flow
Retract Full Flow
B to AB
Retract Full Flow
B to AB
2 vdc Full flow
10 vdc No flow
VB-731x stem down
closed B to AB
OFF
OFF
ON
VB-731x stem up
open B to AB
ON
OFF
ON
Extend Full Flow
A to AB
Extend No Flow
B to AB
2 vdc No flow
10 vdc Full flow
Extend Full Flow
A to AB
Retract Full Flow
B to AB
10 vdc Full flow
2 vdc No flow
VB-731x stem down
closed B to AB
ON
OFF
OFF
VB-732x stem up
flow B to AB
OFF
OFF
OFF
Retract Full Flow
B to AB
Extend No Flow
B to AB
10 vdc No flow
2 vdc Full flow
Retract Full Flow
B to AB
Retract Full Flow
B to AB
2 vdc Full flow
10 vdc No flow
VB-732x stem down
flow B to A
OFF
OFF
ON
Extend Full Flow
B to A
Retract Full Flow
B to AB
10 vdc Full flow
2 vdc No flow
VB-732x stem up
flow B to AB
ON
OFF
ON
Programming Note:
The above switch positions are the base programming configurations, in the base configurations all
other switches should be
switched off
. Once the base programming configuration has been set up you may wish to add
additional program features and functions that are listed below.
VB-732x stem down
flow B to A
ON
OFF
OFF
Extend Full Flow
B to A
Extend No Flow
B to AB
2 vdc No flow
10 vdc Full flow