INSTALLATION

Inspection

Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
If undamaged, open the package and inspect the device for obvious damage. Return 
damaged products.

Requirements

Job wiring diagrams

Tools (not provided)

– Socket wrench 1/2 inch, used for universal mounting clamp nuts
– Open-end wrench 10 mm, used for installing AM-676 universal shaft extension
– Slotted screwdriver, used for installing anti-rotation brackets
– Allen wrench 3/16", used for manual override

Appropriate accessories

– Water tight 1/2 inch conduit seals TAC part number TF-711-02 or T&B #5332 

(straight, TAC part number TF-713-02 or T&B #5352 (90°), or equivalent.

– Water tight 1/2 inch flexible conduit (e.,g. Anaconda: Sealtight) or 20 mm flexible 

water tight conduit when using AM-756 metric conduit adapter with appropriate 
metric water tight seals.

– Water tight 1/2" flexible conduit (Anaconda: Sealtight) or 20 mm flexible water tight 

conduit when using AM-756 metric conduit adaptor

– Two #8 1/2" (13 mm) sheet metal screws for mounting (optional)

Training: Installer must be a qualified, experienced technician

4 to 20 mA DC

Controller

(+) 4 to 20 mA DC

(-) Common DC

Power

GRD

GRD

1

1

2

MS40-717X

MS40-717X

1  Unused conduit port must remain plugged with a 

water tight pipe plug as shipped from factory to 
maintain NEMA Type 4 or IP56 rating.

2  See table for power wire designations.

3  Both actuators must be set to operate in the same 

direction.

Yellow/Black  

AI 

Gray  

Blue  

AO 

Yellow/Black  

AI 

Gray  

Blue  

AO 

Position Feedback (-)

Signal 2 to 10 Vdc (+)

COM 

COM 

3

3

4

4

4  Color coding of wiring on older models (MX40-717x-0-

0-0) manufactured prior to December, 2007, differs 
from current models. See Table 4 on page 14. Consult 
label on product to confirm wiring codes.

5  Keep AI, COM and AO wiring less than 30 meters 

length to meed CE requirements.

5

5

Green/Yellow

Green/Yellow

500 Ohm

Figure-8 Typical 4 to 20 mAdc Control Wiring For Two Actuators On The Same Damper Shaft.

Power Wiring Identification.

Voltage

Designation

Wire Color

24 Vac or

22-30 Vdc

24H (DC+)

Red

24G (DC-)

Black

120 Vac

L1

Black

L2

White

240 Vac

L1

Brown

L2

Light Blue

Summary of Contents for DuraDrive MS40-717 Series

Page 1: ...d reliability and repeatable timing Direct coupled to the damper shaft with dual industrial hardened universal mounting clamps Integral wiring for proportional control by 2 to 10 Vdc or 4 to 20 mAdc1 Clockwise or counterclockwise spring return is determined by actuator mounting position Accurate 92 travel digitally controlled Integral position indication scale Rugged die cast housing Oil immersed ...

Page 2: ...to 25 mm round damper shafts two per package F Number Description Audience Purpose F 26750 MX40 6XXX 2XX MX40 7XXX 2XX Series Actuator Linkage Assemblies General Instructions Sales Personnel Application Engineers Installers Service Personnel Start up Technicians Describes the globe valve actuator linkage assembly s features specifications and possible applications Provides step by step mounting in...

Page 3: ... OD for dual actuator mounting AM 703 Span adjustment AM 704 Modulation Interface converts a PWM to 2 to 10 Vdc AM 705 Positioner remote minimum positioning AM 706 Positioner flush mount digital position indicator AM 707 Digital Indication AM 708 Resistor for 500Ω modulating signal conversion AM 751 Standard anti rotation bracket 9 long x 13 16 wide 229 x 21 mm included with actuator AM 752 Option...

Page 4: ...odes 3 Keep AI COM and AO wiring less than 30 meters length to meet CE requirements 2 3 Figure 1 Typical MS40 7170 2 to 10 Vdc Wiring Diagram MS40 7170 Black White L1 L2 120 Vac GRD Green Yellow Yellow Black Gray AI COM 4 to 20 mA 1 Position Feedback Signal 2 to 10 Vdc Blue AO 500 Ohm Control Signal 1 Unused conduit port must remain plugged with a water tight pipe plug as shipped from factory to m...

Page 5: ...lugged with a water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating 2 Color coding of wiring on older models MX40 717x 0 0 0 manufactured prior to December 2007 differs from current models See Table 4 on page 14 Consult label on product to confirm wiring codes 3 Keep AI COM and AO wiring less than 30 meters length to meet CE requirements 2 3 Figure 4 Typical MS40 717...

Page 6: ...dc Control Signal GRD MS40 717X Power GRD 1 1 2 MS40 717X 1 Unused conduit port must remain plugged with a water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating 2 See table for power wire designations 3 Both actuators must be set to operate in the same direction 3 3 Yellow Black AI Gray COM Blue AO Yellow Black AI Gray COM Blue AO Position Feedback Signal 2 to 10 Vdc...

Page 7: ...r tight conduit when using AM 756 metric conduit adaptor Two 8 1 2 13 mm sheet metal screws for mounting optional Training Installer must be a qualified experienced technician 4 to 20 mA DC Controller 4 to 20 mA DC Common DC Power GRD GRD 1 1 2 MS40 717X MS40 717X 1 Unused conduit port must remain plugged with a water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating 2...

Page 8: ...ference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment to an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio television technician for help Canadian Department of Communications DOC Note This class B digital appa...

Page 9: ... contact the damper manufacturer Damper Shaft Sizing Use the Long Damper Shaft mounting instructions if the damper shaft is at least 4 5 8 117 mm long Use the Short Damper Shaft mounting instructions if the damper shaft is shorter than 4 5 8 or the area around the damper shaft is too narrow to allow standard mounting as described in the Long Damper Shaft mounting section See Figure 9 for minimum s...

Page 10: ...e closed position mount the actuator with the side marked R facing the installer See Figure 10 If the damper shaft rotates counterclockwise to the closed position mount the actuator with the side marked L facing the installer See Figure 11 3 Hand tighten the nuts on both of the actuator s universal mounting clamps 4 Align the actuator at 90 perpendicular to the damper shaft See Figure 12 5 Slide t...

Page 11: ...e Spring Return for Normally Closed Damper R 1 1 5 CENTERLINE 1 Two AM 754 Universal Mounting Clamp Assemblies are provided with each actuator Each clamp assembly includes 1 universal mounting clamp and 1 retaining clip Two Universal Mounting Clamp Assemblies are required for all mounting configurations ...

Page 12: ...TERLINE 1 Two AM 754 Universal Mounting Clamp Assemblies are provided with each actuator Each clamp assembly includes 1 universal mounting clamp and 1 retaining clip Two Universal Mounting Clamp Assemblies are required for all mounting configurations Figure 12 Mounting Anti rotation Bracket to Actuator AM 751 Anti rotation bracket 90 Actuator mounting slot 90 ...

Page 13: ...ctuator is 90 perpendicular to the damper shaft Then hand tighten the nuts on both of the actuator s universal mounting clamps See Figure 12 Note If the universal shaft extension protrudes excessively above the damper actuator s top universal mounting clamp remove the damper actuator from the universal shaft extension remove the extension from the damper shaft shorten the universal shaft extension...

Page 14: ...circuits Table 3 Control and Power Wiring Data Table 4 Wire Color Codes for Models Manufactured before December 2007 Figure 13 Installation of Universal Shaft Extension Actuator Anti rotation Bracket included with actuator AM 753 Universal Mounting Clamps Duct V clamp Mounting Surface Damper Shaft AM 676 Universal Shaft Extension 1 1 The AM 676 extends the damper shaft approximately 9 229 mm Actua...

Page 15: ...ontroller output to minimum 5 Check to see that the actuator travels to the fully closed position Note If anticipated damper operation does not occur verify the Long Damper Shaft or Short Damper Shaft mounting procedures Also verify that the controller has the proper action direct or reverse to match the damper required operation THEORY OF OPERATION The actuator is by means of dual mounting clamps...

Page 16: ...ctive owners Information contained within this document is subject to change without notice F 26748 4 www tac com TAC 1354 Clifford Avenue P O Box 2940 Loves Park IL 61132 2940 DIMENSIONAL DATA Figure 14 dimensions are in inches mm Figure 14 MS40 717X Damper Actuator 4 102 4 102 1 27 64 36 10 27 32 275 R ...

Reviews: