AC-3301L MANUAL
14
Name
Image
Setting screen
Name
Image
Setting screen
Up button
Move to top menu
(Press short: Move slowly)
(Press long : Move quickly)
Down
button
Move to bottom menu
(Press short: Move slowly)
(Press long : Move quickly)
Increase
button
Increase setting value
(Press short: Change slowly)
(Press long : Change quickly)
Decrease
button
Decrease setting value
(Press short: Change slowly)
(Press long : Change quickly)
Save
button
Save setting value
(Press short)
Setting
button
Cancel setting value
(Press short)
Setting Details Description
Item
Set. range Initial value
Contents
Set Temp
1.0 ~
75.0℃
24.0℃
Set the control temperature of the air conditioner.
Cooling
Diff
0.1 ~
5.0℃
1.0℃
Set the operation and stop deviation of cooling operation by the cooling
deviation temperature for set temperature.
(Current temperature ≥ (Setting tempe cooling variation)
(Setting temperature : 15℃ / Cooling variation : In the case of 1℃, cooling
operation ON when current temperature is more 16℃ cooling operation when
current temperature is less 15℃ OFF.)
Heating
Diff
0.1 ~
5.0℃
1.0℃
Set the heating operation for temperature compensation when the
temperature of the room drops due to overcooling.
(Current temperature ≤ (Setting temperature
–
heating variation)
(Setting temperature : 15℃ / heating variation : In the case of 1℃, heating
operation ON when current temperature is less 14℃ heating operation when
current temperature is more 15℃ OFF)
General Setting
Setting Operation
Summary of Contents for AC-3301L
Page 21: ...AC 3301L MANUAL 21...