SystemAir TopVex TX03 Operation And Maintenance Instructions Download Page 14

 

 

_____________________________________________________________________________________________________ 

Topvex TX03-06 

 

 Operation and Maintenance instructions 

 

205875

 

 

Systemair AB

 

14

Troubleshooting 

Should problems occur, please check or correct the following before contacting your service representative. 
Always check if there are any alarms active in the control panel. 

 

1. Fan(s) do not start 

  Check that the fuses are not defect 

  Check the settings in the control panel (times, week schedule, auto/manual operation etc.) 

  Check if there are any alarm messages 

 

2. Reduced airflow 

  Check the settings of Medium and Low fan speed 

  Check that the Outdoor/Exhaust air damper (if used) opens 

  Change of filters required? 

  Cleaning of diffusers/louvers required? 

  Cleaning of fans/exchanger block required? 

  Is the roof unit/air intake clogged? 

  Check ducts for visible damage and/or build up of dust/pollution  

  Check diffuser/louver openings. 

 

3. Cold supply air 

  Check the control temperature on the control panel 

  Check if the overheating thermostat has tripped. If necessary press the red button, marked RESET, 

on top of the electric heater connection box, see fig. 7 on page 13 in the 

installation description

.   

  Check if the extract filter must be changed 

  Check if the fans have stopped due to overheating. If so the thermal contact might have tripped 

(shows as “

Fan alarm

” in the control panel). If necessary reset (see page 6 

Alarms-overview

 

4. Noise/vibrations 

  Clean the fan impellers 

  Pull the two fans out and check that the 2 screws holding the fans are tightened. 

 

 

Service 

Before calling your service representative, make a note of the specification and production number from the 
type label 

(fig. 5).

 

 

 
  
 
 
 
 

 
 
 
Fig. 5 

 

Code explanation  

1: Item number  
2: Production order number 
3: Consecutive number 
4: Production date 
5: Product code (product specification) 

 

1

5

Summary of Contents for TopVex TX03

Page 1: ...Corrigo ver no 1 2 1 00 Topvex TX03 TX04 TX06 Compact Air Handling Unit Operation and Maintenance instructions GB GB...

Page 2: ...of contents 2 Warning 2 Operation 3 General 3 Free cooling 3 Defrost function general description 4 Defrost levels 4 Shortcut to set the menu language 5 Control panel 5 How to operate 5 Navigating th...

Page 3: ...owing criteria are met simultaneously all time channels are in OFF position and that the unit goes back to normal operation the following day set operation time during the following 24 hours the avera...

Page 4: ...preset number of minutes the by pass damper inside the unit opens to help reduce the flow of the cold outdoor air through the heat exchanger block As this cycle is initiated the set supply air tempera...

Page 5: ...arm LED 7a Yellow cable 3 Write enable LED 7b Orange cable 4 OK button 7c Red cable 5 Clearing button 7d Brown cable 6 Mounting holes 7e Black cable Fig 1 How to operate The menus in the Corrigo E con...

Page 6: ...menus through which you may move using the UP DOWN buttons Sometimes there are further sub menus linked to a menu or menu item This is indicated by an arrow symbol at the right hand edge of the displ...

Page 7: ...emperature value 16 30 C Running mode Set the running mode of the unit Choose between Auto Manual high Manual medium Manual low or Manual shut off Time Date Set the present time date and weekday Set t...

Page 8: ...or Not Active Preset is Not Active Function Closes the by pass damper to allow recovery of the cold extract air Is activated when the extract air temperature is 3K lower than the outdoor air temperatu...

Page 9: ...y air fan SAF in of maximum fan speed Choose between 0 to 100 All fan speeds LOW MEDIUM HIGH can be set in this interval Display shows Description Defrost function Set the By pass function to Yes or N...

Page 10: ...ignal 0 10V Set the status to Auto Manual or Off In Manual status it is possible to set the output signal within a range from 0 to10V more than 2V activates the electrical re heater on off function AO...

Page 11: ...is by pressing the OK button at the same time as the main voltage is switched on 4 Display unit type E DSP preset 5 Modbus Comm Not Active or Active Preset is Not Active Modbus Active Modbus address...

Page 12: ...d from Systemair Operation time between filter changes must be reset after filter change see page 8 Filter alarm To change the alarm activating time see page 8 Filter alarm Initial pressure drop over...

Page 13: ...s and louvers are mounted in ceilings walls in bedroom living room wet rooms WC etc Remove diffusers and louvers and wash in hot soapy water if required Diffusers louvers must be put back with their o...

Page 14: ...ake clogged Check ducts for visible damage and or build up of dust pollution Check diffuser louver openings 3 Cold supply air Check the control temperature on the control panel Check if the overheatin...

Page 15: ...el size Series no Filter replaces interval set Present time and date set Week scheduler settings Preset On time is Period 1 07 00 16 00 Monday Sunday Medium fan speed Period 2 00 00 00 00 Monday Sunda...

Page 16: ...35 of max Fan speed Fan speed Medium 75 of max Fan speed Fan speed Maximum 100 of max Fan speed Extended Forced running Running time 240 Minutes Minutes Filter alarm Replaces interval 6 Months Months...

Page 17: ..._____________________________________________________________________________________________________ Topvex TX03 06 Operation and Maintenance instructions 205875 Systemair AB 17 Notes...

Page 18: ...rights at any time without prior notice make changes and improvements to the contents of this manual Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99 www s...

Reviews: